Plan Review Details - Permit 05020338
Plan Review Stops For Permit 05020338
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-05-24 Cont ID  
Sent By jhiggins Date 2005-05-24 Time 09:37 Rev Time 0.00
Received By jwitmer Date 2006-05-30 Time 07:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-06-22 Cont ID  
Sent By jwitmer Date 2006-06-22 Time 08:30 Rev Time 0.55
Received By jwitmer Date 2006-06-22 Time 08:30 Sent To PC
Notes
2006-06-22 00:00:00POOL EQUIPMENT SLAB

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-05-30 Cont ID  
Sent By jwitmer Date 2006-05-30 Time 08:30 Rev Time 2.22
Received By jwitmer Date 2006-05-30 Time 07:46 Sent To  
Notes
2006-05-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05020338
 ADD: 1771 CITYSIDE DR
 CONT:WCI COMMUNITIES
 TEL: (561)662-3569
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THIS PERMIT IS FOR THE CLUBHOUSE
 ONLY! NO PERMIT FOUND FOR POOL EQUIPMENT
 PAVILION.
  
 2) TABLE 600 ISSUES, ASSUMED PROPERTY
 LINE BETWEEN (2) BUILDINGS WILL REQUIRE
 AN ASSUMED PROPERTY LINE, DEPENDING ON
 THE LOCATION, THE WINDOW IN THE
 CLUBHOUSE MAY MAY REQUIRE WORST CASE
 TO BE CLOSED UP, 45 MIN RATED OR NOT AT
 ALL. THE POOL EQUIPMENT PAVILION WOULD
 POSSIBLY REQUIRE A 1 HR RATING CLOSEST
 TO THE CLUBHOUSE.
  
 3) IT APPEARS THERE IS (3) POOL HEATERS,
 NO INFORMATION ON FLUES THROUGH THE
 ROOF?
  
 4) THIS IS A STAND ALONE PERMIT, THE A-1
 AND STRUCTURAL SHEETS REFRENCE SHEETS
 THAT PERTAIN TO THE CLUBHOUSE NOT THE
 POOL EQUIPMENT PAVILION.
  
 5)MISSING PRODUCT APPROVALS FOR THE ROOF
 SHINGLES AS WELL AS TRUSS ANCHORS.
  
 MORE COMMENTS MAY ARISE TO THE RESPONCE
 COMMENTS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-08-16 Cont ID  
Sent By jwitmer Date 2005-08-14 Time 13:13 Rev Time 2.22
Received By jwitmer Date 2005-08-14 Time 12:43 Sent To  
Notes
2005-08-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05020338
 ADD: 747 N CONGRESS
 CONT: WCI COMMUNITIES
 TEL: (561)775-2120
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 4TH REVIEW
 ACTION: REVIEWED/ PERMIT PRINTED
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-07-27 Cont ID  
Sent By jwitmer Date 2005-07-27 Time 18:29 Rev Time 0.77
Received By jwitmer Date 2005-07-27 Time 18:29 Sent To  
Notes
2005-07-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071368
 ADD: 809 N DIXIE HWY
 CONT: GABCO REMODELING, INC
 TEL: (561)644-1434
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION
 ACTION: DENIED
  
 1) PLAN SUBMITTAL IS MISSING THE SECOND
 MEANS OF EGRESS, (FIRE ESCAPE), THE
 NON-COMBUSTIBLE STAIR ASSEMBLY IS GONE
 FROM THE PLANS. FIRDT FLOOR THE
 DESIGNATED STORAGE AREA FOR THE STORM
 SHUTTERS HAS DISSAPEARED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-07-27 Cont ID  
Sent By jwitmer Date 2005-07-27 Time 17:56 Rev Time 0.77
Received By jwitmer Date 2005-07-27 Time 17:56 Sent To  
Notes
2005-07-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05030338
 ADD: 747 NCONGRESS ( CLUBHOUSE)
 CONT:WCI
 TEL: (561)775-2120
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THE ONLY PRODUCT APPROVALS SUBMITTED FOR
 REVIEW ARE THE AMERICAN WARMING &
 VENTILATION, WHICH DO NOT REQUIRE THE
 STATE APPROVAL.
  
 1) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) DOORS SWING & OVERHEAD
 C) STORM SHUTTERS IF GLAZED OPENINGS DO
  
 NOT HAVE LARGE MISSLE IMPACT TESTING
 D) TRUSS ANCHORS
 E) ROOFING ASSEMBLIES
  
 2) MISSING INFORMATION ON THE FACTORY
 BUILT FIREPLACE & CHIMNEY?
 2806.1.2 FACTORY BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH AND
 MEET THE REQUIREMENTS OF UL 127.
 CHIMNEYS FOR THE USE WITH FACTORY-
 BUILT FIREPLACES SHALL MEET THE
 REQUIREMENTS OF UL 127.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-06 Cont ID  
Sent By jwitmer Date 2005-06-06 Time 16:10 Rev Time 0.00
Received By jwitmer Date 2005-07-27 Time 17:56 Sent To  
Notes
2005-06-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05020338
 ADD:747 N CONGRESS AVE
 CONT: WCI COMMUNITIES
 TEL: (561)662-3569
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 2NDREVIEW
 ACTION: DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 2) SUBMIT LOCALPRODUCT APPROVAL
 FOR AMERICAN WARMING & VENTILATION
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-20 Cont ID  
Sent By jwitmer Date 2005-03-20 Time 06:43 Rev Time 0.00
Received By jwitmer Date 2005-03-20 Time 06:37 Sent To  
Notes
2005-03-12 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05030338
 ADD: 747 NCONGRESS ( CLUBHOUSE)
 CONT:WCI
 TEL: (561)775-2120
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PLEASE INDICATE THE CHANGE OF GRADE
 FOR ACCESSIBLE ENTRANCES INTO THE
 BUILDING. 11-4.1.3(1) AT LEAST ONE
 ACCESSIBLE ROUTTE COMPLYING WITH 11-4.3
 SHALL CONNECT ACCESSIBLE BUILDING OR
 FACILITY ENETRANCES WITH ALL ACCESSIBLE
 SPACES AND ELEMENTS WITHIN THE BUILDING
 OR FACILITY. PROVIDE ACCESIBLE ROUTE.
  
 2) THEATER INDICATES RAISED PLATFORMS:
 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIABLE
 GRADE LEVEL.ALSO INDICATE COMPANION
 SEATING.
  
 3)11-5.2 COUNTERS AND BARS
 WHERE FOOD OR DRINK IS SERVED @ COUNTERS
 EXCEEDING 34" IN HEIGHT FOR CONSUMPTION
 BY CUSTOMERS SEATED ON STOOLS OR STAND-
 ING AT THE COUNTER, A PORTION OF THE
 MAIN COUNTER WHICH IS 60" IN LENGTH MIN-
 IMUM SHALL BE PROVIDED IN COMPLIANCE
 WITH 11-4.32 OR SERVICE SHALL BE AVAIL-
 ABLE AT ACCESSIBLE TABLES WITHIN THE
 SAME AREA.
  
 4) 11-4.24.2 SINKS, HEIGHT. SINKS
 SHALL BE MOUNTED WITH THE COUNTER NO
 HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 5) 2806.1.2 FACTORY BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH AND
 MEET THE REQUIREMENTS OF UL 127.
  
 6) 2804.4.1 FACTORY-BUILT CHIMNEYS
 FACTORY BUILT CHIMNEYS SHALL BE LISTED
 AND SHALL BE INSTALLED IN ACCORDANCE
 WITH THE CONDITIONS OF THE LISTING, AND
 MANUFACTURER'S INSTRUCTION.CHIMNEYS
 FOR THE USE WITH FACTORY- BUILT
 FIREPLACES SHALL MEET THE REQUIREMENTS
 OF UL 127.
  
 7) PLEASE INDICATE COMPLIANCE WITH
 DEPARTMENT OF HEALTH RULE 64E-9 PUBLIC
 SWIMMING POOLS FOR "EFFECTIVE BARRIER"
 BETWEEN POOL AND CLUBHOUSE.FBC 424.1.
  
 8) COMPILE PLANS INTO "SETS" INSERT
 A-11 THROUGH A-13 INTO THE SET OF PLANS.
  
 9) PROVIDE SOILS REPORT (3):
 FL BLD CODE 1804.2.2 QUESTIONABLE SOILS,
 WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 10) ATTIC VENTILATION 2309.7.1/ 103.7
 ALTERNATE MATERIALS & METHODS,
 WILL BE PERMITTED:
 1) UNVENETED ATTIC SYSTEMS/ASSEMBLIES
 ARE DESIGNED BY A FLORIDA REGISTERED
 DESIGN PROFESSIONAL.
 2) INSULATION MUST BE CONTINUOUSLY IN
 THE UPPER PLANE OF THE ROOF ASSEMBLIES
 DECK/ SHEATHING WITH SPECIFIED, APPROVED
 INSULATION PRODUCTS, AND THE CEILING
 PLANE (SPACE) IS NOT SEPERATED FROM THE
 CONDITIONED HABITABLE SPACE BELOW, WITH
 INSULATION.
 3) WHEN UNVENTED ATTIC SYSTEMS ARE
 SPECIFIED IN CONJUNCTION WITH ASPHALT
 BASED ROOFING PRODUCTS, THE ROOFING
 MATERIAL/ SYSTEM MANUFACTURER SHALL
 PROVIDE AN AFFIDAVIT CERTIFYING USE OF
 THEIR PRODUCT OVER UNVENTED ATTIC
 SYSTEMS.
 IF THESE 3 LISTED QUALIFIERS ARE MET THE
  
 PALM BEACH COUNTY BUILDING BOARD
 ADVISORY BOARD HAS APPROVED THIS
 INSTALLATION UNDER 103.7.PROVIDE
 DOCUMENTATION.
  
 11) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A)SINGLE HUNG WINDOWS
 B) OVERHEAD GARAGE DOOR
 C) LOUVERS
 D) BAHAMA STYLE STORM SHUTTERS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 12) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A-9 SECTION Q INDICATES A LOAD BEARING
 WALL WITH TRUSSES ABOVE S4 DETAIL 8
 INDICATES THE SAME SECTION BUT NO
 MENTION OF HOW TO STRAP THE TRUSSES
 ABOVE? DETAIL # 8 ON STRUCTURAL
 INDICATES THERE IS NO UPLIFT EXPLAIN?
  
 13) CORRECT S6 WIRE LATH NOTES REFRENCE
 TO 2507& 2507.3 BOTH THESE SECTIONS DEAL
 WITH THE HIGH VELOCITY HURRICANE ZONES,
 SHEET S6 FASTENER SCHEDULE: WIRE LATH
 & 3/8" METAL RIB LATH THE SECTIONS
 QOUTED 2507 ARE THE HIGH VELOCITY HURRI-
 CANE ZONE. THE CORRECT SECTION IS
 2504.2.2 INSTALLATION OF EXTERIOR LATH-
 ING AND FRAMING SHALL COMPLY WITH ASTM
 C-1063.THE FIRST QUESTION IS FOR THE
 WIRE LATH, DIAMOND MESH WHAT WILL THE
 MINIMUM WEIGHT BE OF THE METAL PLASTER
 BASE? SEE FOOTNOTE "D" ON VERTICAL APPLI
 CATIONS, WIRE LATH SHALL BE FURRED AWAY
 FROM VERTICAL SUPPORTS OR SOLID SHEATH-
 ING AT LEAST 1/4". ONCE THE MINIMUM
 WEIGHT IS KNOWN WHAT IS THE MAXIMUM
 CENTER TO CENTER, WALLS AND CEILINGS.
 CORRECT MINIMUM EMBEDMENT FOR VERTICAL
 AND HORIZONTAL APPLICATIONS AND SPACING
 OF FASTENER.PROVIDE THE ACTUAL
 DIAMETER & LENGHT OF NAILSREQUIRED FOR
 FLAT WIRE LATH AND RIBBED LATH BOTH FOR
 HORIZONTAL AND VERTICAL SURFACES. WE
 ALSO NEED TO KNOW THE WEIGHT OF THE WIRE
 LATH SPECIFIED FOR HRIZONTAL RUNS FOR
 SPAN LIMITATION. THE CODE REFERS YOU TO
 ASTM C-1063 TO LOCATE THE REQUIRED SPANS
 WEIGHT AND NAIL PENETRATION REQUIRED FOR
 EACH APPLICATION.
  
 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-06-02 Cont ID  
Sent By dpalmer Date 2006-06-02 Time 07:14 Rev Time 0.00
Received By dpalmer Date 2006-06-02 Time 07:14 Sent To  
Notes
2006-06-02 00:00:00REVISED AND CORRECTED E-5.1.
 PLANS ARE NOT TO BE RELEASED WHEN ALL
 REVIEWS ARE DONE. DUE TO THE BUILDING
 REVIEW FAILING, ALL PME PLANS MUST BE
 SEPARATE AND ONE SET OF PME'S MUST BE
 RETAINED FOR OFFICE FILE COPIES.
 DO NOT RELEASE PLANS>

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-04-24 Cont ID  
Sent By dpalmer Date 2006-04-24 Time 17:26 Rev Time 0.00
Received By dpalmer Date 2006-04-24 Time 17:17 Sent To  
Notes
2006-04-24 00:00:00********** UNSAT *********
  
 1)NOTE: PLEASE SEE REVISION IN TITLE
 MENTIONS CHNAGED TO SINGLE PHASE
 SERVICE, HOWEVER PLEASE SEE MAIN IS
 STILL SHOWN AS 3-PHASE.
 PLEASE ALSO SEE FEEDERS ON MDP SCHEDULE
 TO "PP" IS SHOWN FOR 3-PHASE, HOWEVER
 RISER IS CORRECT FOR SINGLE PHASE.
 PLEASE MAKE NECESSARY CORRECTTIONS AND
 CORRELATE.
 PLEASE ALSO EXPLAIN THE USE OF "XX" AT
 MCB.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-03-16 Cont ID  
Sent By dpalmer Date 2006-03-16 Time 18:31 Rev Time 0.00
Received By dpalmer Date 2006-03-16 Time 17:55 Sent To  
Notes
2006-03-16 00:00:00REDLINED,
  
 MCB IN MDP, UNCLEAR AS MDP SHOWS 1000AMP
 3-POLE, "XX"?
 230.70

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-05-19 Cont ID  
Sent By dpalmer Date 2005-05-19 Time 08:26 Rev Time 0.50
Received By dpalmer Date 2005-05-19 Time 07:36 Sent To  
Notes
2005-05-19 00:00:00REDLINED 250.6,250.24

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-23 Cont ID  
Sent By dpalmer Date 2005-02-23 Time 07:12 Rev Time 0.50
Received By dpalmer Date 2005-02-23 Time 07:11 Sent To  
Notes
2005-02-23 00:00:00************ UNSAT *********
  
 1)NOTE: PLEASE SEE LOAD CALCULATIONS
 SUBMITTED ARE FOR A SFR?
 PLEASE SHOW LOAD CALCULATIONS FOR A
 COMMERCIAL BLDG.P
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 2)NOTE: PLEASE SEE 250.6,250.24,
 EQUIPMENT GRNDS ARE NOT INSTALLED BEFORE
 FIRST MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE SEE 310.16 FOR RATING OF
 FEEDERS FROM 400A DISC TO PANEL PB-1,
 SHOWN AS 350 MCM? ON 400A FUSES.
  
 4)NOTE: PLEASE PROVIDE LIGHTING /
 RECEPTS FOR AHU'SPER 210.70, 210.63
  
 5)NOTE: PLEASE SEE 210.8(B)(3) IN THE
 2002 NEC. THIS REQUIRES ALL 15- AND
 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-02-07 Cont ID  
Sent By mamini Date 2005-02-07 Time 15:23 Rev Time 0.50
Received By mamini Date 2005-02-07 Time 15:23 Sent To  
Notes
2005-02-07 00:00:00PASSED:
  
 1. SEE PERMIT # 03101412 FOR
 UNDERGROUND UTILITIES AND SITE WORK
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2006-06-08 Cont ID  
Sent By mwennerg Date 2006-06-08 Time 10:21 Rev Time 0.00
Received By mwennerg Date 2006-06-08 Time 10:21 Sent To  
Notes
2006-06-08 00:00:00******PROVISO******
  
 1) PLEASE NOTE THAT ANY REVISIONS MADE
 TO THE FIRE SPRINKLER SYSTEM SHOULD BE
 SUBMITTED BY THE FIRE SPRINKLER
 CONTRACTOR UNDER THE SEPARATE FIRE
 SPRINKLER PERMIT AND REVISIONS BE MADE
 TO THE FS SHOP DRAWINGS. THIS WILL THEN
 BECOME PART OF THE FIRE SPRINKLER FILE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2006-04-06 Cont ID  
Sent By mwennerg Date 2006-04-06 Time 15:45 Rev Time 0.00
Received By mwennerg Date 2006-04-06 Time 15:45 Sent To  
Notes
2006-04-06 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT ANY REVISIONS MADE
 TO THE FIRE SPRINKLER SYSTEM SHOULD BE
 SUBMITTED BY THE FIRE SPRINKLER
 CONTRACTOR UNDER THE SEPARATE FIRE
 SPRINKLER PERMIT AND REVISIONS BE MADE
 TO THE FS SHOP DRAWINGS. THIS WILL THEN
 BECOME PART OF THE FIRE SPRINKLER FILE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-07-28 Cont ID  
Sent By mwennerg Date 2005-07-28 Time 14:51 Rev Time 0.00
Received By mwennerg Date 2005-07-28 Time 14:51 Sent To  
Notes
2005-07-28 00:00:00******PASSED/PROVISO******
  
 IT IS UNDERSTOOD THAT THIS BUILDING
 DOESN'T MEET THE REQUIREMENT FOR A FULL
 FIRE ALARM SYSTEM. THE PLANS SHOW A FIRE
 SPRINKLER SYSTEM WHICH IS REQUIRED TO BE
 MONITORED. THE MONITORING SHALL BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE
 AND SEPARATE SHOP DRAWING AND PERMIT IS
 REQUIRED FOR THE FIRE SPRINKLER SYSTEM.
 THE DOUBLE CHECK DETECTOR ASSEMBLY FOR
 THE FIRE SPRINKLER SYSTEM SHALL BE
 ELECTRONICALLY SUPERVISED IN ADDITION TO
 SECURED BY CHAIN AND LOCK.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-06-02 Cont ID  
Sent By mwennerg Date 2005-06-02 Time 13:36 Rev Time 0.00
Received By mwennerg Date 2005-06-02 Time 13:35 Sent To  
Notes
2005-06-02 00:00:00****DENIED****
  
 1) PLEASE NOTE THAT YOUR RESPONSE TO
 COMMENT #1 ILLUSTRATES THE DIFFERENT
 TYPES OF INTERIOR FINISH
 CLASSIFICATIONS. PLEASE REFERENCE THE
 CLASSIFICATION THAT IS SPECIFIC IN
 REGARDS TO THIS PROJECT.
  
 2) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS WHERE
 PROVIDED, SHALL BE WIRED TO THE FIRE
 ALARM SYSTEM TO CAUSE A GENERAL FIRE
 ALARM CONDITION AND NOT SUPERVISORY
 SIGNAL.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE SPRINKLER AND
 FIRE ALARM SYSTEMS.
  
 4) NEW BUILDINGS ARE REQUIRED TO BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
  
 5) IN ADDITION TO ELECTRONIC
 SUPERVISION, A CHAIN AND LOCK MUST BE
 PROVIDED FOR THE DOUBLE CHECK DETECTOR
 ASSEMBLY.
  
 6) APPROVED PANIC HARDWARE SHALL BE
 INSTALLED ON DOORS SERVING AN OCCUPANT
 LOAD OF 100 OR MORE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-03-16 Cont ID  
Sent By nmccray Date 2005-03-16 Time 12:16 Rev Time 0.00
Received By nmccray Date 2005-03-16 Time 10:24 Sent To  
Notes
2005-03-16 00:00:00DENIED
  
 1) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 2) WHAT IS THE TOTAL OCCCUPANY LOAD
 UNDER A/C ? THIS BUILDING MAYBE REQUIRED
 TO BE FIRE SPRINKLERED.
  
 3) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINIMUM OF AT LEAST 6"
 NUMBERS ARE REQUIRED.
  
 4) PLEASE BE AWARE THAT WE ARE NOW UNDER
 NEW FIRE CODES EDITION (NFPA 101 LIFE
 SAFETY CODE 2003 EDITION).
  
  
 NATE MCCRAY, CAPTAIN
 561-805-6722 OR 561-835-2910

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 14:59 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 14:59 Sent To B
Notes
2006-08-03 00:00:00TO "JWITMER" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 12:48 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 12:48 Sent To B
Notes
2006-06-21 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-06-06 Cont ID  
Sent By adarroug Date 2006-06-06 Time 08:46 Rev Time 0.00
Received By adarroug Date 2006-06-06 Time 08:46 Sent To P
Notes
2006-06-06 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-05-22 Cont ID  
Sent By adarroug Date 2006-05-22 Time 14:39 Rev Time 0.00
Received By adarroug Date 2006-05-22 Time 14:39 Sent To  
Notes
2006-05-26 00:00:00TO "COMM" BD#2
2006-05-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-10 Cont ID  
Sent By adarroug Date 2006-04-10 Time 09:42 Rev Time 0.00
Received By adarroug Date 2006-04-10 Time 09:42 Sent To  
Notes
2006-05-25 00:00:005/25/06-FROM "COMM" BD TO "P"
2006-04-19 00:00:00TO "COMM" BD#50
2006-04-10 00:00:00WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-21 Cont ID  
Sent By adarroug Date 2006-02-21 Time 14:05 Rev Time 0.00
Received By adarroug Date 2006-02-21 Time 14:05 Sent To  
Notes
2006-03-16 00:00:00TO 'COMM" BD#21
2006-02-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-10 Cont ID  
Sent By adarroug Date 2005-08-10 Time 14:18 Rev Time 0.00
Received By adarroug Date 2005-08-10 Time 14:18 Sent To B
Notes
2005-08-10 00:00:00TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-01 Cont ID  
Sent By adarroug Date 2005-07-01 Time 16:34 Rev Time 0.00
Received By adarroug Date 2005-07-01 Time 16:34 Sent To  
Notes
2005-07-01 00:00:00TO "COMM" BD#43

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-18 Time 09:16 Rev Time 0.00
Received By adarroug Date 2005-05-05 Time 13:34 Sent To  
Notes
2005-05-18 00:00:00TO "COMM" BD#33/PLANS ON RACK
2005-05-05 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-07 Cont ID  
Sent By mjacobs Date 2005-03-22 Time 11:05 Rev Time 0.00
Received By pkrauss Date 2005-03-12 Time 07:47 Sent To  
Notes
2005-02-07 00:00:00TO "COMM BD#53"

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-05-11 Cont ID  
Sent By tgordon Date 2006-05-11 Time 14:01 Rev Time 1.00
Received By tgordon Date 2006-05-11 Time 14:01 Sent To  
Notes
2006-05-11 00:00:00REVISION TO MECH. PLANS PAGE M2.1 AND
 M6.1 .

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-04-04 Cont ID  
Sent By pkrauss Date 2006-04-04 Time 10:23 Rev Time 0.00
Received By pkrauss Date 2006-04-04 Time 10:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-07-26 Cont ID  
Sent By pkrauss Date 2005-07-26 Time 14:14 Rev Time 0.45
Received By pkrauss Date 2005-07-26 Time 14:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-05-28 Cont ID  
Sent By hmoser Date 2005-05-28 Time 14:00 Rev Time 0.00
Received By hmoser Date 2005-05-28 Time 12:54 Sent To  
Notes
2005-05-28 00:00:00PLAN DENIED
 1) PLEASE PROVIDE MANUFACTURES
 INSTALLATIONS INSTRUCTIONS FOR UNITS 1&8
 2) PLEASE MARK ALL DUCT SIZES ON THE
 PLANS
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-03-22 Cont ID  
Sent By pkrauss Date 2005-03-22 Time 10:30 Rev Time 0.00
Received By pkrauss Date 2005-03-22 Time 10:01 Sent To  
Notes
2005-03-22 00:00:00DENIED:
 1.AIR SIZING SUMMARY (MANUAL J) FOR
 AHU'S 1 & 8 INDICATE 5.1 TON UNIT AND
 THE EQUIPMENT SCHEDULE ON PLAN SHEET
 M6.1 INDICATE 3 TON UNIT FOR AHU 1 & 8.
  
 2.PLEASE NOTE, MANUAL J CALCULATIONS
 ARE MISSING FOR AHU 7 & 9.
  
 3.PLAN SHEET M2.1, PLEASE CLARIFY
 OUTSIDE AIR TO AHU'S 1, 3, 4, 5, 6, & 8.
 IT APPEARS THAT ONLY UNITS 7, 2, & 9
 HAVE OUTSIDE AIR.
  
 4.PLAN INDICATES RETURN AIR JUMPER
 FROM THE KITCHEN AREA.PLEASE NOTE PER
 2001 FBC(M) 403.2.2, AIR MAY BE
 TRANSFERRED TO KITCHEN AIR FOR THE
 PURPOSE OF MAKE-UP AIR. AIR FROM THE
 KITCHEN AIR SHALL NOT BE RECIRCULATED.
  
 5.DUCT SMOKE DETECTORS REQUIRED FOR
 SYSTEMS WITH THE AGGREGATE CAPACITY IS
 GREATER THAN 2,000 CFM.
  
 6.FAN SHUTDOW BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS PER 2001
 FBC(M) 606.4.1 EXCEPTION #2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-03-12 Cont ID  
Sent By hmoser Date 2005-03-08 Time   Rev Time 0.00
Received By hmoser Date 2005-03-12 Time 07:49 Sent To  
Notes
2005-03-12 00:00:00NO PLANS TO REVIEW.HM.

Review Stop P PLUMBING
Rev No 7 Status P Date 2006-09-06 Cont ID  
Sent By kstevens Date 2006-09-06 Time 17:28 Rev Time 0.00
Received By kstevens Date 2006-09-06 Time 17:28 Sent To  
Notes
2006-09-06 00:00:00RESTAMP OF SHTS P2.1 AND P3.1

Review Stop P PLUMBING
Rev No 6 Status P Date 2006-08-15 Cont ID  
Sent By kstevens Date 2006-08-15 Time 06:58 Rev Time 0.00
Received By kstevens Date 2006-08-15 Time 06:58 Sent To  
Notes
2006-08-15 00:00:00REVISIONS OK - SHTS P2.1 & P3.1 SANT.
 SEWER LINE TO POOL EQUIPMENT AND WATER
 LINE TO POOL EQUIPMENT WITH HOSE BIBBS
 IN TOILET ROOMS AND ONE HOSE BIBB
 OUTSIDE OF BLDG.

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-06-10 Cont ID  
Sent By kstevens Date 2006-06-10 Time 10:51 Rev Time 0.00
Received By kstevens Date 2006-06-10 Time 10:51 Sent To  
Notes
2006-06-10 00:00:00REVISION OK - SHTS P3.1 & P6.1 ADDED
 HOSE BIBBS AND ASSOCIATED PIPING.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-05-02 Cont ID  
Sent By kstevens Date 2006-05-02 Time 09:56 Rev Time 0.00
Received By kstevens Date 2006-05-02 Time 09:56 Sent To  
Notes
2006-05-02 00:00:00REVISION (3) OK SHTS P2.1, P3.1, P6.1

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-06-16 Cont ID  
Sent By kstevens Date 2005-06-16 Time 07:21 Rev Time 1.00
Received By kstevens Date 2005-06-16 Time 07:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-03-14 Cont ID  
Sent By kstevens Date 2005-03-14 Time 14:14 Rev Time 2.00
Received By kstevens Date 2005-03-14 Time 14:14 Sent To  
Notes
2005-03-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) TOILET AND BATHROOMS SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING THE FOLLOWING INFORMATION:
 W/C
 A) HEIGHT 11-4.16.3
 B) GRAB BARS 11-4.16.4
 C) FLUSH CONTROLS 11-4.16.5
 D) DISPENSERS 11-4.16.6
 URINAL
 A) HEIGHT 11-4.18.2
 B) FLUSH CONTROLS 11-4.18.4
 LAV
 A) HEIGHT & CLEARANCES 11-4.19.2
 B) EXPOSED PIPES & SURFACES 11-4.19.4
 C) FAUCETS 11-4.19.5
 SHOWERS
 A) SIZE AND CLEARANCES 11-4.21.2
 B) SEAT 11-4.21.3
 C) GRAB BARS 11-4.21.4
 D) CONTROLS 11-4.21.5
 E) SHOWER UNIT 11-4.21.6
 F) CURBS 11-4.16.7
 2) SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAINS SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 A) SPOUT HEIGHT 11-4.15.2
 B) SPOUT LOCATION 11-4.15.3
 C) CONTROLS 11-4.15.4
 D) CLEARANCES 11-4.15.5
 3) SHTS A-2 & A-3 SUBMIT CALCULATIONS
 FOR MINIMUM FACILITIES PER TABLES 1003.1
 AND 403.1. INDICATE IF THE THEATER HAS
 FIXED SEATING OR NOT, AND IF SO INDICATE
 THE NUMBER OF SEATS. INDICATE IF THE
 EXERCISE ROOM HAS EQUIPMENT IN IT OR
 NOT. SHOW SQUARE FOOTAGE FOR EACH AREA.
 (NOT REQUIRED IS TOILET ROOMS,
 BATHROOMS, MECH. ROOMS, STORAGE)
 4) SHTS P2.1 & P5.1 FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE RECEPTORS.
 EITHER A HUB DRAIN OR A FLOOR SINK IS
 REQUIRED TO DRAIN THE ICE MACHNIE
 CONDENSATE. SECTION 802.3 OR 802.3.2.
 5) SHT P3.1 SHOWS2 EWH-1'S. PLEASE
 CLARIFY. SECTION 104.2.1.
 6) SHT P6.1 DOMESTIC WATER ISOMETRIC,
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE", NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALL.
 INSTRUCTIONS.
 7) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE OF THE CLUBHOUSE. SECTION
 608.13.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-12 Cont ID  
Sent By kstevens Date 2005-03-12 Time 14:27 Rev Time 0.33
Received By kstevens Date 2005-03-12 Time 14:27 Sent To  
Notes
2005-03-12 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 NO ARCHITECTURAL OR PLUMBING PLANS
 SUBMITTED TO DO A PLAN REVIEW. PLEASE
 SUBMIT ALL REQUIRED PLANS TO BUILD THE
 CLUBHOUSE. SECTION 104.2.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
 FOUND PLANS IN FIRE CUBICLE NEW REVIEW
 TO FOLLOW KSTEVENS
  
  
  
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2005-07-28 Cont ID  
Sent By eschneid Date 2005-07-28 Time 16:30 Rev Time 0.50
Received By eschneid Date 2005-07-28 Time 16:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-06-14 Cont ID  
Sent By eschneid Date 2005-06-14 Time 09:44 Rev Time 0.25
Received By eschneid Date 2005-06-14 Time 09:30 Sent To  
Notes
2005-06-14 00:00:001) SUBMIT APPROVED REVISED SITE PLAN
 DATED 2/23/05.
 2) SUBMIT APPROVED REVISED LANDSCAPE
 PLAN DATED 3/28/05.
 3) BUILDING FOOTPRINT ON SURVEY DOES NOT
 MATCH THE APPROVED SITE AND LANDSCPE
 PLANS NOR THE BUILDING FLOOR PLAN.
 4) SURVEY SHOWS DRAINAGE EASEMENT UNDER
 THE CLUBHOUSE.THE BUILDING MAY NOT SIT
 ON THE EASEMENT.
 CONTACT ERIC SCHNEIDER @ 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2005-02-08 Cont ID  
Sent By eschneid Date 2005-02-08 Time 15:45 Rev Time 0.75
Received By eschneid Date 2005-02-08 Time 15:00 Sent To  
Notes
2005-02-08 00:00:00PLANS SUBMITTED W/BUILDING PERMIT DO NOT
 MATCH APPROVED SITE AND LANDSCAPE PLANS,
 SPECIFICALLY ON THE SOUTH SIDE OF THE
 CLUBHOUSE:
 -ADDED SQUARE FOOTAGE FOR ELECTRICAL
 ROOM
 -ADDED POOL EQUIPMENT AND AC UNITS
 -ADDED DUMPSTER
 MINOR AMENDMENT REQUIRED FOR SITE AND
 LANDSCAPE PLAN CHANGES.
 DUMPSTER DOES NOT COMPLY WITH CITY
 STANDARDS.
 CONTACT ERIC SCHNEIDER @ 822-1435