| 2005-02-04 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05020037 |
| | ADD: 515 COLONIAL RD |
| | CONT: O/B EBERSOLD, SEAN |
| | TEL: (561)358-9245 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | PROVIDE A FLOOR PLAN OF THE HOUSE |
| | INDICATING THE SIZE OF ALL GLAZED |
| | OPENINGS, BOTH WINDOWS, SWING DOORS AND |
| | SLIDING DOORS. |
| | |
| | 2) INDICATE WHICH OF THE GLAZED UNITS |
| | THAT ARE TO BE REPLACED. 3401.7.2.4 THE |
| | REPLACEMENT OF EXTERIOR GLAZED DOORS, |
| | SLIDING DOORS, GLASS PATIO DOORS, |
| | SKYLIGHTS AND OPERABLE AND IN OPERABLE |
| | WINDOWS WITHIN ANY 12 MONTH PERIOD SHALL |
| | NOT REQUIRE PROTECTION BUT SHALL BE HAVE |
| | OPENING PROTECTION, BUT SHALL BE |
| | REQUIRED TO HAVE OPENING PROTECTION, |
| | BUT |
| | SHALL BE DESIGNED FOR WIND PRESSURES FOR |
| | |
| | ENCLOSED BUILDINGS PROVIDED THE |
| | AGGREGATE AREA OF THE GLAZED OPENINGS IN |
| | |
| | THE DWELLING OR DWELLING UNITS. |
| | |
| | 3)2001 FL BLD CODE, 1005.4: |
| | PROVIDE EMERGENCY EGRESS WINDOWS IN |
| | SLEEPING ROOMS WITH A MINIMUM NET CLEAR |
| | OPENING HEIGTH OF 24" AND NET CLEAR |
| | OPENING WIDTH OF 20" AND A NET CLEAR |
| | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR |
| | OPENINGS ARE PERMITTED TO HAVE A NET |
| | CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH |
| | SHALL NOT BE MORE THAN 44 " ABOVE THE |
| | FINISH FLOOR. INDICATE WHICH WINDOWS |
| | ARE |
| | EGRESS WINDOWS IN BEDROOMS BEING |
| | REPLACED. |
| | |
| | 4)FBC 1005.4.5 (GLITCH AMENDMENTS JULY |
| | 1, 2003) REQUIRES AT LEAST ONE MEANS OF |
| | ESCAPE FROM A DWELLING WHEN SHUTTERED |
| | FOR IMPACT PROTECTION. THE MEANS OF |
| | ESCAPE SHALL BE WITHIN THE FIRST FLOOR |
| | OF THE DWELLING AND CAN NOT BE LOCATED |
| | IN A GARAGE. OCCUPANTS IN ANY PART OF |
| | THE DWELLING SHALL HAVE ACCESS TO IT |
| | WITHOUT HAVING TO PASS THROUGH A |
| | LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| | INDICATE HOW COMPLIANCE WILL BE |
| | ACHIEVED. |
| | |
| | 5) FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 6) PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | |
| | 7)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |