Plan Review Details - Permit 05020780
Plan Review Stops For Permit 05020780
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-27 Cont ID  
Sent By btrobaug Date 2006-02-27 Time 16:54 Rev Time 0.50
Received By btrobaug Date 2006-02-27 Time 13:05 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-17 Cont ID  
Sent By btrobaug Date 2006-02-17 Time 07:29 Rev Time 0.50
Received By btrobaug Date 2006-02-17 Time 06:33 Sent To PC
Notes
2006-02-17 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SINCE THE SERVICE HAS NOW BEEN
 CHANGED TO INCLUDE THE THE COTTAGE
 PLEASE SUBMIT ALL PANEL SCHEDULES SO
 THAT BRANCH CIRCUIT COMPLIANCE CAN BE
 DETERMINED.
  
 2} THE HOT TUB MUST BE INCLUDED IN THE
 CALCULATIONS. 220.31.
  
 3} INDICATE THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR(S), AND INDICATE
 GROUNDING ELECTRODE SYSTEM PER 250.52.
  
 4} 110.9 INTERRUPTING RATING.
 EQUIPMENT INTENDED TO INTERRUPT CURRENT
 AT FAULT LEVELS SHALL HAVE AN
 INTERRUPTING RATING SUFFICIENT FOR THE
 NOMINAL CIRCUIT VOLTAGE AND THE CURRENT
 THAT IS AVAILABLE AT THE LINE TERMINALS
 OF THE EQUIPMENT.
 EQUIPMENT INTENDED TO INTERRUPT CURRENT
 AT OTHER THAN FAULT LEVELS SHALL HAVE AN
 INTERRUPTING RATING AT NOMINAL CIRCUIT
 VOLTAGE SUFFICIENT FOR THE CURRENT THAT
 MUST BE INTERRUPTED. INDICATE RATING ON
 PLAN.
  
 5} A SMOKE DETECTOR IS REQUIRED AT THE
 STAIRWAY ON THE FIRST FLOOR TO COMPLY
 WITH NFPA-72 AND FBC 8-1.4.2. SEE
 PERMITED SET OF PLANS.
  
 6} THE PERSON RESPONSIBLE FOR THE PLAN
 MUST SIGN SAME.104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-02-25 Cont ID  
Sent By btrobaug Date 2005-02-25 Time 14:41 Rev Time 0.50
Received By btrobaug Date 2005-02-25 Time 14:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-24 Cont ID  
Sent By adarroug Date 2006-02-24 Time 11:54 Rev Time 0.00
Received By adarroug Date 2006-02-24 Time 11:54 Sent To E
Notes
2006-02-24 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-16 Cont ID  
Sent By adarroug Date 2006-02-16 Time 11:57 Rev Time 0.00
Received By adarroug Date 2006-02-16 Time 11:57 Sent To E
Notes
2006-02-16 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-14 Cont ID  
Sent By adarroug Date 2005-02-14 Time 10:21 Rev Time 0.00
Received By adarroug Date 2005-02-14 Time 10:21 Sent To E
Notes
2005-02-14 00:00:00TO "E" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved