Plan Review Details - Permit 05020237
Plan Review Stops For Permit 05020237
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-04-12 Cont ID  
Sent By shill Date 2006-04-12 Time 18:09 Rev Time 0.00
Received By shill Date 2006-04-12 Time 18:09 Sent To  
Notes
2006-04-12 00:00:00REVISED SP1, SP2, A1, A2, A10 DATED 12/7

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-01-10 Cont ID  
Sent By shill Date 2006-01-10 Time 12:26 Rev Time 0.50
Received By shill Date 2006-01-10 Time 12:18 Sent To PC
Notes
2006-01-10 00:00:00REVISED SP1, AP2, A1, A2, A10,

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-05-20 Cont ID  
Sent By shill Date 2005-05-20 Time 13:40 Rev Time 0.50
Received By shill Date 2005-05-20 Time 13:37 Sent To  
Notes
2005-05-20 00:00:00REVISED S2,3,4

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-05-20 Cont ID  
Sent By shill Date 2005-05-20 Time 13:09 Rev Time 1.00
Received By shill Date 2005-05-20 Time 13:09 Sent To PC
Notes
2005-05-20 00:00:00***CORRECTIONS***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)NO CHANGES SHOWN ON S2 AND S3.
 PLEASE CLOUD ALL CHANGES.
  
 2.)SHEET S4, NO ZONE 3 FOR THE HIP
 ROOF IS SHOWN.FBC FIGURE 1606.2(C).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-22 Cont ID  
Sent By shill Date 2005-04-22 Time 09:12 Rev Time 2.00
Received By shill Date 2005-04-22 Time 09:12 Sent To PC
Notes
2005-04-22 00:00:00SUBMIT STATE OR LOCAL PRODUCT APPROVALS
 FOR NOA03-0730.03, USP TD HOLDDOWNS OR
 SUBMIT A REVISION FOR CONNECTORS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-28 Cont ID  
Sent By alange Date 2005-03-28 Time 09:05 Rev Time 0.66
Received By alange Date 2005-03-28 Time 08:54 Sent To  
Notes
2005-03-28 00:00:00DENIED
  
 3.PRODUCT APPROVALS WITH QUALITY
 ASSURANCE REQUIRED FOR THEFOLLOWING.
 STRAPS AND TIE-DOWNS AND LATICRETE
 MEMBRANE.
  
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-08 Cont ID  
Sent By alange Date 2005-03-08 Time 07:09 Rev Time 2.25
Received By alange Date 2005-03-08 Time 06:49 Sent To  
Notes
2005-03-08 00:00:00DENIED
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3.PRODUCT APPROVALS WITH QUALITY
 ASSURANCE REQUIRED FOR THE FOLLOWING.
 FLAT ROOF, STRAPS AND TIE-DOWNS,
 LATICRETE MEMBRANE.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.ATTIC ACCESS SHALL BE A MIN OF 20 X
 36" PER FBC 2309.6
  
 5.SUBMIT A GUARDRAIL DETAIL SHOWING
 OPENINGS COMPLYING WITH FBC 1015.3
  
 6.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 7.REVISE DETAIL ON DOOR AND WINDOW
 BUCKS SO THAT THE BUCK OFFERS FULL
 SUPPORT OF THE DOOR OR WINDOW FRAME.
 FBC 1707.4.4.2
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2006-06-25 Cont ID  
Sent By dpalmer Date 2006-06-25 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2006-06-25 Time 14:36 Sent To PC
Notes
2006-06-25 00:00:00*** PLEASE SEE RISER SHOW PANEL "C" AS
 100A AND PANEL "C" SCHEDULE SHOWS 125A.
  
 PLEASE CORRELATE BEFORE FINAL.
 THIS CAN BE ADDRESSED IN LTR FORM AS
 LONG AS THERE ARE NO OTHER
 REVISIONS/CHANGES.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICALPLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2006-06-09 Cont ID  
Sent By dpalmer Date 2006-06-09 Time 07:08 Rev Time 0.00
Received By dpalmer Date 2006-06-09 Time 07:01 Sent To PC
Notes
2006-06-09 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE IN NO CASE CAN WHITE
 OUT BE USED ON PLANS WHICH ARE SIGNED,
 DATED AND SEALED. FS 471/481
 PLEASE SEE CONDUCTORS ON PLANS CHANGED
 FROM 3/0'S TO 2/0'S FROM ALL PREVIOUS
 DESIGNS ON PLANS.
 215.5
  
 2) NOTE: PLEASE CORRELATE RISER WITH
 FEEDERS SHOWN ON PANEL "B" FOR PANEL
 "C".
 PLEASE SEE TWO DIFFERENT SIZES ARE
 SHOWN?
 215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-05-19 Cont ID  
Sent By btrobaug Date 2006-05-19 Time 12:22 Rev Time 0.50
Received By btrobaug Date 2006-05-19 Time 09:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-03-18 Cont ID  
Sent By dpalmer Date 2006-03-18 Time 15:20 Rev Time 0.00
Received By dpalmer Date 2006-03-18 Time 13:22 Sent To Z
Notes
2006-03-18 00:00:00********* UNSAT *********
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW AND SOME NEW COMMENTS DUE TO
 CHANGES IN PLANS.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW WIHT NEW
 NOTES ADDED.
  
  
 1)NOTE: NOTE #1 NO, SPOKE TO CONTRACTOR,
 HE WILL COME IN AND ADJUST.
  
 ** PREVIOUS NOTE**
 PLEASE SEE THERE HAVE BEEN MAJOR
 CHANGES IN THE SCOPE OF ELECTRICAL WORK
 AND OTHER REMODEL WORK DONE FOR
 DWELLING.
 PLEASE SEE FBC ADMINSTRATIVE 104.6.5
 WHICH REQUIRES A MAJOR ADJUSTMENT IN
 VALUATION OF PERMITTING.
 PLEASE SEE ORIG WAS INCLUSIVE OF SOME
 REMODEL AND ADDITION WORK AT $130,000
 PLEASE ADJUST.
 PLANS ARE NOW INDICATING THE ENTIRE
 HOUSE BEING REWIRED ETC.
  
 2)NOTE: NOTE #2 NO, PLEASE SEE REDLINED
 PLANS. THESE LOCATIONS COULD BE
 REDLINED, HOWEVER PLANS ARE COMING BACK
 FOR OTHER COMMENTS.
  
 ** PREVIOUS NOTE**
 PLEASE SEE SOME RECEPTS NOW
 MISSING DUE TO SOME WALL CHANGES.210.52
  
 3)NOTE: NOTE #3 OK? SPACE IN KITCHEN
 SEEMS TO BE 12" OR MORE, THIS IS TO BE
 FEILD VERIFIED AND IF ONE IS NEEDED, IT
 IS TO BE ADDED.
  
 ** PREVIOUS NOTE **
 PLEASE BE SURE TO DOUBLE CHECK
 KITCHEN COUNTERSPACE AS SOME SPACING
 SEEMS TO REQUIRE ADDITIONAL
 RECEPTS.210.52C1
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE NEW
 COMMENTS DUE TO CHANGES NOW MADE AND
 SOME ITEMS ARE MISSING.
  
 ** PREVIOUS NOTE**
 PLEASE SEE COMPLETE CHANGE IN
 ELECTRICAL SERVICE HAS NOW CREATED SOME
 ELECTRICAL COMMENTS:
  
 A)OK
  
 B)OK
  
 C)OK, HOWEVER SEE CONDUITS FROM MAINS AT
 HOUSE TO SUB PANELS AT HOUSE ARE MISSING
 EQUIPMENT GROUNDING CONDUCTOR.
 250.110,250.122
 ** PRE-NOTE**
 PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS FROM METER/MAIN UP TO MAIN
 HOUSE. 250.32
 PLEASE ALSO SEE MISSING GROUNDING
 ELECTRODE SYSTEM AT MAIN HOUSE, SINCE
 SERVICE IS NOW MOVED.
  
 D) OK, PLEASE SEE OCP WAS ADDED ,
 HOWEVER SEE NEW NOTE AS 100A OCP IN
 METERMAIN IS FEEDING A 70 BRKR PANEL.
 PLEASE VERIFY AS EITHER THE GUEST HOUSE
 BRKR PANEL IS 100A'S, OR BRKR AT METER
 MAIN IS 70A'S?
  
 ** PRE-NOTE**PLEASE SEE METER/MAIN IS
 SHOWN AS
 400A, AND THERE IS NO INDICATION OF THE
 OCP PROVIDED FOR SUB-PANEL FEEDERS TO
 MAIN HOUSE OR ANY OTHER BRANCH BRKRS.
 240.4,310.16 ETC.
 PLEASE ALSO VERIFY GUEST HOUSE BEING
 SHOWN WITH A MAIN DISCONNECT AND
 SUB-PANEL, AS IT IS SHOWN ON RISER BEING
 FED FROM THE METER MAIN PANEL AT GUEST
 HOUSE BLDG ALREADY?
 DISC?
  
 E) NO, PLEASE SEE PANEL SCHEDULES STILL
 SHOW PANEL AS 200A MCB WHICH IS OK,
 HOWEVER PLEASE SEE RISER DIAGRAM NOW
 SHOWS THE PANELS LOCATED INSIDE AS MLO??
 PLEASE CORRELATE.
  
 ** PRE-NOTE**
 PLEASE ALSO VERIFY THE PANELS INSIDE
 THE MAIN HOUSE AS BOTH ARE SHOWN WITH
 MCB'S WHICH ARE PERMITTED ALTHOUGH NOT
 REQUIRED. THIS IS ONLY A NOTE AND NO
 CHNAGE IS NEEDED. PLEASE KNOW, IF SHOWN
 AS MCB , THEN THESE WILL BE REQUIRED.
  
 F) OK.
  
 7)NOTE: NOTE #7 OK
  
 8)NOTE: NOTE #8 OK.
  
 9)NOTE: NOTE # 9 OK.
  
 10)NOTE: NOTE #10 OK , NOTED.
  
 ** NOW NOTE**
  
 11)NOTE: PLEASE CORRELATE LOADS SHOWN
 ON PANEL "C" AND LOAD ON PANEL "B" FOR
 PANEL "C" LOAD. PREVIOUS PLANS, THESE
 MATCHED, BUT HAVE NOW BEEN CHANGED.
  
 12)NOTE: PLEASE KNOW, RISER SHOWS "IRON"
 GROUND RODS, THIS IS OK, HOWEVER DOES
 NOT SEEM TO BE A COMMON GE. THIS SI ONLY
 A NOTE:
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-12-21 Cont ID  
Sent By dpalmer Date 2005-12-21 Time 18:57 Rev Time 0.00
Received By dpalmer Date 2005-12-21 Time 17:45 Sent To Z
Notes
2005-12-21 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE THERE HAVE BEEN MAJOR
 CHANGES IN THE SCOPE OF ELECTRICAL WORK
 AND OTHER REMODEL WORK DONE FOR
 DWELLING.
 PLEASE SEE FBC ADMINSTRATIVE 104.6.5
 WHICH REQUIRES A MAJOR ADJUSTMENT IN
 VALUATION OF PERMITTING.
 PLEASE SEE ORIG WAS INCLUSIVE OF SOME
 REMODEL AND ADDITION WORK AT $130,000
 PLEASE ADJUST.
 PLANS ARE NOW INDICATING THE ENTIRE
 HOUSE BEING REWIRED.
  
 2)NOTE:PLEASE SEE SOME RECEPTS NOW
 MISSING DUE TO SOME WALL CHANGES.210.52
  
 3)NOTE: PLEASE BE SURE TO DOUBLE CHECK
 KITCHEN COUNTERSPACE AS SOME SPACING
 SEEMS TO REQUIRE ADDITIONAL
 RECEPTS.210.52C1
  
 4)NOTE: PLEASE SEE CU'S HAVE NOW BEEN
 MOVED TO SIDE OF DWELLING, HOWEVER A NEW
 GFI RECEPT WAS NOT ADDED FOR CU'S AS
 REQUIRED PER 210.63
  
 5)NOTE: PLEASE SEE SD IN MASTER BEDRM
 SHALL BE MOVED TO BE LOCATED WITHIN 3'
 OF THE PEAK OF THE SLOPED CEILING AS
 REQUIRED UNDER NFPA-72 11.8.3.5
 PLEASE SEE THIS WAS NOT NOTICED ON
 PREVIOUS REVIEW, HOWEVER STILL IS
 REQUIRED TO MEET CODE COMPLIANCE.
  
 6)NOTE: PLEASE SEE COMPLETE CHANGE IN
 ELECTRICAL SERVICE HAS NOW CREATED SOME
 ELECTRICAL COMMENTS:
  
 A)PLEASE SEE RISER DIAGRAM AS IT SHOWS A
 200A DISCONNECT FEEDING THE 200A PANEL
 WITH 3-#1'S ETC.
  
 B)PLEASE SEE CONDUCTORS TO POOL PANEL
 ARE NOW SHOWN AS 3/0'S??
 BOTH SEEM TO BE A MIX-UP OF SORTS,
 PLEASE CORRELATEAND ADJUST.
 310.16,240.4
  
 C)PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS FROM METER/MAIN UP TO MAIN
 HOUSE. 250.32
 PLEASE ALSO SEE MISSING GROUNDING
 ELECTRODE SYSTEM AT MAIN HOUSE, SINCE
 SERVICE IS NOW MOVED.
  
 D)PLEASE SEE METER/MAIN IS SHOWN AS
 400A, AND THERE IS NO INDICATION OF THE
 OCP PROVIDED FOR SUB-PANEL FEEDERS TO
 MAIN HOUSE OR ANY OTHER BRANCH BRKRS.
 240.4,310.16 ETC.
 PLEASE ALSO VERIFY GUEST HOUSE BEING
 SHOWN WITH A MAIN DISCONNECT AND
 SUB-PANEL, AS IT IS SHOWN ON RISER BEING
 FED FROM THE METER MAIN PANEL AT GUEST
 HOUSE BLDG ALREADY?
 DISC?
  
 E)PLEASE ALSO VERIFY THE PANELS INSIDE
 THE MAIN HOUSE AS BOTH ARE SHOWN WITH
 MCB'S WHICH ARE PERMITTED ALTHOUGH NOT
 REQUIRED. THIS IS ONLY A NOTE AND NO
 CHNAGE IS NEEDED. PLEASE KNOW, IF SHOWN
 AS MCB , THEN THESE WILL BE REQUIRED.
  
 F)PLEASE SEE PANEL "C" AS THIS PANEL
 SCHEDULE SHOWS THE OCP AND FEED FOR
 GUEST HOUSE PANEL.??
 PLEASE CORRELATE WITH THE ABOVE NOTES
 AND PLANS.
  
 7)NOTE: PLEASE INDICATE THE GFI
 PROTECTION REQUIRED FOR SPA/JACUZZI AT
 MASTER BATH. THIS WAS REDLINED ON
 PREVIOUS PLANS.
 680.71
  
 8)NOTE: PLEASE SEE WHAT APPEARS TO BE
 SWITCHED RECEPTS IN A ROOM WITHOUT ANY
 MEANS OF CONTROL.
  
 9)NOTE: PLEASE PROVIDE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS.
  
 10)NOTE: PLEASE SEE BLDG AND ZONING
 COMMENTS AS BLDG ELECTRICAL AND ZONING
 CHANGES ON SITE PLANS, AND DETAILED SITE
 PLAN WILL BE REQUIRED TO BE DONE UNDER
 SEPARATE PERMITS FOR FENCE/GATES,
 FOUNTAIN, ETC. SEE OTHER REVIEWERS
 NOTES.
 ELECTRIC FOR GATES , LTS ETC SHALL BE ON
 SEPARATE PLANS AND PERMITS. PLEASE KNOW,
 WHEN SUBMITTING FOR ELECTRICAL FOR
 GATES, SUPPLY ANY GATE CONTOLLER
 SPEC/CUT SHEETS AND BE SURE THEY CONTAIN
 A LISTING FROM A NRTL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-12 Cont ID  
Sent By dpalmer Date 2005-04-12 Time 18:58 Rev Time 0.50
Received By dpalmer Date 2005-04-12 Time 18:44 Sent To B
Notes
2005-04-12 00:00:00NOTED THE FOLLOWING, NO CORRECTIONS OR
 CHANGES NEEDED.
  
 "J-BOX" SHOWN FOR WP TUB, THIS IS TO BE
 A DISC(IF HARDWIRED), GFI RECEPT OR
 RECEPT WITH GFI BRKR PROTECTION.
 680.24
  
 NOTED ON RISER, "ONLY NEW FOOTER STEEL
 IS REQUIRED TO BE ATTACHED TO GROUNDING
 ELECTRODE CONDUCTOR/SYSTEM.
  
 ARCHITECT CALLED, ALL COMMENTS WERE GONE
 OVER AND CORRECTED AS NOTED.
  
 PLANS STAMPED.
 THANK YOU

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-25 Cont ID  
Sent By dpalmer Date 2005-03-25 Time 15:09 Rev Time 1.50
Received By dpalmer Date 2005-03-25 Time 14:12 Sent To B
Notes
2005-03-25 00:00:00******* UNSAT 2ND REVIEW **********
  
 PLEASE SEE SOME ITEMS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1 OK.
  
 2)NOTE: NOTE #2 NO, PLEASE SEE MISSING
 ONE.
  
 3)NOTE: NOTE #3 OK
  
  
 4)NOTE: NOTE #4 OK, HOWEVER PLEASE SEE
 TWO SD'S WHICH APPEAR TO HAVE BEEN ADDED
 TODINING RM?
 THIS IS ONLY A NOTE AND ARE PERMITTED,
 IF SHOWN ON PLANS THEN THEY MUST BE
 INSTALLED.
  
 5)NOTE: NOTE #5 OK
  
 6)NOTE: OK, HOWEVER PLEASE CLARIFY HOW
 DETACHED BLDG IS BEING FED?
 225.31,250.32 ETC.
  
 7)NOTE: NOTE #7 OK
  
 8)NOTE: NOTE #8 OK, HOWEVER NOW THAT
 PANEL SCHEDULES HAVE BEEN SUBMITTED FOR
 REVIEW WITH CIRCUITING/OCP ETC, PLEASE
 SEE NEW COMMENTS AT END OF THIS REVIEW.
  
 9)NOTE: NOTE #9 OK
  
 10)NOTE; NOTE #10 OK
  
 11)NOTE: NOTE #11 NO, PLEASE SEE TWO
 LOCATIONS REDLINED ON PLANS ON SECOND
 FLR.
  
 12)NOTE: NOTE # 12 OK
  
 13)NOTE: NOTE #13 OK
  
 14)NOTE: NOTE #14 NO, PLEASE SEE BOTH
 AHU'S STILL DO NOT SHOW DISC'S. PLEASE
 SEE PLANS REDLINED.
  
 15)NOTE: NOTE #15 OK.
  
 16)NOTE: NOTE #16, NO, SAME NOTE. 5'
 STILL INDICATED.
  
 NEW NOTES.
  
 1)NOTE: PLEASE SEE END OF NOTES ON
 PREVIOUS REVIEW.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS IN
 SETS AND INSERT ONLY NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SEE THIS IS TO HELP IN THE
 PROCESS AND EXPEDITE PLANS. PLAN SETS
 SHALL BE COMPLETE SETS WHEN SUBMITTING.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED SEPARATELY FOR REFERENCE ONLY.
  
 2)NOTE: PLEASE SEE 424.3B FORMIN OCP
 FOR AHU'S. PLEASE SEE PLANS REDLINED.
  
 3)NOTE: PLEASE CORRELATE PANEL "B" WITH
 RISER DIAGRAM FOR POOL SUB PANEL.
 ONE SHOWS 1/0'S AND THE OTHER #1'S.
  
 4)NOTE: PLEASE SEE RANGE/OVEN SHOWN AS
 2P30A W/# 10AWG, YET RANGE IS SHOWN AS
 MIN 8KW ON LOAD CALCULATIONS.
 PLEASE VERIFY SIZE OF RANGE/OVEN AND
 PROVIDE MIN OCP/AWG.
  
 5)NOTE: PLEASE SEE PLANS AND PANEL
 SCHEDULES BOTH INDICATE WATER HEATERS ON
 BOTH LEVELS, HOWEVER LOAD CALCULATIONS
 ONLY INDICATE ONE WATER HEATER??
 PLEASECORRELATE.
  
 6)NOTE: PLEASE CORRELATE APPLIANCE LOADS
 ON LOAD CALCULATIONS AS SHOWN ON PANEL
 SCHEDULE.
 PLEASE SEE PANEL SCHEDULES INDICATE SM
 APPL AS 360VA AND 1500 VA.
 PLEASE SEE A MIN OF 1500 VA IS REQUIRED
 FOR "EACH" SMALL APPL CIRCUIT PROVIDED.
 PLEASE ADJUST PANEL SCHEDULE AND LOAD
 CALCS.
  
 7)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES WASHER AS 360 VA ALSO, YET
 LOAD CALCS INDICATE 1500 VA AS REQUIRED
 UNDER 220.16, 220.11, 210.52
  
 8)NOTE: PLEASE SEE WHIRLPOOL TUB SHOWN
 ON LOAD CALCUALTIONS, YET NOT ON PANEL
 SCHEDULES?
  
 9)NOTE: PLEASE SEE MISSING FRONT GFI
 RECEPT AS REQUIRED PER 210.52E , NOT A
 COMMENT ON FIRST REVIEW.
  
 10)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL.
 THIS IS A NOTICE ONLY GIVEN AT THIS
 TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-14 Cont ID  
Sent By dpalmer Date 2005-02-14 Time 11:48 Rev Time 1.00
Received By dpalmer Date 2005-02-14 Time 11:48 Sent To P
Notes
2005-02-14 00:00:00******** UNSAT*********
  
 1)NOTE: PLEASE SEE 210.52C1 FOR REQUIRED
 RECETPS ALONG KITCHEN COUNTERSPACE.
  
 2)NOTE: PLEASE SEE 210.8A6, ALL RECEPTS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
  
 3)NOTE: PLEASE SEE MISSING GFI FOR UPPER
 BATH RM. 210.52D/210.11C3
  
 4)NOTE:SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE SEE PLANS HAVE BEEN REDLINED FOR
 MIN LOCATIONS.
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 6)NOTE: PLEASE SEE RISER SHOWS ONE METER
 , YET PLANS INDICATES TWO? PLEASE
 CORRELATE AND SEE ZONING FOR ANY
 POSSIBLE COMMENTS FOR MORE THAN ONE
 METER.
  
 7)NOTE: PLEASE SEE 250.6,250.24,
 EQUIPMNET GROUNDING CONDUCTORS ARE
 INSTALLED AFTER THE FIRST MEANS OF DISC.
  
 8)NOTE: PLEASE PROVIDE PANEL SCHEDULE(S)
 SHOWING MIN CIRCUITS REQUIRED ALONG WITH
 OCP AND AWG.
 215.5
  
 9) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 10)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 11)NOTE: PLEASE SEE 210.52 FOR SOME
 RECEPTS MISSING IN RMS WHICH ARE BEING
 REMODELED.
  
 12)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 13)NOTE: PLEASE VERIFY LOCATION OF POOL
 PANEL, APPEARS TO BE SHOWN "IN"
 WALL/COLUMN?
 PLEASE SEE 110.26 FOR MIN CLEARENCE.
  
 14)NOTE: PLEASE SHOW ALL DISC'S REQUIRED
 FOR A/C EQUIPMENT SHOWN. 440.11
  
 15)NOTE: PLEASE SEE MISSING GFI FOR A/C
 EQUIPMENT. 210.63
  
 16)NOTE: PLEASE SEE "NOTE#6" OF
 ELECTRICAL NOTES. MENTIONS ALL RECEPT
 W/IN 5FT, TO BE GFI. PLEASE SEE THIS
 MEASUREMENT SHOULD READ 6' , HOWEVER THE
 "93" NEC CHANGED TO REQUIRE ALL RECEPTS
 SERVING KITCHEN COUNTERSPACE TO BE
 GFI/GFI PROTECTED. PLEASE SEE PREVIOUS
 NOTE;
  
 PLEASE SEE MANY OF THE ABOVE ITEMS HAVE
 BEEN REDLINED ON ONE SET OF PLANS FOR
 AREAS OF COMMENTS.
  
 PLEASE REMOVE ANY/ OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING ME.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 ** ADDED NOTE: PLEASE PROVIDE ROOM
 DESIGNATIONS ON ELECTRICAL PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-06-23 Cont ID  
Sent By adarroug Date 2006-06-23 Time 15:03 Rev Time 0.00
Received By adarroug Date 2006-06-23 Time 15:03 Sent To E
Notes
2006-06-23 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-05-31 Cont ID  
Sent By adarroug Date 2006-05-31 Time 15:54 Rev Time 0.00
Received By adarroug Date 2006-05-31 Time 15:54 Sent To E
Notes
2006-05-31 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-05-18 Cont ID  
Sent By adarroug Date 2006-05-18 Time 11:16 Rev Time 0.00
Received By adarroug Date 2006-05-18 Time 11:16 Sent To E
Notes
2006-05-18 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-03-14 Cont ID  
Sent By adarroug Date 2006-03-14 Time 15:38 Rev Time 0.00
Received By adarroug Date 2006-03-14 Time 15:38 Sent To E
Notes
2006-03-14 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-01-06 Cont ID  
Sent By adarroug Date 2006-01-06 Time 08:27 Rev Time 0.00
Received By adarroug Date 2006-01-06 Time 08:27 Sent To B
Notes
2006-01-06 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-12-13 Cont ID  
Sent By adarroug Date 2005-12-13 Time 19:30 Rev Time 0.00
Received By adarroug Date 2005-12-13 Time 19:30 Sent To E
Notes
2005-12-13 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-09-27 Cont ID  
Sent By adarroug Date 2005-09-27 Time 15:38 Rev Time 0.00
Received By adarroug Date 2005-09-27 Time 15:38 Sent To M
Notes
2005-09-27 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-06 Cont ID  
Sent By adarroug Date 2005-05-06 Time 15:43 Rev Time 0.00
Received By adarroug Date 2005-05-06 Time 15:43 Sent To B
Notes
2005-05-06 00:00:00TO "SHILL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-06 Cont ID  
Sent By adarroug Date 2005-04-06 Time 16:52 Rev Time 0.00
Received By adarroug Date 2005-04-06 Time 16:52 Sent To E
Notes
2005-04-06 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-23 Cont ID  
Sent By adarroug Date 2005-03-23 Time 11:26 Rev Time 0.00
Received By adarroug Date 2005-03-23 Time 11:26 Sent To E
Notes
2005-03-23 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-11 Cont ID  
Sent By mjacobs Date 2005-02-11 Time 10:22 Rev Time 0.00
Received By mjacobs Date 2005-02-11 Time 10:22 Sent To E
Notes
2005-02-11 00:00:00TO "E" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-04 Cont ID  
Sent By adarroug Date 2005-02-04 Time 14:46 Rev Time 0.00
Received By adarroug Date 2005-02-04 Time 14:46 Sent To Z
Notes
2005-02-04 00:00:00TO "Z"BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-28 Cont ID  
Sent By tgordon Date 2005-09-28 Time 12:03 Rev Time 0.20
Received By tgordon Date 2005-09-28 Time 12:02 Sent To  
Notes
2005-09-28 00:00:00MECH. REVISION (AS BUILT) 9-28-05

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-02-23 Cont ID  
Sent By prafter Date 2005-02-23 Time 08:24 Rev Time 1.00
Received By prafter Date 2005-02-23 Time 08:24 Sent To B
Notes
2005-02-23 00:00:00MECH. PLAN REVIEW.
  
 PROVISO:PROVIDE FOR AUX. DRAIN PAN
 UNDER A/C UNITS IN CLOSITS.2003 FBC/M
 307.2.3 .
 PAT RAFTER 561/805/6728 .
 PLEASE CALL IF THEAR ENY QUISTION.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-02-17 Cont ID  
Sent By jleech Date 2005-02-17 Time 18:30 Rev Time 0.25
Received By jleech Date 2005-02-17 Time 18:30 Sent To M
Notes
2005-02-17 00:00:00NO PLUMBING RISER DIAGRAM. UNABLE TO DO
 PLAN REVIEW.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-01-05 Cont ID  
Sent By mmclean Date 2006-01-05 Time 14:27 Rev Time 0.00
Received By mmclean Date 2006-01-05 Time 14:27 Sent To I
Notes
2006-01-05 00:00:00APPROVING REVISION FOR THE REAR DECK OF
 PROPERTY ONLY.
  
 NOTE: MUST PULL SEPERATE PERMIT FOR
 FENCE/GATE/COLUMNS/WALL WITH EASEMENT
 APPROVAL FROM THE CITY OF WEST PALM
 UTILITY DEPT.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-02-10 Cont ID  
Sent By mmclean Date 2005-02-10 Time 16:13 Rev Time 0.00
Received By mmclean Date 2005-02-10 Time 16:13 Sent To I
Notes
2005-02-10 00:00:00MUST PULL SEPERATE PERMIT FOR
 WALL/FENCE/GATE WITH UTILITY EASEMENT
 APPROVAL FROM CITY OF WEST PALM BEACH
 UTILITY DEPT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 CONSTRUCTION SERVICES
 805-6720