| 2005-02-17 00:00:00 | PERMIT #05020722 |
| | |
| | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.) IMPACT FEES MAY BE DUE.THE PLANS |
| | MUST BE STAMPED AND THE RECEIPT ATTACHED |
| | TO THE APPLICATION.233-5025.DOR TO |
| | PROVIDE AREA CALCULATIONS (ADDITION |
| | SQUARE FOOTAGE) ON THE PLAN. |
| | |
| | 2.) THE OWNER ON THE APPLICATION DOESN?T |
| | MATCH THE OWNER IN OUR RECORDS, SEE |
| | ATTACHED. |
| | |
| | 3.) FBC*104.3.1.1, MINIMUM PLAN REVIEW |
| | CRITERIA FOR BUILDINGS, PLEASE PROVIDE |
| | OCCUPANCY GROUP, MINIMUM CONSTRUCTION |
| | TYPE, FIRE SUPPRESSION SYSTEM PLAN, |
| | OCCUPANCY LOAD. |
| | |
| | 4.) PROVIDE ENERGY CALCS, FBC13-103.1. |
| | |
| | 5.) THE BREAK ROOM SINK IS TO COMPLY |
| | WITH FBC11-4.24.PROVIDE A DETAIL. |
| | |
| | 6.) PROVIDE DETAILS FOR THE ACCESSIBLE |
| | BATHROOM (GRAB BARS, SINK, WC, WITH |
| | DIMENSIONS). |
| | |
| | 7.) WILL PARKING SPACES BE PROVIDED FOR |
| | EMPLOYEES?SEE FBC11-4.2(5)(A). |
| | |
| | 8.) SHOW THE ACCESSIBLE ROUTE, FROM |
| | ACCESSIBLE PARKING AND FROM THE PUBLIC |
| | WAY, 11-4.1.2. |
| | |
| | 9.) PROVIDE A WATERPROOFING DETAIL AT |
| | THE BASE OF THE WALL, A-A2.1. |
| | |
| | 10.) PLEASE CLARIFY AS TO WHY YOU |
| | SPECIFY A 45 MINUTE DOOR AND 1 ? HOUR |
| | WINDOWS. |
| | |
| | 11.) D-A2.1 SPECIFIES SMS SCREWS; |
| | PROVIDE UPLIFT INFORMATION AND SIZE, |
| | NUMBER OF FASTENERS. |
| | |
| | 12.) SIMPSON ST22 STRAPS SPECIFIED. |
| | THIS IS A WOOD CONNECTOR WHICH YOU ARE |
| | USING IN A METAL STUD APPLICATION. |
| | FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED FAC9B72. |
| | |
| | 13.) SPECIFY THE CONCRETE STRENGTH FOR |
| | THE CURB, D-A2.1. |
| | |
| | 14.) SPECIFY THE SIZE OF ALL FRAMING |
| | MEMBERS AND ATTACHMENTS.SEE ATTACHED |
| | CEILING SPAN TABLE. |
| | |
| | 15.) PLYWOOD (COMBUSTIBLE) IS NOT |
| | ALLOWED IN A TYPE II BUILDING; APPEARS |
| | ON SEVERAL DETAILS. |
| | |
| | 16.) THE INTERIOR WALLS AND HEADER |
| | (A-A2.1, C-A2.1) DO NOT COMPLY WITH THE |
| | 2 HOUR WALL DETAIL PROVIDED (THE TWO |
| | SHEETS OF DRYWALL MISSING AT THE |
| | FIREBLOCKING). |
| | |
| | 17.) D-A2.1, HOW DOES THE BRACING ATTACH |
| | TO THE DOUBLE T? |
| | |
| | 18.) D-A2.1, PROVIDE EMBEDMENT FOR THE |
| | EXPANSION ANCHOR AND THE #5 INTO THE |
| | SLAB. |
| | |
| | 19.) PROVIDE CLEARANCE INFORMATION FOR |
| | THE BIFOLD DOOR, FBC11-4.13.5. |
| | |
| | 20.) PROVIDE A BACKING DETAIL FOR THE |
| | GRAB BARS. |
| | |
| | 21.) PRODUCT APPROVALS AND TEST |
| | REPORTS/INSTALLATION INSTRUCTIONS |
| | REQUIRED FOR THE IMPACT PROTECTION, DOOR |
| | AND WINDOWS.STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED, FAC9B72. |
| | |
| | 21.) IMPACT PROTECTION REQUIRED, |
| | FBC1606.1.4. |
| | |
| | 22.) PROVIDE DESIGN INFORMATION ON THE |
| | PLAN, FBC1606.1.7. |
| | |
| | 23.) WHERE WILL THE SHUTTERS BE STORED? |
| | IF THEY ARE STORED VERTICALLY, PROVIDE A |
| | RACK DETAIL. |
| | |
| | 24.) SPECIFY ALL ATTACHMENTS FOR THE |
| | METAL FRAMING. |
| | |