| 2005-02-11 00:00:00 | *********** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER DIAGRM |
| | AND PANEL "M". |
| | PLEASE SEE RISER INDICATES AS METER/MAIN |
| | COMBO WITH 200A MAIN BREAKER AND FEED |
| | THRU LUGS, HOWEVER PANEL "M" IS SHOWN AS |
| | 225A MLO W/ A 200A BRKR FEEDING |
| | PANEL"A".? |
| | PLEASE SEE RISER SHOWS 1/0'S (RATED AT |
| | 150A'S) AS THE "FEED-THRU" CONDUCTORS |
| | WHICH ARE PROTECTED BY A 200A BRKR. |
| | 310.16/310.15B6 |
| | PLEASE SEE PANEL SCHEDULE "M" SHOWS |
| | 3/0'S FEEDING PANEL "A"?? |
| | PLEASE ALSO SEE PANEL "M" CONTAINS MORE |
| | THAN 6 POSSIBLE MAINS, WHICH IS NOT |
| | PERMITTED UNDER 230.71A |
| | PLEASE PROVIDE A MCB AS SHOWN ON RISER. |
| | |
| | 2)NOTE: PLEASE SEE CIRCUITING FOR SD'S |
| | WHICH IS #21. PLEASE SEE 210.12 UNDER |
| | 2002 NEC. SD'S ARE ALSO REQUIRED TO BE |
| | ON AN ARC FAULT PROTECTED CIRCUIT. |
| | PLEASE SEE CIRCUIT #21 IS ALSO SHOWN AS |
| | "WATER HEATER" CIRCUIT. |
| | |
| | |
| | 3)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 4)NOTE: PLEASE SEE MISSINGREQUIRED |
| | GFI'S AT ISLNAD PER 210.8A6(PREVIOUS |
| | NOTE) AND ALSO SPACING PER 210.52C1-5 |
| | |
| | 5)NOTE: PLEASESEE RECEPT SHOWN ON |
| | SMALL APPL CIRCUIT WHICH IS NOT PART OF |
| | DINING RM.(MORNING RM)? A-13. |
| | THIS MAY NOT BE ON SAME CIRCUIT. |
| | 210.52B |
| | |
| | 6)NOTE: PLEASE SEE 210.52D. |
| | IN DWELLING UNITS, AT LEAST ONE WALL |
| | RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| | BATHROOMS WITHIN 900 MM (3 FT) OF THE |
| | OUTSIDE EDGE OF EACH BASIN. THE |
| | RECEPTACLE OUTLET SHALL BE LOCATED ON A |
| | WALL OR PARTITION THAT IS ADJACENT TO |
| | THE BASIN OR BASIN COUNTERTOP. |
| | |
| | 7)NOTE: PLEASE SEE PLANS INDICATE A "GAS |
| | WATER HEATER", YET PANEL SCHEDULE |
| | INDICATES ELECTRIC? |
| | PLEASE CORRELATE. |
| | |
| | 8)NOTE: PLEASE SEE "NOTES" #15, MENTIONS |
| | 250.60 FOR NEUTRAL/GROUNDING FOR RANGES |
| | AND DRYERS. PLEASE SEE THIS ART IS FROM |
| | A PREVIOUS CODE. WE ARE NOW UNDER 2002 |
| | NEC. THIS IS NOW 250.140 |
| | |
| | 9)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| | SPACING IN BDRM #5 AND DINING RM. |
| | |
| | 10)NOTE: PLEASE SEE RISER MENTIONS |
| | GROUNDING ELECTRODE "OPTIONS". PLEASE |
| | SEE 250.50 FOR MIN REQUIRED. FOOTER |
| | STEEL AND CWP (IF METAL) IS NOT AN |
| | OPTIONAL CONNECTION POINT.PLEASE |
| | ADJUST NOTE. |
| | |
| | 11)NOTE: PLEASE SEE FS 481.025 WHICH |
| | REQUIRES PLANS TO BE SIGNED WITH LEGAL |
| | SIGNATURE. PLANS APPEAR TO BE "SIGNED" |
| | WITH AN INITIAL? IF THIS IS THE LEGAL |
| | SIGNATURE, PLEASE PROVIDE A SIGNED, |
| | DATED AND SEALED NOTORIZED LETTER TO |
| | ATTEST THIS AS YOUR LEGAL SIGNATURE. |
| | THIS WILL BE PLACED IN SIGNATURE FILE |
| | FOR ANY NEED OF FUTURE REFERENCE. |
| | WE HAVE HAD A PROBLEM, WITH PLANS |
| | FORGED, SEALS STOLEN ETC. |
| | |
| | 12)NOTE: PLEASE SEE CODE REFERENCES FOR |
| | SD'S ARE FROM THE 1996 NFPA-72. PLEASE |
| | SEE WE ARE CURRNETLY UNDER THE 1999 |
| | NFPA-72. THESE REFERENCES SHOULD READ |
| | 8-1.4.1.6.2, 8-1.4.2 FOR SD |
| | REQUIREMENTS |
| | |
| | PLEASE SEE MOST OF THE ABOVE HAS BEEN |
| | REDLINED ON ONE SET OF PLANS FOR AREAS |
| | OF NOTES ABOVE. |
| | |
| | ***PLEASE REMOVE ANY/ ALL OLD VOIDED |
| | SHEETS AND INSERT NEW REVISED SHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | * ADDED NOTE **** |
| | |
| | PLEASE SEE CIRCUIT FOR WHIRLPOOL TUB |
| | SHOWS GFI PROTECTION OPTIONAL? |
| | PLEASE SEE 680.71 |