Plan Review Details - Permit 05020246
Plan Review Stops For Permit 05020246
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-02-10 Cont ID  
Sent By jwitmer Date 2006-02-10 Time 14:39 Rev Time 0.77
Received By jwitmer Date 2006-02-10 Time 14:39 Sent To PC
Notes
2006-02-10 00:00:00REVISIONS A RCH AND STRUCTURAL NEW
 ENGINEER MORGAN VILLANUEVA P. E.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-02-03 Cont ID  
Sent By jwitmer Date 2006-02-03 Time 12:42 Rev Time 2.22
Received By jwitmer Date 2006-02-03 Time 12:42 Sent To PC
Notes
2006-02-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05020246
 ADD: 5405 N HAVERHILL BLED# 2
 CONT:MILLER
 TEL: (786)202-8374
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
  
 1) PLANS INDICATE CHANGE OF WIND SPEED
 AND EXPOSURE. WILL REQUIRE REVIEW OF ALL
 STRUCTURAL COMPONENTS & CLADDING.
  
 NEW ENGINEER: 61G15-27

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-12-23 Cont ID  
Sent By jwitmer Date 2005-12-23 Time 16:06 Rev Time 1.11
Received By jwitmer Date 2005-12-23 Time 16:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-10-05 Cont ID  
Sent By jwitmer Date 2005-10-05 Time 15:11 Rev Time 3.33
Received By jwitmer Date 2005-10-05 Time 15:11 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-01 Cont ID  
Sent By jwitmer Date 2005-06-01 Time 13:17 Rev Time 2.22
Received By jwitmer Date 2005-06-01 Time 13:17 Sent To  
Notes
2005-06-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05020246
 ADD: 5405 N HAVERHILL RD PH#2
 CONT:NORTON
 TEL: (561)252-0590
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE
 ISSUED.A0.01 CORRECT NOTE THAT NOC WILL
 BE REQUIRED BY FIRST INSPECTION,
 BUILDING OFFICIAL IS MORE RESTRICTIVE.
 NOC RECORDED FOR BUILD# 1 AND
 BUILDING# 3.
  
  
 2) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-17 Cont ID  
Sent By jwitmer Date 2005-02-17 Time 07:31 Rev Time 2.22
Received By jwitmer Date 2005-02-17 Time 07:31 Sent To  
Notes
2005-02-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05020246
 ADD: 5405 N HAVERHILL RD PH#2
 CONT:NORTON
 TEL: (561)252-0590
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE
 ISSUED.A0.01 CORRECT NOTE THAT NOC WILL
 BE REQUIRED BY FIRST INSPECTION,
 BUILDING OFFICIAL IS MORE RESTRICTIVE.
  
 2) SINCE THE IST REVIEW OF PHASE #1, A
 REPLAT WAS SUBMITTED, THIS LOT CAN NO
 LONGER USE THIS ADDRESS , EACH PCN HAS
 ITS OWN ADDRESS, IT WILL BE ASSIGNED
 WITH THE NEW PCN.
  
 3) E2.02/E2.03 WHEN THE SPACE BENEATH
 MEZZANINES ARE ENCLOSED MUST COMPLY WITH
 1005.7.3 (EXCEPTION) A SMOKE DETECTION
 SYSTEM SHALL BE PLACED BENEATH A
 ENCLOSED MEZZANINE WHICH SOUNDS A ALARM
 IN THE MEZZANINEIN ACCORDANCE WITH
 NFPA 72.
  
 4) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 XX - BUILDING/STRUCTURES OF UNUSUAL
 DESIGN OR METHODS OF CONSTRUCTION
 (TILT WALL CONSTRUCTION)
  
 5)106.4.2 STORAGE & FACTORY- INDUS-
 TRIAL OCCUPANCIES. IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
  
 6) THESE ARE CODE REQUIREMENTS FOR
 TERMITE PROTECTION NOT FOUND IN 1816:
 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED & STOREFRONT: REPORTS
 WERE SRUNK & COPIED UNREADABLE,
 FASTEN REPORTS TOGETHER MISSING
 STOREFRONT. THREE COPIES.
 B) EXTERIOR SWING DOORS-3 COPIES
 C) GARAGE DOORS- PARTIAL REPORT, 3
 COPIES
 D) MULLIONS- NO SUBMITTALS
 E) STORM SHUTTERS- NO SUBMITTAL, 3
 COPIES
 F) ROOFING ASSEMBLIES- 3 COPIES
  
 8A)!!!!!!!!PLEASE TAKE NOTE!!!!!!!!!!!!
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8B) NOT A CODE ISSUE, BUT REFRENCED IN
 THE PLANS THE ARCHITECT OF RECORD IS TO
 REVIEW AND APPROVE ALL COMPONENTS &
 CLADDING.
  
 8C) THE PRODUCT APPROVALS FOR PGT FIXED
 WINDOWS (2) REPORTS WERE SUBMITTED, ONE
 FOR LARGE MISSLE IMPACT OR GLAZING NOT
 RATED, INDICATE WHICH IS TO BE USED.
 THEN A SECOND REPORT WAS SUBMITTED FOR
 F6000, EACH REPORT HAS DIFFERENT
 PRESSURES WHICH REPORT IS TO BE USED?
  
 9A)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY SEE A9.02 SEE WINDOW
 SCHEDULE AND NOTE #1, EITHER IMPACT
 WINDOWS ARE TO BE USED OR STORM
 SHUTTERS.
  
 9B) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.COMMERCIAL
 AREA WHERE SHUTTERS WILL BE STORED.
 FBC 1606.1.4.
  
 9C)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 9D) SEE A9.02 PLANS INDICATE THE USE OF
 STORM SHUTTERS, SEE CITY INTERPRETATION
 ON THE STANDARD FOR HURRICANE MISSLE
 IMPACT PROTECTION, QUESTION #13, DEALING
 WITH THE "PRESTORM HURRICANE PREPARDNESS
 PLAN" SUBMIT FOR REVIEW. SEE ATTACHMENT.
  
 10) A0.01 CONTRACTOR PRICING
 REQUIREMENTS FBC SECTION 104.6.4.5, NOT
 FOUND IN THE ADMINISTRATIVE CODE NOR THE
 CITY ADOPTED ADMINISTRATIVE CODE?
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-03-29 Cont ID  
Sent By dpalmer Date 2006-03-29 Time 16:24 Rev Time 0.00
Received By dpalmer Date 2006-03-29 Time 16:24 Sent To  
Notes
2006-03-29 00:00:00REV TO RELOCATE TWO PANELS IN TENANT
 SPACE 31 AND 32

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-03-01 Cont ID  
Sent By dpalmer Date 2006-03-01 Time 17:38 Rev Time 0.00
Received By dpalmer Date 2006-03-01 Time 17:14 Sent To ENG
Notes
2006-03-01 00:00:00REV'S 2.01,2.06, AND 2.07** STAMPED.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-02-10 Cont ID  
Sent By dpalmer Date 2006-02-10 Time 18:20 Rev Time 0.00
Received By dpalmer Date 2006-02-10 Time 18:02 Sent To FIRE
Notes
2006-02-10 00:00:00************ UNSAT **********
  
 1)NOTE: PLEASE SEE PLANS WHICH WERE
 REDLINED ON 11/10/05 FOR GROUPING OF
 MAINS WHICH DO NOT APPEAR AS SHOWN ON
 SITE PLANS.
 MAINS MUST BE GROUPED IN CLOSE
 PROXIMITY, WHICH THAT DOES APPEAR TO BE
 THE CASE AS SHOWN ON [PLANS.
 230.72
  
 2)NOTE: PLEASE SEE CORRELATE PLANS,
 PANEL SCHEDULES, LOAD CALCUALTIONS AND
 RISER DIAGRAM.
 PLEASE SEE PANELS 120/208V, SERVICE AS
 277/480V AND LOADS AS ????
 215.5
  
 3)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM WHICH WILL CHANGE. PLEASE SEE
 PLANS/RISER DOES NOT INDICATE GE SYSTEM.
  
 250.50,250.66 ETC
  
 4)NOTE: PLEASE SEE ONLY3-PHASE PANELS
 ARE BEING SHOWN, HOWEVER, PLEASE SEE
 RISER INDICATES SINGLE PHASE AND THREE
 PHASE FEEDERS???CIRCIRLED NOTES #9 AND
 #10.
 PLEASE ALSO SEE TYPICAL DETAIL WHICH
 SHOWS BOTH ??
 215.5
 IF SERVICE IS THREE PHASE ALL THE WAY
 THROUGH TO TENANT, PLEASE ADJUST AND
 CORRELATE ALL PANELS
  
  
 *** PLEASE CORRELATE PLANS FOR REVIEW OF
 CODE COMPLIANCE.
  
 PLEASE SUBMIT ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-01-13 Cont ID  
Sent By dpalmer Date 2006-01-13 Time 09:43 Rev Time 0.00
Received By dpalmer Date 2006-01-12 Time 13:03 Sent To  
Notes
2006-01-13 00:00:00REV'S 2.02, .03,.05

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-10 Cont ID  
Sent By dpalmer Date 2005-11-10 Time 20:47 Rev Time 0.00
Received By dpalmer Date 2005-11-10 Time 20:30 Sent To  
Notes
2005-11-10 00:00:00PLANS REDLINED.
  
 REVISIONS FOR LIGHTING ONLY,
 MAINS /AND SINGLE SERVICE GROUPED.
 230.72,230.2

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 17:31 Rev Time 0.00
Received By dpalmer Date 2005-06-13 Time 17:20 Sent To  
Notes
2005-06-13 00:00:00ELECTRICAL SHEETS STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-25 Cont ID  
Sent By dpalmer Date 2005-02-25 Time 11:38 Rev Time 0.75
Received By dpalmer Date 2005-02-25 Time 11:38 Sent To  
Notes
2005-02-25 00:00:00***** UNSAT ****
  
 1)NOTE: PLEASE SEE BLDG /FIRE REVIEW
 COMMENTS WHICH WILL HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 2)NOTE: PLEASEPLACE NOTE ON PLANS:
 "OCCUPANCIES NOT SUBJECT TO
 PUBLIC/PEDESTIRAN TRAFFIC"
 IF SO, PLEASE SEE 600.5
 PLEASE ADJUST IF NEEDED.
 \
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2006-03-03 Cont ID  
Sent By mamini Date 2006-03-03 Time 11:14 Rev Time 0.50
Received By mamini Date 2006-03-03 Time 11:14 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2006-01-27 Cont ID  
Sent By mamini Date 2006-01-27 Time 14:09 Rev Time 0.50
Received By mamini Date 2006-01-27 Time 14:09 Sent To  
Notes
2006-01-27 00:00:00PASSED:
  
 1. REVIEWED FOR REVISION, SHEETS C.2,
 2.3, C.4,C.5, AND C.6
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-02-07 Cont ID  
Sent By mamini Date 2005-02-07 Time 10:20 Rev Time 0.50
Received By mamini Date 2005-02-07 Time 10:20 Sent To  
Notes
2005-02-07 00:00:00PASSED:
  
 1. SEE PERMIT # 04110991 FOR
 UNDERGROUND UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2006-02-16 Cont ID  
Sent By nmccray Date 2006-02-16 Time 10:46 Rev Time 0.00
Received By nmccray Date 2006-02-16 Time 10:44 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-01-30 Cont ID  
Sent By mwennerg Date 2006-01-30 Time 13:48 Rev Time 0.00
Received By mwennerg Date 2006-01-30 Time 13:48 Sent To  
Notes
2006-01-30 00:00:00REVISION DATED 12/5/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-11-16 Cont ID  
Sent By mwennerg Date 2005-11-16 Time 10:46 Rev Time 0.00
Received By mwennerg Date 2005-11-16 Time 10:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-06-14 Cont ID  
Sent By mwennerg Date 2005-06-14 Time 11:29 Rev Time 0.00
Received By mwennerg Date 2005-06-14 Time 11:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-03-22 Cont ID  
Sent By mwennerg Date 2005-03-22 Time 16:41 Rev Time 0.00
Received By mwennerg Date 2005-03-22 Time 16:41 Sent To  
Notes
2005-03-22 00:00:001) PLEASE BE ADVISED THAT ALL LIFE
 SAFETY MUST COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2) THE TURN AROUND LOCATED NEXT TO THE
 10' UTILITY EASEMENT MUST PROVIDE A
 CENTERLINE TURNING RADIUS OF 50'.
  
 3) PLEASE BE ADVISED THAT THE FIRE
 DEPARTMENT CONNECTION SHALL BE LOCATED
 NO FURTHER THAN 150' FROM THE CLOSEST
 FIRE HYDRANT.
  
 4) PLANS DON'T REFLECT ANY FIRE HYDRANTS
 ON THE WEST SIDE OF THE PROJECT. ARE
 THERE ANY, AND COULD YOU PROVIDE THE
 LOCATIONS?
  
 5) WILL THERE BE GATE ACCESS INTO THE
 PROPERTY AFTER HOURS? IF SO, PLEASE BE
 ADVISED THAT A KNOX KEY SYSTEM SHALL BE
 PROVIDED WITH A BACK UP IN THE EVENT OF
 POWER FAILURE.
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-02-19 Cont ID  
Sent By adarroug Date 2006-02-19 Time 12:59 Rev Time 0.00
Received By adarroug Date 2006-02-19 Time 12:59 Sent To E
Notes
2006-02-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-02-10 Cont ID  
Sent By adarroug Date 2006-02-10 Time 11:30 Rev Time 0.00
Received By adarroug Date 2006-02-10 Time 11:30 Sent To B
Notes
2006-02-10 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-02-03 Cont ID  
Sent By adarroug Date 2006-02-03 Time 15:23 Rev Time 0.00
Received By adarroug Date 2006-02-03 Time 15:23 Sent To E
Notes
2006-02-03 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-01-19 Cont ID  
Sent By adarroug Date 2006-01-19 Time 13:23 Rev Time 0.00
Received By adarroug Date 2006-01-19 Time 13:23 Sent To  
Notes
2006-01-19 00:00:00TO "COMM" BD#37

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-12-12 Cont ID  
Sent By adarroug Date 2005-12-12 Time 19:38 Rev Time 0.00
Received By adarroug Date 2005-12-12 Time 19:38 Sent To  
Notes
2005-12-12 00:00:00WAITING FOR "COMM" BD/3
 REV.(BLDG,ELEC,MECH)

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-03 Cont ID  
Sent By adarroug Date 2005-10-03 Time 16:46 Rev Time 0.00
Received By adarroug Date 2005-10-03 Time 16:46 Sent To  
Notes
2005-10-13 00:00:00TO "COMM" BD#45
2005-10-03 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-28 Cont ID  
Sent By adarroug Date 2005-09-28 Time 17:17 Rev Time 0.00
Received By adarroug Date 2005-09-28 Time 17:17 Sent To B
Notes
2005-09-28 00:00:00TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-28 Cont ID  
Sent By adarroug Date 2005-05-04 Time 17:17 Rev Time 0.00
Received By adarroug Date 2005-05-04 Time 16:34 Sent To  
Notes
2005-05-17 00:00:00TO "COMM" BD#11
2005-05-04 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-04 Cont ID  
Sent By adarroug Date 2005-02-04 Time 14:50 Rev Time 0.00
Received By adarroug Date 2005-02-04 Time 14:50 Sent To  
Notes
2005-02-04 00:00:00TO COMM BOARD #63/COMM SHELF

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-01-23 Cont ID  
Sent By hmoser Date 2006-01-23 Time 18:04 Rev Time 0.00
Received By hmoser Date 2006-01-23 Time 17:58 Sent To  
Notes
2006-01-23 00:00:00PLEASE HAVE MANUFACTURERS INSTALLATION
 INSTRUCTIONS ON CONDENSER STANDS ON SITE
 FOR INSPECTOR.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2005-12-05 Cont ID  
Sent By rregueir Date 2005-12-05 Time 17:33 Rev Time 0.00
Received By rregueir Date 2005-12-05 Time 17:30 Sent To  
Notes
2005-12-05 00:00:00NO MECHANICAL PLANS SUBMITTED WITH THIS
 REVISION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-17 Cont ID  
Sent By pkrauss Date 2005-06-17 Time 09:22 Rev Time 0.40
Received By pkrauss Date 2005-06-17 Time 09:14 Sent To  
Notes
2005-06-17 00:00:00PROVISO:
 PLAN SHEET M7.01 SPLIT SYSTEM A/C UNIT
 SCHEDULE, NOTE #7 - ALL AC UNITS HANG IN
 WAREHOUSE WITH TOP OF THE UNITS AT 19 FT
 AFF.PER 2001 FBC(M)306.5, WHERE
 EQUIPMENT IS INSTALLED AT A HEIGHT
 GREATER THAN 16 FT, PERMANENT MEANS OF
 ACCESS REQUIRED.THIS HEIGHT WILL
 EXTEND FROM THE FLOOR LEVEL TO THE LEVEL
 SERVICE SPACE OF THE EQUIPMENT.PLEASE
 PROVIDE INFORMATION HOW EQUIPMENT IS TO
 BE SERVICED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-03-21 Cont ID  
Sent By pkrauss Date 2005-03-21 Time 16:30 Rev Time 1.45
Received By pkrauss Date 2005-03-21 Time 16:30 Sent To  
Notes
2005-03-21 00:00:00DENIED:
 1.PLAN SHEET M8.01 DETAIL 2, THE
 DETAIL FOR THE AHU INDICATES AN OVERFLOW
 SWITCH IN THE UNIT DRAIN PAN.PER 2001
 FBC/M 307.2.3, AN AUXILIARY DRAIN PAN IS
 REQUIRED WITH THE FLOAT SWITCH INSTALLED
 IN THE AUXILIARY DRAIN PAN.THE CODE
 DOES NOT ALLOW FOR THE INSTALLATION AS
 DEPICTED IN DETAIL 2.
  
 2.PLEASE INDICATE AT WHAT HEIGHT THE
 AHU WILL BE INSTALLED.
  
 3.PLEASE NOTE, SYSTEMS WIHT THE DESIGN
 CAPACITY GREATER THAN 2,000 CFM ARE
 REQUIRED TO BE EQUIPPED WITH A DUCT
 SMOKE DETECTOR.PLEASE REFERENCE AC-3
 ON THE EQUIPMENT SCHEDULE.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  

Review Stop P PLUMBING
Rev No 3 Status N Date 2005-10-15 Cont ID  
Sent By pschmitz Date 2005-10-15 Time 10:36 Rev Time 0.00
Received By pschmitz Date 2005-10-15 Time 10:36 Sent To  
Notes
2005-10-15 00:00:00NO PLUMBING REVISIONS ON THIS REVISION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-01 Cont ID  
Sent By kstevens Date 2005-06-01 Time 11:31 Rev Time 2.00
Received By kstevens Date 2005-05-25 Time 16:19 Sent To  
Notes
2005-06-01 00:00:00IRRIGATION SHEET VOID - SEPARATE PLANS
 AND PERMIT REQUIRED FOR IRRIGATION -
 PLANS SHALL SHOW THE LOCATION OF THE
 TIMER/CONTROLLER, RAIN SENSOR, AND
 BACKFLOW PROTECTION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-04 Cont ID  
Sent By kstevens Date 2005-03-04 Time 10:26 Rev Time 3.50
Received By kstevens Date 2005-03-03 Time 18:53 Sent To  
Notes
2005-03-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT L-3 SHOW THE LOCATION OF THE
 CONTROLLER/TIMER, AND RAIN SENSOR.
 SECTION 104.2.1.
 2) SGT C.5 RPZ BACKFLOW IS REQUIRED ON
 THE WATER SERVICE TO EACH BUILDING.
 SECTION 608.13.2.
 3) INDICATE THE SF AREA FOR EACH UNIT TO
 CALCULATED THE MINIMUM FACILITIES PER
 TABLES 1003.1 & 403.1.
 4) SHT A301 SHOW THE SQUARE FOOTAGE FOR
 ALL SPACES INCLUDING MEZZNINE LEVEL.
 SHOW SF FOR EACH OCCUPANCY. (OFFICE AND
 STORAGE). SECTION 104.2.1.
 5) SHT A3.06 DETAIL #8 PROVIDE
 CALCULATIONS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.26.3(2)(3)(4).
 CALCULATIONS FROM THE ENGINEER REQD.
 6) SHT A3.06 SHOW COMPLIANCE WITH
 SECTION 11-4.19.4 EXPOSED PIPES &
 SURFACES.
 7) SHTS P5.01 & P5.02 WATER RISER
 DIAGRAMS, SECTION 606.1(4) FULL OPEN
 VALVES ARE REQUIRED ON EVERY WATER DOWN
 FEED PIPE. SECTION 606.2(2) SHUT OFF
 VALVES REQUIRED FOR HOSE BIBBS. SHOW
 THESE VALVES ON THE ISOMETRIC. SECTION
 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2006-01-30 Cont ID  
Sent By lshapiro Date 2006-01-30 Time 08:37 Rev Time 0.00
Received By lshapiro Date 2006-01-30 Time 08:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-01-20 Cont ID  
Sent By lshapiro Date 2006-01-20 Time 17:14 Rev Time 0.00
Received By lshapiro Date 2006-01-20 Time 17:14 Sent To  
Notes
2006-01-20 00:00:00THE PLANNING & ZONING DEPARTMENT WILL
 NEED A REVISED SITE AND LANDSCAPE PLANS
 PRIOR TO BUILDING PERMIT APPROVAL.
  
 THE FOLLOWING INFORMATION IS NEEDED:
 1. PROVIDE A SITE PLAN AND LANDSCAPE
 PLAN MATCHING THE BUILDING PLANS
 (INCLUDING BUILDINGS 1-3);
 2. PROVIDE A JUSTIFICATION LETTER
 EXPLAINING WHY AN ADDITIONAL DRIVE IS
 NEEDED ON THE CUL-DE-SAC.
 3. APPROVAL OF THE DRIVE IS SUBJECT TO
 REVIEW AND APPROVAL BY THE PUBLIC
 UTILITIES DEPARTMENT.
 4. SHOW WHERE ANY PARKING IS AFFECTED BY
 THE LOCATION OF THE NEW DRIVE.
 5. MATCH THE PHOTOMETRICS PLAN WITH THE
 REVISED SITE PLAN.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-01 Cont ID  
Sent By mmclean Date 2005-03-01 Time 09:40 Rev Time 0.00
Received By mmclean Date 2005-03-01 Time 09:40 Sent To  
Notes
2005-03-01 00:00:00JOSH LONG, SENIOR PLANNER 822-1449,
 APPROVED