Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-18 Cont ID  
Sent By btrobaug Date 2005-02-18 Time 12:19 Rev Time 0.50
Received By btrobaug Date 2005-02-18 Time 11:10 Sent To  
Notes
2005-02-18 00:00:00 
 PLEASE NOTE THE FOLLOWING REQUIREMENTS
 FOR CODE COMPLIANCE MUST REFLECT ON
 DRAWINGS.
  
 1} THE DISCONNECTS FOR THE SERVICE
 EQUIPMENT SHALL BE GROUPED PER 230.72.
  
 2} INDICATE THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR PER 250.66.
  
 3} INDICATE THE AIC RATING OF THE
 SERVICE EQUIPMENT PER 110.9 & 110.10.
  
 4} THE PANEL ON THE SECOND FLOOR MAY NOT
 BE LOCATED IN THE CLOSET. SEE 110.26 AND
 408.7 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-07 Cont ID  
Sent By adarroug Date 2005-03-07 Time 13:10 Rev Time 0.00
Received By adarroug Date 2005-03-07 Time 13:10 Sent To E
Notes
2005-03-07 00:00:00TO BTROBAUG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 09:02 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 09:02 Sent To E
Notes
2005-02-09 00:00:00TO "E"BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved