Plan Review Details - Permit 05020282
Plan Review Stops For Permit 05020282
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-07-27 Cont ID  
Sent By shill Date 2005-07-27 Time 09:33 Rev Time 0.50
Received By shill Date 2005-07-27 Time 09:33 Sent To  
Notes
2005-07-27 00:00:00WORK CROSSED OFF ON THE PLAN WAS
 PERMITTED SEPARATELY UNDER TRADE
 PERMITS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-07-25 Cont ID  
Sent By shill Date 2005-07-25 Time 18:44 Rev Time 0.50
Received By shill Date 2005-07-25 Time 18:44 Sent To  
Notes
2005-07-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE SITE PLAN HAS BEEN PREPARED BY
 AN ARCHITECT BUT SEALED BY THE ENGINEER
 OF RECORD.PLEASE SEE FAC61G15 IN
 REGARDS TO SEALING ANOTHER
 PROFESSIONAL'S WORK.HE CANNOT USE THE
 COMMENT ON THE PLAN THAT THE SEAL
 APPLIES TO LOCATION ONLY.
  
 2.)TITLE BLOCK REQUIRED FOR THE
 ENGINEER ON SHEET A3.
  
 3.)MANY PLANS WERE SUBMITTED,
 INCLUDING PLANS WHICH WERE NOT SEALED.
 PLEASE KEEP ADDITIONAL COPIES AND ONLY
 SUBMIT OLD REVIEWED PLANS AND THE SET
 YOU ARE SUBMITTING FOR PERMITTING.
  
 4.)SHEET M3 HAS THE COMMENT NEXT TO
 THE SEAL "SEAL APPLIES TO AWNING AND
 FENCE ONLY.CONSTRUCT REAMINDER TO REV
 3".PLEASE SUBMIT A PLAN OF WHAT YOU
 WOULD LIKE TO BUILD, SIGNED AND SEALED,
 FOR REVIEW.IT OTHERWISE APPEARS CODE
 COMPLIANT.
  
 5.)WHEN CHANGES ARE DONE TO THE PLAN,
 CLOUD AND NUMBER THE REVISIONS TO
 EXPEDITE PLAN REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-03-23 Cont ID  
Sent By shill Date 2005-03-23 Time 10:44 Rev Time 0.50
Received By shill Date 2005-03-23 Time 10:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-15 Cont ID  
Sent By shill Date 2005-02-15 Time 11:58 Rev Time 1.00
Received By shill Date 2005-02-15 Time 11:36 Sent To  
Notes
2005-02-15 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE DESIGN CRITERIA FOR THE
 ANCHORING OF THE EQUIPMENT, FBC
 1606.1.7.
  
 2.)THE "COMPRESSED AIR SYSTEM
 FOUNDATIONS" STATES "PLACE ON PAVING."
 DOES THIS MEAN THAT THE AIR RECEIVER IS
 NOT ANCHORED?NO ANCHORING DETAIL
 PROVIDED FOR THE AIR RECEIVER.
  
 3.)SEPARATE PERMIT REQUIRED FOR THE
 FENCE.

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2005-07-26 Cont ID  
Sent By dpalmer Date 2005-07-26 Time 11:20 Rev Time 0.30
Received By dpalmer Date 2005-07-26 Time 11:18 Sent To  
Notes
2005-07-26 00:00:00REMOVED ELECTRICAL PLANS FROM BOTH SETS
 PER DAVE BERINGER OF SOUTHEAST CONT.
 ELECTRICLA NOT INCLUDE UNDER HIS SCOPE
 PF WORK.
 ELECTRICAL PLANS AND PERMIT WAS ISSUED
 UNDER LIGHTNING ELECTRIC.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2005-03-22 Cont ID  
Sent By dpalmer Date 2005-03-22 Time 16:14 Rev Time 0.30
Received By dpalmer Date 2005-03-22 Time 16:14 Sent To  
Notes
2005-03-22 00:00:00ELECTRICAL PERMIT APPLIED FOR SEPARATELY
 FOR HOOKING UP OF COMPRESSED AIR
 SYSTEM.BY LIGHTNING ELEC.
 WAITING TO ISSUE PERMIT FOR LIGHTNING
 ELECTRIC WHEN RUSSELL JENNING'S PERMIT
 FROM LAST YEAR HAS BEEN FINALED AND
 CLOSED OUT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-03-17 Time 14:20 Rev Time 0.25
Received By dpalmer Date 2005-02-09 Time 18:20 Sent To  
Notes
2005-02-09 00:00:00******* UNSAT *******
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS ELECTRICAL AND MECHANICAL TO BE
 SUBMITTED SEPARATELY UNDER ELECTRICAL
 CONTRACTOR ETC. PLEASE SEE PERMIT
 APPLICATIONINDICATES WORK FOR
 FOUNDATION AND STRUCTUAL WORK ONLY?
 HOWEVER PLEASE SEE ONLY MECHANICAL AND
 ELECTRICAL SHEETS WERE SUBMITTED??
  
 2)NOTE: PLEASE BE AWARE , WE ARE
 CURRENTLY AWAITING VERIFICATION OF
 COMPLETED WORK ON SERVICE ETC WHICH WAS
 PERMITTED JUST A SHORT TIME AGO.
 A PHONE CALL HAS BEEN PLACED FOR
 VERIFICATION.
  
  
 ** PLEASE BE AWARE, ENGINEER'S PE #
 EXPIRES 2/28/05*** THIS IS ONLY A NOTE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-04-06 Cont ID  
Sent By mwennerg Date 2005-04-06 Time 14:30 Rev Time 0.00
Received By mwennerg Date 2005-04-06 Time 14:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-02-11 Cont ID  
Sent By mwennerg Date 2005-02-11 Time 10:09 Rev Time 0.00
Received By mwennerg Date 2005-02-11 Time 10:08 Sent To  
Notes
2005-02-11 00:00:001) PLEASE ADVISE IF A MANUAL SHUTOFF
 SWITCH IS BEING PROVIDED FOR THE PURPOSE
 OF CONTROL.
  
 2) PLEASE INDICATE THE LOCATION OF THE
 SYSTEM. THE STORAGE AND USE OF
 COMPRESSES GASES SHALL BE NOT LESS THAN
 50 FEET FROM AIR INTAKES.
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 13:47 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 13:47 Sent To  
Notes
2005-07-21 00:00:00TO "COMM" BD#6

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-28 Cont ID  
Sent By adarroug Date 2005-06-28 Time 08:14 Rev Time 0.00
Received By adarroug Date 2005-06-28 Time 08:14 Sent To Z
Notes
2005-06-28 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-18 Cont ID  
Sent By shill Date 2005-06-18 Time 07:19 Rev Time 0.00
Received By shill Date 2005-06-18 Time 07:19 Sent To Z
Notes
2005-06-18 00:00:00DIDN'T GET 2ND ZONING REVIEW, PUT IN
 ZONING BOX, SENT EMAIL TO RG AND MM

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-21 Cont ID  
Sent By adarroug Date 2005-03-21 Time 11:55 Rev Time 0.00
Received By adarroug Date 2005-03-21 Time 11:55 Sent To  
Notes
2005-03-21 00:00:00TO "COMM" BD#57

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-07 Cont ID  
Sent By adarroug Date 2005-02-07 Time 16:10 Rev Time 0.00
Received By adarroug Date 2005-02-07 Time 15:16 Sent To Z
Notes
2005-02-07 00:00:00TO "Z"BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2005-07-25 Cont ID  
Sent By pkrauss Date 2005-07-25 Time 13:22 Rev Time 0.30
Received By pkrauss Date 2005-07-25 Time 13:18 Sent To  
Notes
2005-07-25 00:00:00PERMIT APPLICATION INDICATES "FOUNDATION
 ONLY" MECHANICAL & ELECTRICAL ARE TO
 APPLY SEPARATELY - FEES FOR MECHANICAL &
 ELECTRICAL WERE NOT INCLUDED WITH
 FOUNDATION PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-04-15 Cont ID  
Sent By pkrauss Date 2005-04-15 Time 06:57 Rev Time 0.40
Received By pkrauss Date 2005-04-15 Time 06:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-02-22 Cont ID  
Sent By pkrauss Date 2005-02-22 Time 16:30 Rev Time 0.55
Received By pkrauss Date 2005-02-22 Time 16:04 Sent To  
Notes
2005-02-22 00:00:00DENIED:
 PERMIT APPLICATION INDICATES MECHANICAL
 AND ELECTRICAL NOT INCLUDED IN THE VALUE
 OF THE PERMIT.PLANS SUBMITTED ARE FOR
 MECHANICAL AND ELECTRICAL REVIEW.
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION:
  
 1.INDICATE OCCUPANCY TYPE.
  
 2.PROVIDE INFORMATION AS THE USE OF
 THE COMPRESSED AIR.
  
 3.WILL ANY CHEMICALS BE USED FOR THIS
 PROCESS OR STORED AT THIS LOCATION?
  
 4.PROVIDE OUTSIDE AIR CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC(M)TABLE 403.3.
  
 5.INDICATE IF THE RTU'S WILL BE NEW OR
 EXISTING.PROVIDE EQUIPMENT SCHEDULE
 FOR ALL NEW EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status N Date 2005-04-15 Cont ID  
Sent By kstevens Date 2005-04-15 Time 11:26 Rev Time 0.60
Received By kstevens Date 2005-04-15 Time 11:26 Sent To  
Notes
2005-04-15 00:00:00SEE PERMIT NUMBER 05031447 - COMPRESSOR
 AND COMPRESSED AIR SYSTEM ON SEPARATE
 PERMIT. KSTEVENS

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-25 Cont ID  
Sent By kstevens Date 2005-03-25 Time 11:21 Rev Time 1.00
Received By kstevens Date 2005-03-24 Time 17:34 Sent To  
Notes
2005-03-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
  
 1) SHT M2 INDICATE DISPOSAL METHOD FOR
 THE OIL SEPARATED IN THE OIL/WATER
 SEPARATOR. SECTION 104.2.1.
 2) DRAIN LINE FROM COMPRESSED AIR SYSTEM
 SHALL BE PIPED TO THE EXISTING SANT.
 DRAIN. MINIMUM SIZE FOR PIPING SHALL BE
 2" PIPE. SECTIONS S01.3 & 710.3. A HUB
 DRAIN IS RECOMMENDED TO KEEP STORM WATER
 FROM ENTERING THE SANT. SYSTEM.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2005-07-13 Cont ID  
Sent By alongo Date 2005-07-13 Time 12:17 Rev Time 0.00
Received By alongo Date 2005-07-13 Time 12:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-06-22 Cont ID  
Sent By mmclean Date 2005-06-22 Time 09:38 Rev Time 0.00
Received By mmclean Date 2005-06-22 Time 09:38 Sent To I
Notes
2005-06-22 00:00:00DENIED,
 1. NEED TO APPLY FOR A MINOR AMENDMENT
 ANY QUESTIONS, PLEASE CALL RANDALL
 GRANBERRY, PLANNER 822-1454 OR 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2005-03-02 Cont ID  
Sent By mmclean Date 2005-03-02 Time 14:48 Rev Time 0.00
Received By mmclean Date 2005-03-02 Time 14:48 Sent To  
Notes
2005-03-02 00:00:00DENIED,
 1. NEED TO PROVIDE LANDSCAPE PLANS.
 RANDALL G, PLANNER 822-1454, 5TH FLOOR
 PLANNING DEPT.