Plan Review Details - Permit 05020853
Plan Review Stops For Permit 05020853
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-26 Cont ID  
Sent By adarroug Date 2005-04-26 Time 10:00 Rev Time 0.00
Received By adarroug Date 2005-04-26 Time 10:00 Sent To M
Notes
2005-04-26 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-15 Cont ID  
Sent By adarroug Date 2005-02-15 Time 11:29 Rev Time 0.00
Received By adarroug Date 2005-02-15 Time 11:29 Sent To M
Notes
2005-02-15 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-05-04 Cont ID  
Sent By pkrauss Date 2005-05-04 Time 07:05 Rev Time 0.30
Received By pkrauss Date 2005-05-04 Time 06:53 Sent To  
Notes
2005-05-04 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR SYSTEMS WHICH HAS THE
 DESIGN CAPACITY GREATER THAN 2,000 CFM
 OR WHEN THE AGGREATEAIR EXCEEDS 2,000
 CFM, PER 2001 FBC(M)606.2.1 & 606.2.5.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-02-22 Cont ID  
Sent By pkrauss Date 2005-02-22 Time 13:22 Rev Time 0.40
Received By pkrauss Date 2005-02-22 Time 13:22 Sent To  
Notes
2005-02-22 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR SYSTEMS WITH THE DESIGN
 CAPACITY GREATER THAN 2,000 CFM OR WHEN
 THE AGGREATE AIR EXCEEDS 2,000 CFM, PER
 2001 FBC(M)606.2.1 & 606.2.5,
 RESPECTIVELY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.