Plan Review Details - Permit 05020155
Plan Review Stops For Permit 05020155
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-06-27 Cont ID  
Sent By lmartine Date 2007-06-27 Time 11:37 Rev Time 0.00
Received By lmartine Date 2007-06-27 Time 11:37 Sent To  
Notes
2007-06-27 11:38:17REVISION FOR KNEE WALL , UPSTAIRS BATH.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-10-17 Cont ID  
Sent By lmartine Date 2006-10-17 Time 15:10 Rev Time 0.00
Received By lmartine Date 2006-10-17 Time 15:09 Sent To  
Notes
2006-10-17 15:19:11 
  
  
 REVISION TO ENCLOSE CABANA FOR STORAGE ONLY, OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-07 Cont ID  
Sent By lmartine Date 2006-08-07 Time 12:29 Rev Time 0.00
Received By lmartine Date 2006-08-07 Time 12:28 Sent To  
Notes
2006-08-07 00:00:00 
  
 "PROVISO"
 -------
  
  
  
 1]
 PERMITTED SETS OF PLANS ARE REQUIRED TO
 BE STAMPED BY THE COUNTY IMPACT OFFICE.
 (SQUARE FOOTAGE IS DIFFERENT FROM
 STAMPED SETS SUBMITTED)
  
 2)
 ENGINEERS GRADE BEAM AND COLUMN SK1 AND
 SK2 SHALL BE SIGNED AND SEALED.
  
 3)
 ENERGY EFFICIENCY FORM 600A-2004 SHALL
 BE SIGNED AND DATED BY OWNERS/AGENT.
  
  
  
  
  
  
 L. MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-07-18 Cont ID  
Sent By lmartine Date 2006-07-18 Time 16:47 Rev Time 0.00
Received By lmartine Date 2006-07-18 Time 16:47 Sent To  
Notes
2006-07-18 00:00:00 
  
  
  
 BUILDING REVIEW COMMENTS
 ------- ------ --------
  
  
  
 1)
 SUBMIT ALL PRODUCT APPROVAL REPORTS FOR
 NEW WINDOWS, DOORS AND ROOF COVER.
  
 2)
 PROVIDE ENGINEER'S STRUCTURAL PAGES
 REFERRED TO THROUGHOUT THE DRAWINGS.
 INCLUDE DETAIL FOR NEW STEEL COLUMN AT
 PUB ROOM.
  
 3)
 SUBMIT PLANS TO PALM BEACH COUNTY
 IMPACT FEE OFFICE FOR REVIEW, PROVIDE
 RECEIPT AND STAMPED PLANS BACK TO THE
 CITY.
  
 4)
 PROVIDE ENERGY EFFICIENCY REPORT.
  
 5)
 ADDITIONAL FEES OWED FOR INCREASE IN
 CONSTRUCTION VALUE.
  
  
  
  
  
  
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-04-05 Cont ID  
Sent By lmartine Date 2005-04-05 Time 13:09 Rev Time 0.00
Received By lmartine Date 2005-04-05 Time 13:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-25 Cont ID  
Sent By alange Date 2005-02-25 Time 14:06 Rev Time 0.30
Received By jleahy Date 2005-04-01 Time 08:28 Sent To Z
Notes
2005-02-25 00:00:00DENIED
  
 1.SUBMIT 2 COMPLETE SETS OF QUALITY
 ASSURANCE PRODUCT APPROVALS FOR PGT
 SH-701 AND PW-701 ALSO FOR STRAPS AND
 TIE-DOWNS.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2.SUBMIT INFORMATION ON TYPE OF SIDING
 USED.PRODUCT APPROVALS MAY BE REQUIRED
 DEPENDING ON THE TYPE OF SIDING USED.
  
 3.IF YOU WANT TO REMOVE THE ELEVATOR,
 PLEASE CROSS OF ALL INFORMATION FOR THE
 ELEVATOR.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-06-22 Cont ID  
Sent By btrobaug Date 2007-06-22 Time 11:42 Rev Time 0.00
Received By btrobaug Date 2007-06-22 Time 10:06 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-05-17 Cont ID  
Sent By btrobaug Date 2007-05-17 Time 12:20 Rev Time 2.00
Received By btrobaug Date 2007-05-17 Time 09:12 Sent To B
Notes
2007-05-17 12:20:45 
  
 REVISION DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE 350 MCM SERVICE CONDUCTORS MUSTTERMINATE IN
 350 AMP OVERCURRENT PROTECTION. 400 AMP IS ON THE PLAN.
 SEE 240.6,310.15(B)(6) AND 230.90(A).
  
 2} PLEASE PROVIDE A PANEL SCHEDULE FOR THE 400 AMP
 DISCONNECT SO THE OCP FOR THE 200 AMP FEEDERS CAN BE
 REVIEWED.
  
 3}PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 4}AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER
 250.118, SIZED PER 250.122. THEY ARE OMITTED FROM THE
 PLAN.
  
 5} THE EQUIPMENT GROUNDING CONDUCTOR MUST COMPLY WITH
 250.66, 1/0 CU. MINIMUM.
  
 6} THE FEED TO PANEL "C" IS NOT LISTED ON PANEL "B"
 SCHEDULE. VERIFYTHE FEED IS 2/0 CONDUCTORS TO THE 100
 AMP SUB PANEL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-08-17 Cont ID  
Sent By jleahy Date 2006-08-17 Time 10:22 Rev Time 1.00
Received By jleahy Date 2006-08-17 Time 10:20 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-08-03 Cont ID  
Sent By jleahy Date 2006-08-03 Time 08:01 Rev Time 1.00
Received By jleahy Date 2006-08-03 Time 08:01 Sent To M
Notes
2006-08-03 00:00:00ON PAGE E1 PANEL A ON RISER IS IN GARAGE
 AND ON PLAN IT IS IN THE PANTRY OFF THE
 KITCHEN.
  
 THE PANEL IN THE GARAGE THAT COMES OFF
 THE GUTTER SHOWN AS PANEL "A" DOES IT
 HAVE A MAIN BREAKER?THE PLAN DOES NOT
 SHOW IT!!!!!!!!!!!
  
 THE GUTTER EXISTING OR NOT MUST BE SIZED
 INACCORDANCE WITH THE CODE.
  
 NEW OFFICE ON SECOND FLOOR WILL REQUIRE
 ARC FAULT PROTECTION BECAUSE IT COULD BE
 TURNED INTO A BEDROOM IF THIS OWNER
 SELLS. PLEASE INDICATE ALL ARC FAULT
 BREAKERS IN THE PANEL(S).
  
 NO WIRE SIZES SHOWN ON RISER TO GUTTER
 AND PANEL "A"
  
 STEAM UNIT? UNIT SHOWS 5000W THIS CAN
 NOT BE PUT ON A 20A BREAKER.
  
 PANEL SCHEDULE FOR "A SHOWS 15,000 WATTS
 ON THE GENERAL LIGHTING CIRCUITS.
  
 QUESTIONS 644-7291JAKE
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-07-06 Cont ID  
Sent By btrobaug Date 2006-07-06 Time 15:24 Rev Time 1.00
Received By btrobaug Date 2006-07-06 Time 14:14 Sent To B
Notes
2006-07-06 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A LOAD CALCULATION PER
 220.31, INCLUDE ADDED LOADS. SHOW
 ELEVATOR CIRCUITING AS WELL.
  
 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC
 AND 106.3.5.4(8) FBC, ALL PANELS.
  
 3} THE RISER INDICATES A NEW METER, SHOW
 THE GROUNDING ELECTRODE SYSTEM AND SIZE
 PER 250.50 AND 250.66.
  
 4} PLACE THE GUTTER, SHOWN ON THE RISER,
 ON THE PLAN AT LOCATION.
  
 5} INDICATE WHAT THE 200 AMP DISCONNECT
 ON THE RISER AND LOCATED IN THE GARAGE,
 SERVES. SHOW CONNECTIONS ON RISER.
  
 6} THE DISCONNECTING MEANS MUST COMPLY
 WITH 225.32. IT IS UNCLEAR WHETHER THE
 FEEDERS TO THE PANELS ARE UNDER THE
 SLAB. IF NOT A DISCONNECT WOUD BE
 REQUIRED AT THE METER, SINCE THE PANELS
 ARE NOT BACK TO BACK, THEREFORE NOT AT
 THE NEAREST POINT OF ENTRANCE.
  
 7} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE SERVICE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 8} 210.63 HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR
 20-AMPERE-RATED RECEPTACLE OUTLET SHALL
 BE INSTALLED AT AN ACCESSIBLE LOCATION
 FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 7.5
 M (25 FT) OF THE HEATING,
 AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING MEANS.
  
 9} PLEASE SEE ALL SMOKE DETECTORS MUST
 BE INTERCONNECTED, WITH A BATTERY BACK
 UP, PER R313 FBC. ALSO ARC FAULT PER
 210.12. PLEASE LOCATE DETECTORS ON THE
 PLAN SO LOCATION COMPLIANCE PER 313.1
 CAN BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-04-01 Cont ID  
Sent By jleahy Date 2005-04-01 Time 08:28 Rev Time 0.30
Received By jleahy Date 2005-04-01 Time 08:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-15 Cont ID  
Sent By jleahy Date 2005-02-15 Time 09:07 Rev Time 0.45
Received By jleahy Date 2005-02-15 Time 09:06 Sent To M
Notes
2005-02-15 00:00:00NEED TO SHOW SIZE OF MOTOR FOR ELEVATOR
  
 SHOW LOCATION OF ELEVATOR EQUIPMENT.
  
 SHOW BRANCH CIRCUIT NUMBERS FOR THE
 ELEVATOR CIRCUITS.
  
 NEED LOCATION OF PANEL FOR BRANCH
 CIRCUITS.
  
 SHOW SIZE OF SERVICE MAIN. IF SMALL
 SHOW LOAD CALCULATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-06-14 Cont ID  
Sent By btrobaug Date 2007-06-14 Time 09:37 Rev Time 0.00
Received By btrobaug Date 2007-06-14 Time 09:37 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-05-08 Cont ID  
Sent By adarroug Date 2007-05-08 Time 14:15 Rev Time 0.00
Received By adarroug Date 2007-05-08 Time 14:15 Sent To E
Notes
2007-05-08 14:16:16TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 09:57 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 09:57 Sent To B
Notes
2006-10-10 09:57:41TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-10-04 Cont ID  
Sent By jroach Date 2006-10-06 Time 10:22 Rev Time 0.00
Received By adarroug Date 2006-10-04 Time 16:46 Sent To Z
Notes
2006-10-04 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-11 Cont ID  
Sent By jroach Date 2006-10-06 Time 10:22 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 11:18 Sent To Z
Notes
2006-08-11 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-01 Cont ID  
Sent By adarroug Date 2006-08-01 Time 11:08 Rev Time 0.00
Received By adarroug Date 2006-08-01 Time 11:08 Sent To E
Notes
2006-08-01 00:00:00TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-29 Cont ID  
Sent By adarroug Date 2006-06-29 Time 16:59 Rev Time 0.00
Received By adarroug Date 2006-06-29 Time 16:59 Sent To B
Notes
2006-06-29 00:00:00TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-25 Cont ID  
Sent By adarroug Date 2005-03-25 Time 11:17 Rev Time 0.00
Received By adarroug Date 2005-03-25 Time 11:17 Sent To Z
Notes
2005-03-25 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-03 Cont ID  
Sent By adarroug Date 2005-02-03 Time 08:04 Rev Time 0.00
Received By adarroug Date 2005-02-03 Time 08:04 Sent To E
Notes
2005-02-03 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-03 Cont ID  
Sent By tgordon Date 2006-08-03 Time 10:57 Rev Time 0.30
Received By tgordon Date 2006-08-03 Time 10:57 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-07 Cont ID  
Sent By tgordon Date 2006-07-07 Time 15:30 Rev Time 0.45
Received By tgordon Date 2006-07-07 Time 15:30 Sent To  
Notes
2006-07-07 00:00:00*** DENIED ***
 1) PLEASE SUBMIT MECHANICAL PLANS
 SHOWING NEW A/C SYSTEM AND DUCT WORK.
  
 2) PLEASE SUBMIT ENERGY CALCULATIONS,
 PER FBC 13-600.3.A .
  
 3) PLEASE SUBMITMANUAL J CALCULATIONS,
 PER 2004 FBC 13-607.1.ABC.1 .
  
 4) PLEASE SUBMIT DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR WINE COOLER EQUIPMENT.
  
 5) PLEASE SUBMIT DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR KITCHEN HOOD IF
 EXHAUSTED BY DUCTS.
  
 NOTE: THIS MAY BE DONE AS A REVISION TO
 MACHANICAL PERMIT #06021326 BUT MUST BE
 DONE BEFORE BUILDING PERMIT REVISION
 REVIEWS CAN BE COMPLETE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-02-16 Cont ID  
Sent By prafter Date 2005-02-16 Time 09:11 Rev Time 0.15
Received By prafter Date 2005-02-16 Time 09:11 Sent To B
Notes
2005-02-16 00:00:00 
 NO A/C MECH. WORK REFLECTED ON PLANS OR
 JOB DESCRIPTION.
  
 PAT RAFTER 561/805/6728 .

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-07 Cont ID  
Sent By jleech Date 2006-07-07 Time 07:33 Rev Time 0.00
Received By jleech Date 2006-07-07 Time 07:33 Sent To B
Notes
2006-07-07 00:00:00REVISION;
 ADDED ONE AND 1/2 BATHROOMS OK

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-03-01 Cont ID  
Sent By lmartine Date 2005-03-01 Time 15:53 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2006-10-06 Cont ID  
Sent By jroach Date 2006-10-06 Time 10:19 Rev Time 0.00
Received By jroach Date 2006-10-06 Time 10:19 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2006-08-07 Cont ID  
Sent By lmartine Date 2006-08-07 Time 14:18 Rev Time 0.00
Received By lmartine Date 2006-08-07 Time 14:18 Sent To  
Notes
2006-08-07 00:00:00SEE PLANS FOR APPROVAL

Review Stop Z ZONING
Rev No 3 Status F Date 2006-07-06 Cont ID  
Sent By mmclean Date 2006-07-06 Time 09:58 Rev Time 0.00
Received By mmclean Date 2006-07-06 Time 09:58 Sent To B
Notes
2006-07-06 00:00:00DENIED, (REVISION)
 1. NEED TO SUBMIT TWO COPY OF THE
 CURRENT SURVEYS SHOWING THE LOCATION OF
 THE WORK THAT IS SHOWN ON THE SITEPLAN.
 2. MUST SHOW THE A/C UNIT ON THE TWO
 COPY OF SURVEYS, AS WELL SITEPLANS.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status P Date 2005-03-29 Cont ID  
Sent By mmclean Date 2005-03-29 Time 10:07 Rev Time 0.00
Received By mmclean Date 2005-03-29 Time 10:04 Sent To B
Notes
2005-03-29 00:00:00APPROVING ADDITION - MASTER BEDROOM &
 BALCONY MM

Review Stop Z ZONING
Rev No 1 Status F Date 2005-03-01 Cont ID  
Sent By mmclean Date 2005-03-01 Time 12:13 Rev Time 0.00
Received By mmclean Date 2005-03-01 Time 12:13 Sent To B
Notes
2005-03-01 00:00:00DENIED,
 1. MUST PROVIDE A FULL SITEPLAN TO SCALE
 SHOWING THE EXTENDED MASTER BEDROOM &
 CLOSING EXISTING BALCONY WITH SETBACKS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 CONSTRUCTION SERVICES
 805-6720
  
 RETURNED PLANS TO LUIS M MM