| Plan Review Stops For Permit 05020069 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-02-02 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-02-02 |
Time |
16:25 |
Rev Time |
0.33 |
| Received By |
alange |
Date |
2005-02-02 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2005-02-02 00:00:00 | DENIED | | | | | | BUILDING STRUCTURAL REVIEW OK. | | | SUBMIT 2 ORIGINAL SIGNED AND SEALED | | | COPIES OF PLANS.F.S. 471.025 | | | | | | NOTE:WELDING CERTIFICATE REQUIRED ON | | | SITE AT TIME OF INSPECTION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-02-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-02-02 |
Time |
15:44 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-02-02 |
Time |
15:41 |
Sent To |
B |
|
| Notes |
| 2005-02-02 00:00:00 | | | | PLEASE SUBMIT 2 COPIES OF SIGNED AND | | | SEALED PLANS. COPY IS NOT ACCEPTABLE PER | | | F.S. 471.025. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-02-01 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-02-01 |
Time |
17:26 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-02-01 |
Time |
17:26 |
Sent To |
E |
|
| Notes |
| 2005-02-01 00:00:00 | TO "E" BOX. |
|
|
|