Plan Review Details - Permit 05020722
Plan Review Stops For Permit 05020722
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-17 Cont ID  
Sent By shill Date 2005-02-17 Time 09:30 Rev Time 5.00
Received By shill Date 2005-02-17 Time 08:10 Sent To  
Notes
2005-02-17 00:00:00PERMIT #05020722
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) IMPACT FEES MAY BE DUE.THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED
 TO THE APPLICATION.233-5025.DOR TO
 PROVIDE AREA CALCULATIONS (ADDITION
 SQUARE FOOTAGE) ON THE PLAN.
  
 2.) THE OWNER ON THE APPLICATION DOESN?T
 MATCH THE OWNER IN OUR RECORDS, SEE
 ATTACHED.
  
 3.) FBC*104.3.1.1, MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS, PLEASE PROVIDE
 OCCUPANCY GROUP, MINIMUM CONSTRUCTION
 TYPE, FIRE SUPPRESSION SYSTEM PLAN,
 OCCUPANCY LOAD.
  
 4.) PROVIDE ENERGY CALCS, FBC13-103.1.
  
 5.) THE BREAK ROOM SINK IS TO COMPLY
 WITH FBC11-4.24.PROVIDE A DETAIL.
  
 6.) PROVIDE DETAILS FOR THE ACCESSIBLE
 BATHROOM (GRAB BARS, SINK, WC, WITH
 DIMENSIONS).
  
 7.) WILL PARKING SPACES BE PROVIDED FOR
 EMPLOYEES?SEE FBC11-4.2(5)(A).
  
 8.) SHOW THE ACCESSIBLE ROUTE, FROM
 ACCESSIBLE PARKING AND FROM THE PUBLIC
 WAY, 11-4.1.2.
  
 9.) PROVIDE A WATERPROOFING DETAIL AT
 THE BASE OF THE WALL, A-A2.1.
  
 10.) PLEASE CLARIFY AS TO WHY YOU
 SPECIFY A 45 MINUTE DOOR AND 1 ? HOUR
 WINDOWS.
  
 11.) D-A2.1 SPECIFIES SMS SCREWS;
 PROVIDE UPLIFT INFORMATION AND SIZE,
 NUMBER OF FASTENERS.
  
 12.) SIMPSON ST22 STRAPS SPECIFIED.
 THIS IS A WOOD CONNECTOR WHICH YOU ARE
 USING IN A METAL STUD APPLICATION.
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED FAC9B72.
  
 13.) SPECIFY THE CONCRETE STRENGTH FOR
 THE CURB, D-A2.1.
  
 14.) SPECIFY THE SIZE OF ALL FRAMING
 MEMBERS AND ATTACHMENTS.SEE ATTACHED
 CEILING SPAN TABLE.
  
 15.) PLYWOOD (COMBUSTIBLE) IS NOT
 ALLOWED IN A TYPE II BUILDING; APPEARS
 ON SEVERAL DETAILS.
  
 16.) THE INTERIOR WALLS AND HEADER
 (A-A2.1, C-A2.1) DO NOT COMPLY WITH THE
 2 HOUR WALL DETAIL PROVIDED (THE TWO
 SHEETS OF DRYWALL MISSING AT THE
 FIREBLOCKING).
  
 17.) D-A2.1, HOW DOES THE BRACING ATTACH
 TO THE DOUBLE T?
  
 18.) D-A2.1, PROVIDE EMBEDMENT FOR THE
 EXPANSION ANCHOR AND THE #5 INTO THE
 SLAB.
  
 19.) PROVIDE CLEARANCE INFORMATION FOR
 THE BIFOLD DOOR, FBC11-4.13.5.
  
 20.) PROVIDE A BACKING DETAIL FOR THE
 GRAB BARS.
  
 21.) PRODUCT APPROVALS AND TEST
 REPORTS/INSTALLATION INSTRUCTIONS
 REQUIRED FOR THE IMPACT PROTECTION, DOOR
 AND WINDOWS.STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.
  
 21.) IMPACT PROTECTION REQUIRED,
 FBC1606.1.4.
  
 22.) PROVIDE DESIGN INFORMATION ON THE
 PLAN, FBC1606.1.7.
  
 23.) WHERE WILL THE SHUTTERS BE STORED?
 IF THEY ARE STORED VERTICALLY, PROVIDE A
 RACK DETAIL.
  
 24.) SPECIFY ALL ATTACHMENTS FOR THE
 METAL FRAMING.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-17 Cont ID  
Sent By dpalmer Date 2005-02-17 Time 06:05 Rev Time 0.25
Received By dpalmer Date 2005-02-15 Time 04:44 Sent To  
Notes
2005-02-17 00:00:00************ UNSAT **********
  
 1)NOTE: PLEASE SEE FS 471.003(2)(H)2A.
 PLANS FOR NEW ELECTRICAL SYSTEMS FOR
 277/480V MUST BE DONE AND SIGNED,DATED
 AND SEALED BY AN PE.
  
 2)NOTE: PLEASE PROVIDE GROUNDING FOR NEW
 TRANSFORMER. PLEASE SEE 250.30
  
 3)NOTE: PLEASE SEE PLANS APPEAR TO SHOW
 TRANSFORMER IN THE CLEARENCE ARE
 REQUIRED FOR PANEL PER 110.26?
  
 4)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS (LIGHTING) AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.
 PLEASE ALSO SEE 700.12E
  
 5)NOTE: PLEASE SEE CONDUCTORS SHOWN FOR
 FEED FROM NEW 60A DISC TO TRANSFORMER.
 PLEASE SEE EQUIPMENT GROUNDING CONDUCTOR
 APPEARS TO BE SHOWN AS A 4/0?
 PLEASE VERIFY.
 250.122
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATING SHOWN FOR PANEL , NEEDED FOR
 MAIN DISC.
  
 7)NOTE: PLEASE SEE PANEL INDICATES
 270V/480V. 270V APPEARS TO BE A
 MISPRINT.
  
 8)NOTE: PLEASE PROVIDE CONDUCTOR SIZES
 AND LOAD CALCULATIONS FOR EXISTING
 WIREWAY IN WHICH NEW FEED IS BEING
 TAPPED FROM.
 220,215.5
  
 9)NOTE: PLEASE SEE MISSING GFI FOR COND
 UNIT SERVICE RECEPT. 210.63
  
 10)NOTE: PLEASE SHOW LOCATION OF NEW
 DISC AT OFFICE BLDG ON LINE SIDE OF
 TRANSFORMER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-02-14 Cont ID  
Sent By mamini Date 2005-02-14 Time 09:14 Rev Time 0.50
Received By mamini Date 2005-02-14 Time 09:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-02-11 Cont ID  
Sent By mwennerg Date 2005-02-11 Time 10:59 Rev Time 0.00
Received By mwennerg Date 2005-02-11 Time 10:58 Sent To  
Notes
2005-02-11 00:00:001) PLEASE SUBMIT SEPARATE SHOP DRAWINGS
 FOR THE FIRE ALARM AND FIRE SPRINKLER
 REMODEL.
  
 ALL WORK SHALL COMPLY WITH THE 2003
 EDITION OF THE LIFE SAFETY CODE AFTER
 JANUARY 1, 2005.
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-11 Cont ID  
Sent By adarroug Date 2005-02-11 Time 09:01 Rev Time 0.00
Received By adarroug Date 2005-02-11 Time 09:01 Sent To  
Notes
2005-02-11 00:00:00TO "COMM"BD #25

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2005-03-12 Time   Rev Time 0.00
Received By hmoser Date 2005-03-12 Time 06:59 Sent To  
Notes
2005-03-12 00:00:00PLAN DENIED
 1) NO DUCT SIZE ON RETURN AIR.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-02-19 Cont ID  
Sent By kstevens Date 2005-02-19 Time 15:33 Rev Time 0.64
Received By kstevens Date 2005-02-19 Time 15:33 Sent To  
Notes
2005-02-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SUBMIT A SANITARY RISER DIAGRAM IN
 ISOMETRIC FORM SHOWING ALL PIPE SIZES,
 VENTS, CLEANOUTS, AND INDICATE POINT OF
 CONNECTION. SECTION 1-4.3.1.1.
 2) SUBMIT A WATER RISER DIAGRAM
 ISOMETRIC SHOWING ALL PIPE SIZES,
 VALVES, WATER HAMMER ARRESTORS REQUIRED
 BY SECTION 604.9, AND INDICATE POINT OF
 CONNECTION. SECTION 104.2.1.1.
 3) SUBMIT A ACCESSIBLITY DETAIL FOR THE
 TOILET ROOM SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 4) SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL
 SUBSTECTIONS. (FORWARD APPROACH
 REQUIRED)
 5) WATER COOLER SHALL COMPLY WITH
 ARI-1010 PER SECTION 410.1. SUBMIT
 MANUF. SPECIFICATION SHEET SHOWING
 COMPLIANCE.
 6) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO PARKING GARAGE OFFICE.
 SECTION 608.13.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2005-03-11 Cont ID  
Sent By eschneid Date 2005-03-11 Time 16:30 Rev Time 0.25
Received By eschneid Date 2005-03-11 Time 16:15 Sent To  
Notes
2005-03-11 00:00:001) NEW OFFICE REQUIRES APPROVAL OF A
 MINOR PD AMENDMENT.
 2) ACCURATE SITE PLAN IS REQUIRED
 SHOWING ALL DIMENSIONS AND FEATURES FOR
 THE NEW BUILDING AND REDESIGNED PARKING
 AREA.
 3) REVISED PARKING CLACULATIONS ARE
 REQUIRED.
 CONTACT ERIC SCHNEIDER (561) 822-1435.