| Plan Review Stops For Permit 05020282 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-07-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-07-27 |
Time |
09:33 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-07-27 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2005-07-27 00:00:00 | WORK CROSSED OFF ON THE PLAN WAS | | | PERMITTED SEPARATELY UNDER TRADE | | | PERMITS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-07-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-07-25 |
Time |
18:44 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-07-25 |
Time |
18:44 |
Sent To |
|
|
| Notes |
| 2005-07-25 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THE SITE PLAN HAS BEEN PREPARED BY | | | AN ARCHITECT BUT SEALED BY THE ENGINEER | | | OF RECORD.PLEASE SEE FAC61G15 IN | | | REGARDS TO SEALING ANOTHER | | | PROFESSIONAL'S WORK.HE CANNOT USE THE | | | COMMENT ON THE PLAN THAT THE SEAL | | | APPLIES TO LOCATION ONLY. | | | | | | 2.)TITLE BLOCK REQUIRED FOR THE | | | ENGINEER ON SHEET A3. | | | | | | 3.)MANY PLANS WERE SUBMITTED, | | | INCLUDING PLANS WHICH WERE NOT SEALED. | | | PLEASE KEEP ADDITIONAL COPIES AND ONLY | | | SUBMIT OLD REVIEWED PLANS AND THE SET | | | YOU ARE SUBMITTING FOR PERMITTING. | | | | | | 4.)SHEET M3 HAS THE COMMENT NEXT TO | | | THE SEAL "SEAL APPLIES TO AWNING AND | | | FENCE ONLY.CONSTRUCT REAMINDER TO REV | | | 3".PLEASE SUBMIT A PLAN OF WHAT YOU | | | WOULD LIKE TO BUILD, SIGNED AND SEALED, | | | FOR REVIEW.IT OTHERWISE APPEARS CODE | | | COMPLIANT. | | | | | | 5.)WHEN CHANGES ARE DONE TO THE PLAN, | | | CLOUD AND NUMBER THE REVISIONS TO | | | EXPEDITE PLAN REVIEW. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-03-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-03-23 |
Time |
10:44 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-03-23 |
Time |
10:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-02-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-02-15 |
Time |
11:58 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-02-15 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2005-02-15 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)PROVIDE DESIGN CRITERIA FOR THE | | | ANCHORING OF THE EQUIPMENT, FBC | | | 1606.1.7. | | | | | | 2.)THE "COMPRESSED AIR SYSTEM | | | FOUNDATIONS" STATES "PLACE ON PAVING." | | | DOES THIS MEAN THAT THE AIR RECEIVER IS | | | NOT ANCHORED?NO ANCHORING DETAIL | | | PROVIDED FOR THE AIR RECEIVER. | | | | | | 3.)SEPARATE PERMIT REQUIRED FOR THE | | | FENCE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2005-07-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-26 |
Time |
11:20 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-07-26 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2005-07-26 00:00:00 | REMOVED ELECTRICAL PLANS FROM BOTH SETS | | | PER DAVE BERINGER OF SOUTHEAST CONT. | | | ELECTRICLA NOT INCLUDE UNDER HIS SCOPE | | | PF WORK. | | | ELECTRICAL PLANS AND PERMIT WAS ISSUED | | | UNDER LIGHTNING ELECTRIC. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2005-03-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-03-22 |
Time |
16:14 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-03-22 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2005-03-22 00:00:00 | ELECTRICAL PERMIT APPLIED FOR SEPARATELY | | | FOR HOOKING UP OF COMPRESSED AIR | | | SYSTEM.BY LIGHTNING ELEC. | | | WAITING TO ISSUE PERMIT FOR LIGHTNING | | | ELECTRIC WHEN RUSSELL JENNING'S PERMIT | | | FROM LAST YEAR HAS BEEN FINALED AND | | | CLOSED OUT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-02-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-17 |
Time |
14:20 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-02-09 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2005-02-09 00:00:00 | ******* UNSAT ******* | | | | | | 1)NOTE: PLEASE SEE PERMIT APPLICATION | | | MENTIONS ELECTRICAL AND MECHANICAL TO BE | | | SUBMITTED SEPARATELY UNDER ELECTRICAL | | | CONTRACTOR ETC. PLEASE SEE PERMIT | | | APPLICATIONINDICATES WORK FOR | | | FOUNDATION AND STRUCTUAL WORK ONLY? | | | HOWEVER PLEASE SEE ONLY MECHANICAL AND | | | ELECTRICAL SHEETS WERE SUBMITTED?? | | | | | | 2)NOTE: PLEASE BE AWARE , WE ARE | | | CURRENTLY AWAITING VERIFICATION OF | | | COMPLETED WORK ON SERVICE ETC WHICH WAS | | | PERMITTED JUST A SHORT TIME AGO. | | | A PHONE CALL HAS BEEN PLACED FOR | | | VERIFICATION. | | | | | | | | | ** PLEASE BE AWARE, ENGINEER'S PE # | | | EXPIRES 2/28/05*** THIS IS ONLY A NOTE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-04-06 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-04-06 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-04-06 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-02-11 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-02-11 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-02-11 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2005-02-11 00:00:00 | 1) PLEASE ADVISE IF A MANUAL SHUTOFF | | | SWITCH IS BEING PROVIDED FOR THE PURPOSE | | | OF CONTROL. | | | | | | 2) PLEASE INDICATE THE LOCATION OF THE | | | SYSTEM. THE STORAGE AND USE OF | | | COMPRESSES GASES SHALL BE NOT LESS THAN | | | 50 FEET FROM AIR INTAKES. | | | | | | | | | MIKE WENNERGREN, ACTING CAPTAIN | | | WPBFR(561) 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-07-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-21 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-21 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2005-07-21 00:00:00 | TO "COMM" BD#6 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-06-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-06-28 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-06-28 |
Time |
08:14 |
Sent To |
Z |
|
| Notes |
| 2005-06-28 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-06-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-18 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-18 |
Time |
07:19 |
Sent To |
Z |
|
| Notes |
| 2005-06-18 00:00:00 | DIDN'T GET 2ND ZONING REVIEW, PUT IN | | | ZONING BOX, SENT EMAIL TO RG AND MM |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-03-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-21 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-21 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2005-03-21 00:00:00 | TO "COMM" BD#57 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-02-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-07 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-07 |
Time |
15:16 |
Sent To |
Z |
|
| Notes |
| 2005-02-07 00:00:00 | TO "Z"BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2005-07-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-07-25 |
Time |
13:22 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2005-07-25 |
Time |
13:18 |
Sent To |
|
|
| Notes |
| 2005-07-25 00:00:00 | PERMIT APPLICATION INDICATES "FOUNDATION | | | ONLY" MECHANICAL & ELECTRICAL ARE TO | | | APPLY SEPARATELY - FEES FOR MECHANICAL & | | | ELECTRICAL WERE NOT INCLUDED WITH | | | FOUNDATION PERMIT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-04-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-04-15 |
Time |
06:57 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2005-04-15 |
Time |
06:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-02-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-02-22 |
Time |
16:30 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2005-02-22 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2005-02-22 00:00:00 | DENIED: | | | PERMIT APPLICATION INDICATES MECHANICAL | | | AND ELECTRICAL NOT INCLUDED IN THE VALUE | | | OF THE PERMIT.PLANS SUBMITTED ARE FOR | | | MECHANICAL AND ELECTRICAL REVIEW. | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION: | | | | | | 1.INDICATE OCCUPANCY TYPE. | | | | | | 2.PROVIDE INFORMATION AS THE USE OF | | | THE COMPRESSED AIR. | | | | | | 3.WILL ANY CHEMICALS BE USED FOR THIS | | | PROCESS OR STORED AT THIS LOCATION? | | | | | | 4.PROVIDE OUTSIDE AIR CALCULATIONS IN | | | ACCORDANCE WITH 2001 FBC(M)TABLE 403.3. | | | | | | 5.INDICATE IF THE RTU'S WILL BE NEW OR | | | EXISTING.PROVIDE EQUIPMENT SCHEDULE | | | FOR ALL NEW EQUIPMENT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2005-04-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-04-15 |
Time |
11:26 |
Rev Time |
0.60 |
| Received By |
kstevens |
Date |
2005-04-15 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2005-04-15 00:00:00 | SEE PERMIT NUMBER 05031447 - COMPRESSOR | | | AND COMPRESSED AIR SYSTEM ON SEPARATE | | | PERMIT. KSTEVENS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-03-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-03-25 |
Time |
11:21 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2005-03-24 |
Time |
17:34 |
Sent To |
|
|
| Notes |
| 2005-03-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | | | | 1) SHT M2 INDICATE DISPOSAL METHOD FOR | | | THE OIL SEPARATED IN THE OIL/WATER | | | SEPARATOR. SECTION 104.2.1. | | | 2) DRAIN LINE FROM COMPRESSED AIR SYSTEM | | | SHALL BE PIPED TO THE EXISTING SANT. | | | DRAIN. MINIMUM SIZE FOR PIPING SHALL BE | | | 2" PIPE. SECTIONS S01.3 & 710.3. A HUB | | | DRAIN IS RECOMMENDED TO KEEP STORM WATER | | | FROM ENTERING THE SANT. SYSTEM. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2005-07-13 |
|
|
Cont ID |
|
| Sent By |
alongo |
Date |
2005-07-13 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
alongo |
Date |
2005-07-13 |
Time |
12:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2005-06-22 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-06-22 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-06-22 |
Time |
09:38 |
Sent To |
I |
|
| Notes |
| 2005-06-22 00:00:00 | DENIED, | | | 1. NEED TO APPLY FOR A MINOR AMENDMENT | | | ANY QUESTIONS, PLEASE CALL RANDALL | | | GRANBERRY, PLANNER 822-1454 OR 822-1435 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-03-02 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-03-02 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-03-02 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2005-03-02 00:00:00 | DENIED, | | | 1. NEED TO PROVIDE LANDSCAPE PLANS. | | | RANDALL G, PLANNER 822-1454, 5TH FLOOR | | | PLANNING DEPT. |
|
|