| Plan Review Stops For Permit 05020535 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-02-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-02-23 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-02-23 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2005-02-23 00:00:00 | 10,000 AIC RATING PER FPL/ OWNER. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-02-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-02-16 |
Time |
15:08 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-02-16 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2005-02-16 00:00:00 | ** UNSAT ** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-02-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-08 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-08 |
Time |
15:29 |
Sent To |
E |
|
| Notes |
| 2005-02-08 00:00:00 | TO "E"BOX |
|
|
|