Plan Review Details - Permit 05020223
Plan Review Stops For Permit 05020223
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-05-06 Cont ID  
Sent By rmcdouga Date 2005-05-06 Time 14:05 Rev Time 0.00
Received By rmcdouga Date 2005-05-06 Time 14:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-03-29 Cont ID  
Sent By rmcdouga Date 2005-03-29 Time 16:45 Rev Time 0.00
Received By rmcdouga Date 2005-03-29 Time 07:26 Sent To  
Notes
2005-03-29 00:00:00DENIED
  
 1) THE TRUSS TIE DOWN SCHEDULE ON S4
 SPECIFIES A HDSA FOR MARK J. THERE IS NO
 SUCH CONNECTOR IN THE SIMPSON CATALOG.
 SHOULD THIS BE AN HD5A? ALSO INDICATE
 HOW THE SPECIFIED ALLOWABLE UPLIFT OF
 8310 WAS DETERMINED.
  
 2) THE MARK F CONNECTORS SPECIFIED FOR
 THE MG1 TRUSSES DO NOT HAVE ADEQUATE
 UPLIFT RESISTANCE.
  
 3)DETAIL 10 ON S7 WHICH IS CALLED OUT ON
 S4 FOR THE ROOF GIRDER TRUSSES INDICATES
 THAT IT IS FOR FLOOR TRUSSES. PLEASE
 CLARIFY. THE ARROW INDICATING THE
 LOCATION IS NOT AT THE WALL AND DOES NOT
 INDICATE THAT THIS CONNECTION IS FOR ALL
 OF THE CENTER GIRDERS.
  
 4) TWO OF THE ENERGY CALCS. DO NOT LIST
 THE THE 2X6 EXTERIOR WOOD FRAME WALLS
 AND INCORRECTLY SPECIFY R 19 INSULATION
 IN THE CEILING.
  
 5) SPECIFY ON THE PLANS THE MECHANICAL
 CONNECTIONS FOR THE FL36 FLOOR TRUSSES
 AT THE SECOND FLOOR STAIR OPENINGS AS
 REQUIRED BY THE TRUSS DRAWINGS. THESE
 FLOOR TRUSSES ARE NOT SHOWN ON THE
 ARCHITECTURAL PLANS.
  
 6) SUBMIT THE MIAMI-DADE NOA FOR THE
 GLASS BLOCK.
  
 7) SUBMIT THE MANUFACTURER'S SPECS. FOR
 THE ROOF SHINGLES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-02-09 Cont ID  
Sent By dpalmer Date 2005-02-09 Time 19:18 Rev Time 0.33
Received By dpalmer Date 2005-02-09 Time 19:17 Sent To  
Notes
2005-02-09 00:00:00ELECTRICAL PLANS OK, ALL THREE SETS
 STAMPED.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-02-07 Cont ID  
Sent By mamini Date 2005-02-07 Time 09:38 Rev Time 0.50
Received By mamini Date 2005-02-07 Time 09:38 Sent To  
Notes
2005-02-07 00:00:00PASSED:
  
 1. SEE PERMIT # 03101412 FOR
 UNDERGROUND UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-25 Cont ID  
Sent By nmccray Date 2005-03-25 Time 13:03 Rev Time 0.00
Received By nmccray Date 2005-03-25 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-05 Cont ID  
Sent By adarroug Date 2005-04-05 Time 11:26 Rev Time 0.00
Received By adarroug Date 2005-04-05 Time 11:26 Sent To B
Notes
2005-04-05 00:00:00TO "RMCDOUGAL" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-04 Cont ID  
Sent By adarroug Date 2005-02-04 Time 15:33 Rev Time 0.00
Received By adarroug Date 2005-02-04 Time 15:33 Sent To  
Notes
2005-02-04 00:00:00TO "COMM" BD#39/COMM SHELF

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-03-11 Cont ID  
Sent By pkrauss Date 2005-03-11 Time 07:00 Rev Time 0.55
Received By pkrauss Date 2005-03-10 Time 08:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-03-03 Cont ID  
Sent By kstevens Date 2005-03-03 Time 18:21 Rev Time 0.50
Received By kstevens Date 2005-03-03 Time 18:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-02-14 Cont ID  
Sent By eschneid Date 2005-02-14 Time 14:24 Rev Time 0.20
Received By eschneid Date 2005-02-14 Time 14:12 Sent To  
Notes
***NONE***