Plan Review Details - Permit 05011550
Plan Review Stops For Permit 05011550
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-03-23 Cont ID  
Sent By lursu Date 2006-03-23 Time 11:17 Rev Time 0.00
Received By lursu Date 2006-03-23 Time 11:16 Sent To  
Notes
2006-03-23 00:00:00THE EXISTING ADDRESS 3802 GEORGIA AVE
 FOR BLDG B WILL REMAIN.LU
2006-03-22 00:00:00NEEDS AS THERE ARE TWO BLDGS ON THE SAME
 SITE. SEE PERMIT #05081029 FOR OTHER
 BLDG

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2007-03-21 Cont ID  
Sent By lmartine Date 2007-03-21 Time 17:32 Rev Time 0.00
Received By lmartine Date 2007-03-21 Time 17:32 Sent To  
Notes
2007-03-21 17:36:252/23/07 REVISION FOR OFFICE WALLS

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2007-01-24 Cont ID  
Sent By shill Date 2007-01-24 Time 12:21 Rev Time 0.00
Received By shill Date 2007-01-24 Time 12:21 Sent To E
Notes
2007-01-24 12:25:02REVISION SHEETS 1 AND 3 DATED 7/24/06
  
 RESTAMP
  
 ROUTED TO DVP (REDLINES ON RESTAMP SHEETS)

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2007-01-23 Cont ID  
Sent By shill Date 2007-01-23 Time 16:11 Rev Time 0.00
Received By shill Date 2007-01-23 Time 16:11 Sent To  
Notes
2007-01-23 16:11:26REVISION, DOOR OPENING DETAIL

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-09-16 Cont ID  
Sent By shill Date 2006-09-16 Time 10:50 Rev Time 0.00
Received By shill Date 2006-09-16 Time 10:50 Sent To PC
Notes
2006-09-16 00:00:00BLDG REV, SHEETS 2 & 5

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-09-16 Cont ID  
Sent By shill Date 2006-09-16 Time 10:17 Rev Time 0.00
Received By shill Date 2006-09-16 Time 10:17 Sent To I
Notes
2006-09-16 00:00:00REVISED 2, 3, 4, 5 DATED 8/23/6
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-08-24 Cont ID  
Sent By shill Date 2006-08-24 Time 13:38 Rev Time 0.00
Received By shill Date 2006-08-24 Time 13:38 Sent To  
Notes
2006-08-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PLANS APPEAR CODE COMPLIANT, BUT
 NALYWAJKO & ASSOCIATES IS THE DESIGNER
 OF RECORD FOR THE STRUCTURAL PORTION OF
 THIS JOB.IT APPEEARS THAT SHEETS 2 AND
 5 SHOULD BE SEALED BY THE ENGINEER OF
 RECORD.ROBERT L BELL ARCHITECT PA
 CANNOT REVISE NALYWAJKO'S ENGINEERING
 DESIGN.EITHER HAVE THE STRUCTURAL
 SHEETS SIGNED, SEALED AND DATED BY
 NALYWAJKO & ASSOCIATES OR SEE
 FAC61G15-23 IN REGARDS TO TAKING OVER AN
 ENGINEER'S WORK.
  
 2.)THE TITLE BLOCK FOR NALYWAJKO &
 ASSOCIATES IS TO HAVE ALL INFORMATION
 REQUIRED BY FAC61G15-23.002.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-06-30 Cont ID  
Sent By dpalmer Date 2006-06-30 Time 08:37 Rev Time 0.00
Received By dpalmer Date 2006-06-30 Time 08:37 Sent To  
Notes
2006-06-30 00:00:002ND SETOF WEDGCOR PLANS SUBMITTED
 WITH TITLE BLOCK FOR PE.
 THIS WAS THE ONLY COMMENT FROM SAMANTAH
 HILL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-06-28 Cont ID  
Sent By shill Date 2006-06-28 Time 12:31 Rev Time 0.00
Received By shill Date 2006-06-28 Time 12:31 Sent To  
Notes
2006-06-28 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)ONE COPY OF THE WEDGECOR PLAN
 (ENGINEERING FOR METAL BUILDING) DOES
 NOT HAVE A TITLE BLOCK FOR THE ENGINEER,
 FAC61G15-23.002.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.ALL
 STRUCTURAL AND ARCHITECTURAL SHEETS
 STAMPED WITH THE EXCEPTION OF THE
 WEDGECOR PLAN LACKING A TITLE BLOCK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-04-14 Cont ID  
Sent By shill Date 2006-04-14 Time 15:30 Rev Time 0.00
Received By shill Date 2006-04-14 Time 08:53 Sent To  
Notes
2006-04-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS REVIEW, NUMBERING TO
 REMAIN THE SAME FOR CONSISTENCY
  
 1. ADDRESSED.
  
 2. DECLARE AN OCCUPANCY AND BUILDING
 TYPE FOR FBC TABLE 600 AND TABLE 500
 REVIEW.PLEASE NOTE THAT FOR TABLE 600
 REVIEW THE FLORIDA EAST COAST RAIL ROAD
 IS CONSIDERED PRIVATE PROPERTY.
  
 (SECOND REVIEW) NOT ADDRESSED.SEE
 CHAPTER 3, CHAPTER
 6, CHAPTER 5.PROVIDE INFORMATION ABOUT
 WHAT WILL BE STORED IN THIS BUILDING.
  
 (THIRD REVIEW) NOT ADDRESSED PROPERLY.
 A RESPONSE LETTER FROM THE ARCHITECT
 STATING THAT THERE ARE NO OPENINGS
 WITHIN 3' DOES NOT SHOW CODE COMPLIANCE.
 SHOW THE PROPERTY LINE IN RELATION TO
 THE BUILDING OPENINGS ON THE PLANS.
 THERE IS A DOOR NEAR THE SOUTH EAST
 CORNER WHICH MUST BE OVER THREE FEET
 FROM THE PROPERTY LINE PER TABLE 600.
 ALSO SHOW THE PROPERTY LINE ON THE
 FOUNDATION PLAN.IT APPEARS THAT ONE OF
 THE FOOTINGS CROSSES OVER THE PROPERTY
 LINE.
  
 PROVIDE INFORMATION IN REGARDS TO WHAT
 WILL BE STORED IN THE BUILDING (NOT
 ADDRESSED FROM LAST REVIEW, SEE FBC312,
 FBC308.
  
 DECLARE A SUBCLASSIFICATION, FBC312.
  
 THE OCCUPANCY NUMBERS DECLARED ARE LESS
 THAN THE FBC TABLE 1003.1, FBC 1003.1.
  
 3. ADDRESSED.
  
 4. THE WALL PANELS, ROOF PANELS, DOORS,
 WINDOWS, IMPACT PROTECTION, AND OVERHEAD
 DOOR REQUIRE FLORIDA OR LOCAL PRODUCT
 APPROVAL, FAC9B72.
 WWW.FLORIDABUILDING.ORG FOR MORE
 INFORMATION.
  
 (SECOND REVIEW)NOT ADDRESSED.A
 PERMIT CANNOT BE
 ISSUED UNTIL THIS ITEM IS ADDRESSED.
 PLEASE SEE FAC9B72.
  
 (THIRD REVIEW)A STATE PRODUCT APPROVAL
 2001 WAS SUBMITTED FOR WEDGCOR.NO
 OTHER STATE APPROVALS PROVIDED.PLEASE
 SEE FAC9B72.IF A STATE PRODUCT
 APPROVAL IS NOT AVAILABLE, PLEASE ADVISE
 AND A LOCAL PRODUCT APPROVAL WILL BE
 ISSUED USING THE NOA.
  
 5. ADDRESSED.
  
 6. ADDRESSED.
  
 7. PROVIDE THE INFORMATION REQUIRED BY
 FBC1606.1.7 ON BOTH PLANS.
  
 (SECOND REVIEW) NOT ADDRESSED.CODE
 COMPLIANCE CANNOT
 BE DETERMINED IF THERE WIND DESIGN
 CRITERIA IS NOT STATED.
  
 (THIRD REVIEW)
  
 WIND PRESSURES FOR THE OPENINGS HAVE
 BEEN HANDWRITTEN ON THE PLAN.PLEASE
 CLOUD AND INITIAL.OTHER INFORMATION IS
 STILL LACKING.SEE FBC1606.1.7.THIS
 IS TO BE INCLUDED ON BOTH SETS OF PLANS;
 THE PLAN PREPARED BY ROBERT L. BELL
 ARCHITECT (OR THE PLANS PREPARED BY
 NALYWAJKO & ASSOCIATES) AND THE PLAN FOR
 THE WEDGCOR BUILDING.
  
 THIS IS THE THIRD REQUEST FOR MR.
 RICHARD JOYCE, PE TO PROVIDE WIND DESIGN
 INFORMATION.
  
 8. ADDRESSED.
  
 9. ADDRESSED.
  
 10. THERE ARE TO BE TWO INDEPENDENT
 EXITS, FBC1004.2.
  
 THERE ARE TO BE TWO ACCESSIBLE EXITS,
 FBC11-4.1.3(9).SEE DEFINITION OF
 EGRESS IN CHAPTER 11.SHOW COMPLIANCE
 ON THE PLAN.IT IS STILL NOT CLEAR AS
 TO WHICH DOORS ARE ACCESSIBLE.YOU
 INDICATE 'ACCESSIBLE ROUTE' WITH NO
 ELEVATIONS.THE PAVING & DRAINAGE PLAN
 SHOWS A FFE OF 17-17.6 FOR THE BUILDING,
 AND 18 SHOWN IN THE PARKING AREA.IS
 THE X SUPPOSED TO BE OVER THE CURB, NOT
 THE PAVEMENT?THE SLOPE OF THE SIDEWALK
 IS NOT CLEAR.THE CURB IS NOT
 CONTINUOUS SO THERE SHOULD BE AN
 ELEVATION CHANGE, BUT THAT ISN'T CLEAR.
 CLEARLY SHOW WHICH DOORS
 ARE ACCESSIBLE, AND THAT THEYARE
 INDEPENDENT EXITS REMOTELY LOCATED
 FBC1004.1.4, LEADING TO THE PUBLIC WAY
 AS REQUIRED BY DEFINITION, DO NOT EXCEED
 TRAVEL DISTANCE FBC TABLE 1004 OR COMMON
 PATH OF TRAVEL FBC1004.1.3.
  
 11. PROVIDE INFORMATION IN REGARDS TO
 THE ACCESSIBLE ROUTE, ACCESSIBLE
 PARKING.
  
 (SECOND REVIEW) ACCESSIBLE ROUTE NOT
 SHOWN FBC11-4.1.2(1) AND (2).
 ACCESSIBLE PARKING DOES NOT COMPLY WITH
 CITY STANDARD, SEE ATTACHED.
 SHOW ACCESSIBLE ROUTE INTO THE BUILDING.
 NO FLOOR ELEVATIONS PROVIDED.
  
 (THIRD REVIEW)PLANS SHOULD SHOW CODE
 COMPLIANCE.THERE APPEARS TO BE A 6'
 INCH ELEVATION DIFFERENCE ON THIS
 PROPERTY AND IT IS NOT CLEAR HOW THIS IS
 ADDRESSED FOR ACCESSIBILITY.STATING
 THAT SOMETHING IS AN ACCESSIBLE PATH IS
 NOT SUFFICIENT.PROVIDE ELEVATIONS,
 ELEVATION CHANGE OR SLOPE AS REQUESTED.
  
 THE PAVING & DRAINAGE PLAN ACCESSIBLE
 PARKING DETAIL DOES NOT COMPLY WITH THE
 CITY OF WPB STANDARD.
  
 12. ADDRESSED.
  
 13. ADDRESSED.
  
 14. A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 NEW COMMENTS, SECOND REVIEW:
  
 15. ADDRESSED.
  
 16. DOCUMENTS PREPARED BY AN ARCHITECT
 AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS
 FAC61G16.
  
 (THIRD REVIEW) PLANS SUBMITTED ARE NOT
 SEALED.
  
 17. ADDRESSED.
  
 18.ADDRESSED.
  
 19.ADDRESSED.
  
 20.SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW WILL BE CHARGED IF THE
 COMMENTS ARE NOT ADDRESSED A THIRD TIME.
  
 (THIRD REVIEW) A 4X FEE HAS BEEN
 CHARGED.NO RESUB FEE DUE FOR FOURTH
 REVIEW.
  
 NEW COMMENT, THIRD REVIEW
  
 21.CLARIFY SCOPE OF WORK.ONE PLAN
 STATES THAT THERE IS A SLAB ONLY, FLOOR
 PLAN SHOW EXISTING INTERIOR PARTITIONS,
 AND I HAVE BEEN INFORMED THAT THE
 INTERIOR PARTITIONS SHOWN AS EXISTING
 ARE NOT THERE NOW.PROVIDE DETAILS FOR
 NEW WALLS, CONNECTIONS FROM EXISTING TO
 NEW WALLS IF ANY.
  
 22.A VALUATION ADJUSTMENT HAS BEEN
 DONE (USING SBCCI VALUATION TABLE FROM
 2003).A BILL INCLUDING THE ADDITIONAL
 FEES DUE AS WELL AS THE 4X FEE CHARGED
 IS ATTACHED.THIS MUST BE PAID PRIOR TO
 RESUBMITTAL.
  
 23.EFFECTIVE JAN 1, 2006 THE SEAL FOR
 THE ENGINEER IS TO STATE "LICENSE", NOT
 "CERTIFICATE" FAC61G15-23.
  
 A COPY OF THE PLAN HAS BEEN RETAINED.
  
 WHEN RESUBMITTING, ALL CHANGES ON THE
 PLAN ARE TO BE CLEARLY INDICATED WITH
 CLOUDS AND REVISION NUMBERS.REPLACE
 ONLY SHEETS WHICH HAVE CHANGED.SUBMIT
 OLD SHEETS SEPARATELY.TO EXPEDITE PLAN
 REVIEW, PROVIDE A TRANSMITTAL LETTER
 EXPLAINING HOW EACH ITEM HAS BEEN
 ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-10-04 Cont ID  
Sent By shill Date 2005-10-04 Time 15:38 Rev Time 2.00
Received By shill Date 2005-10-04 Time 15:37 Sent To  
Notes
2005-10-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS REVIEW, NUMBERING TO
 REMAIN THE SAME FOR CONSISTENCY
  
 1. ADDRESSED.
  
 2. DECLARE AN OCCUPANCY AND BUILDING
 TYPE FOR FBC TABLE 600 AND TABLE 500
 REVIEW.PLEASE NOTE THAT FOR TABLE 600
 REVIEW THE FLORIDA EAST COAST RAIL ROAD
 IS CONSIDERED PRIVATE PROPERTY.
  
 NOT ADDRESSED.SEE CHAPTER 3, CHAPTER
 6, CHAPTER 5.PROVIDE INFORMATION ABOUT
 WHAT WILL BE STORED IN THIS BUILDING.
  
 3. ADDRESSED.
  
 4. THE WALL PANELS, ROOF PANELS, DOORS,
 WINDOWS, IMPACT PROTECTION, AND OVERHEAD
 DOOR REQUIRE FLORIDA OR LOCAL PRODUCT
 APPROVAL, FAC9B72.
 WWW.FLORIDABUILDING.ORG FOR MORE
 INFORMATION.
  
 NOT ADDRESSED.A PERMIT CANNOT BE
 ISSUED UNTIL THIS ITEM IS ADDRESSED.
 PLEASE SEE FAC9B72.
  
 5. ADDRESSED.
  
 6. ADDRESSED.
  
 7. PROVIDE THE INFORMATION REQUIRED BY
 FBC1606.1.7 ON BOTH PLANS.
  
 NOT ADDRESSED.CODE COMPLIANCE CANNOT
 BE DETERMINED IF THERE IS NOT WIND
 DESIGN CRITERIA.
  
 8. ADDRESSED.
  
 9. ADDRESSED.
  
 10. THERE ARE TO BE TWO INDEPENDENT
 EXITS, FBC1004.2.
  
 11. PROVIDE INFORMATION IN REGARDS TO
 THE ACCESSIBLE ROUTE, ACCESSIBLE
 PARKING.
  
 ACCESSIBLE ROUTE NOT SHOWN
 FBC11-4.1.2(1) AND (2).
  
 ACCESSIBLE PARKING DOES NOT COMPLY WITH
 CITY STANDARD, SEE ATTACHED.
  
 SHOW ACCESSIBLE ROUTE INTO THE BUILDING.
 NO FLOOR ELEVATIONS PROVIDED.
  
 12. ADDRESSED.
  
 13. ADDRESSED.
  
 14. A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 NEW COMMENTS:
  
 15. THE TITLE BLOCK FOR THE ARCHITECT IS
 TO COMPLY WITH FAC61G16.THE CA NUMBER
 IS MISSING.
  
 16. DOCUMENTS PREPARED BY AN ARCHITECT
 AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS
 FAC61G16.
  
 17. THE SEAL FOR THE LANDSCAPE ARCHITECT
 IS TO BE DATED, FS481.321.
  
 18.ACCESSIBLE BATHROOM DETAILS WERE
 GIVEN, BUT THE BATHROOM IS NOT ON THE
 FLOOR PLAN.THE SITE PLAN SHOWS AN
 OFFICE.CLARIFY SO THAT CODE COMPLIANCE
 CAN BE DETERMINED.
  
 19.PROVIDE A DETAIL FOR THE ACCESSIBLE
 SINK, FBC11-4.24.
  
 20.SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW WILL BE CHARGED IF THE
 COMMENTS ARE NOT ADDRESSED A THIRD TIME.
  
 WHEN RESUBMITTING, ALL CHANGES ON THE
 PLAN ARE TO BE CLEARLY INDICATED WITH
 CLOUDS AND REVISION NUMBERS.REPLACE
 ONLY SHEETS WHICH HAVE CHANGED.SUBMIT
 OLD SHEETS SEPARATELY.TO EXPEDITE PLAN
 REVIEW, PROVIDE A TRANSMITTAL LETTER
 EXPLAINING HOW EACH ITEM HAS BEEN
 ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-17 Cont ID  
Sent By shill Date 2005-02-17 Time 16:25 Rev Time 2.00
Received By shill Date 2005-02-17 Time 14:51 Sent To  
Notes
2005-02-17 00:00:00PERMIT #05011550
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1. SEE ZONING CORRECTION.A PERMIT
 CANNOT BE ISSUED UNTIL ZONING
 REQUIREMENTS HAVE BEEN MET.
  
 2. DECLARE AN OCCUPANCY AND BUILDING
 TYPE FOR FBC TABLE 600 AND TABLE 500
 REVIEW.PLEASE NOTE THAT FOR TABLE 600
 REVIEW THE FLORIDA EAST COAST RAIL ROAD
 IS CONSIDERED PRIVATE PROPERTY.
 FBC104.3.1.1.
  
 3. THE EXISTING BUILDING ON THE SURVEY
 ENCROACHES THE PROPERTY LINE.PROVIDE A
 SITE PLAN CLEARLY SHOWING DISTANCE FROM
 THE PROPERTY LINE.
  
 4. THE WALL PANELS, ROOF PANELS, DOORS,
 WINDOWS, IMPACT PROTECTION, AND OVERHEAD
 DOOR REQUIRE FLORIDA OR LOCAL PRODUCT
 APPROVAL, FAC9B72.
 WWW.FLORIDABUILDING.ORG FOR MORE
 INFORMATION.
  
 5. HOW WILL THE NEW BLOCK WALL TIE INTO
 THE STEEL STRUCTURE?PROVIDE STRUCTURAL
 DETAIL ON A WALL SECTION.
  
 6. THE STEEL BUILDING ENGINEERING IS TO
 HAVE A TITLE BLOCK IN COMPLIANCE WITH
 FAC61G15-23.002.
  
 7. PROVIDE THE INFORMATION REQUIRED BY
 FBC1606.1.7 ON BOTH PLANS.
  
 8. PROVIDE WALL SECTIONS WHICH CORRELATE
 TO THE FLOOR PLAN.THERE APPEAR TO BE
 DIFFERENT CONDITIONS BUT NO DETAILS ARE
 PROVIDED.
  
 9. IMPACT PROTECTION REQUIRED,
 FBC1606.1.4.IF SHUTTERS ARE USED, SHOW
 THEIR STORAGE LOCATION.IF SHUTTERS ARE
 STORED VERTICALLY, PROVIDE A RACK
 DETAIL.
  
 10. THERE ARE TO BE TWO INDEPENDENT
 EXITS, FBC1004.2.
  
 11. PROVIDE INFORMATION IN REGARDS TO
 THE ACCESSIBLE ROUTE, ACCESSIBLE
 PARKING.
  
 12. A LINTEL SCHEDULE IS PROVIDED; HOW
 DOES THIS CORRELATE WITH THE PLAN?
  
 13. ARE THE BATHROOM WALLS NEW?PROVIDE
 STRUCTURAL DETAIL; WALLS, CEILING.
  
 14. A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-02-12 Cont ID  
Sent By dpalmer Date 2007-02-12 Time 12:19 Rev Time 0.00
Received By dpalmer Date 2007-02-12 Time 12:06 Sent To PC
Notes
2007-02-12 12:20:51ELECTRICAL PLANS FOR MAIN FLOOR LAYOUT TO BE VERIFIED
 IN FIELD TO CORRELATE WIHT REVISED RISER.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-01-24 Cont ID  
Sent By dpalmer Date 2007-01-24 Time 18:40 Rev Time 0.00
Received By dpalmer Date 2007-01-24 Time 18:14 Sent To  
Notes
2007-01-24 18:41:59** UNSAT **
  
 1) NOTE: PLEASE SEE PLANS WERE SUBMITTED FOR RE-STAMP
 HOWEVER THEY ARE IN FACT REVISIONS TO THE LAST SET AND
 THE ORIGINAL ELECTRICAL PLANS ON RECORD.
 PLEASE SEE RISER HAS NO BEEN COMPLETELY REVISED TO
 INCLUDE A NEW ELECTRICAL PANEL WITH REVISIONS MADE.
 PLEASE PROVIDE ELECTRICAL PLANS WHICH INDICATE THE
 LOCATIONS OF THE REVISED ITEMS ON PLANS.
 110.26, 408.7, 240.24 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 ** PLEASE SUBMIT TWO COMPLETE COPIES OF PLANS FOR
 REVISIONS. IF ONLY NEEDING A RE-STAMP, PLEASE KNOW THAT
 ONLY ONE COPY OF PLANS WOULD BE NEEDED HOWEVER THEY
 WOULD NEED TO CORRELATE TO THE LATEST REVISION
 SUBMITTED AND STAMPED BY THE CITY, REV DATE 8/23/06.
  
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVOEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-26 Cont ID  
Sent By dpalmer Date 2006-09-26 Time 08:17 Rev Time 0.00
Received By dpalmer Date 2006-09-26 Time 07:57 Sent To PC
Notes
2006-09-26 00:00:00ELEC REV OK,
  
 CROSSES OUT THE PLUMB ON REVSIONS AS NO
 REV'S WERE MADE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-28 Cont ID  
Sent By dpalmer Date 2006-06-28 Time 20:59 Rev Time 0.00
Received By dpalmer Date 2006-06-28 Time 20:46 Sent To  
Notes
2006-06-28 00:00:00** REDLINED **
  
 PLEASE SEE PREVIOUS REQUEST FOR GEC TO
 BE SHOWN ON DETAIL PER MIN SIZING PER
 250.66
  
 ( 1/0 MIN REDLINED AND REQ'D)

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-22 Cont ID  
Sent By dpalmer Date 2006-03-22 Time 19:45 Rev Time 0.00
Received By dpalmer Date 2006-03-22 Time 18:18 Sent To  
Notes
2006-03-22 00:00:00IN ELEC FOR THE FIRST REVIEW.
 ****** UNSAT ******
  
 ** PLEASE KNOW, THIS IS THE FIRST TIME
 ELECTRICAL PLANS ARE BEING SUBMITTED FOR
 REVIEW.
  
  
 1)NOTE: PLEASE KNOW, THE PERMIT
 VALUATION SHALL BE ADJUSTED AND
 INCREASED FOR TOTAL SCOPE OF. PLEASE
 KNOW, THE EXISTING PARTIAL WALL ON NORTH
 AND EAST ELEVATION WAS VISUALLY VERIFIED
 FOR SCOPE OF WORK.
 PLEASE SEE FBC ADMINISTRATIVE CODE
 SECTION, 104.6.5.
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THIS IS NO LONGER A "REPAIR", AND
 WILL BE REQUIRED TO COMPLY WITH FBC
 CHAPTER 34
 ** IT IS NOTED THAT ALL ELECTRICAL
 SYSTEMS ARE GOING TO BE NEW.
  
 2)NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS. PLEASE SEE CIRCUITS FOR OH
 DOORS. (19). PLEASE ALSO PROVIDE HP
 RATINGS FOR THESE MOTORS SO THAT LOADS,
 AWG, AND OCP CAN BE VERIFIED.
 215.5
  
 3)NOTE: PLEASE SEE THE HAND DRAWN
 DELETION ON PLANS OF A/C UNITS, MUST BE
 SIGNED, DATED BY THE ENGINEER, HOWEVER
 SINCE PLANE WILLBE RE-PRINTED DUE TO
 COMMENTS, PLEASE REMOVE AT THAT TIME.
 215.5
  
 4)NOTE: PLEASE INDICATE THE "TAPPED"
 CONDUCTOR SIZS FROM GUTTER TO MAINS.
 PLEASE KNOW, NO "EUIPMENT GROUNDING
 CONDUCTOR" IS INSTALLED UNTIL AFTER THE
 FIRST MEANS OF DISCONNECT. 250.6,250.24B
  
 5)NOTE: PLEASE INDICATE THE SIZE OF THE
 GE CONDUCTOR. 250.66 PLEASE SEE PLANS
 MENTIONS TO SEE DETAIL, HOWEVER NO SIZE
 IS SHOWN.
  
 6)NOTE: PLEASE REFERENCE THE 2002 NEC
 WHICH IS CURRENTLY IN EFFECT.
  
 7) NOTE: PLEASE SEE THE POSSIBILITY OF
 NOTES PERTAINING TO THE MEANS OF EGRESS
 IN REAR OF BLDG(EAST ) WHICH SHOWS
 EGRESS TO FEC EASEMENT WHICH IS NOT THE
 PUBLIC RIGHT OF WAY.
 PLEASE SEE THIS MAY AFFECT ELECTRICAL.?
  
  
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLYINSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE KNOW, ONE COPY OF ANY
 OLD/VOIDED SHEETS SHALL BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-06-29 Cont ID  
Sent By nmccray Date 2006-06-29 Time 15:26 Rev Time 0.00
Received By nmccray Date 2006-06-29 Time 15:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-03-31 Cont ID  
Sent By mwennerg Date 2006-03-31 Time 11:09 Rev Time 0.00
Received By mwennerg Date 2006-03-31 Time 11:09 Sent To  
Notes
2006-03-31 00:00:00******DENIED******
  
 1) PLEASE BE ADVISED THAT THIS IS THE
 THIRD FIRE REVIEW. EACH REVIEW HAS ASKED
 IF THIS BUILDING IS FIRE SPRINKLERED.
 PLEASE INDICATE AND SHOW LAYOUT IF
 APPLICABLE. ALSO NOTE THAT SEPARATE SHOP
 DRAWINGS AND PERMIT WILL BE REQUIRED.
  
 2) PLANS WILL BE STAMPED WHEN RETURNED
 FOR OTHER REVIEW COMMENTS.
  
 3) PLEASE SHOW REQUIRED ADDRESS ON
 ELEVATIONS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
2006-03-22 00:00:00NEW LAYOUT AND EM/EXT LTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-10-05 Cont ID  
Sent By mwennerg Date 2005-10-05 Time 15:17 Rev Time 0.00
Received By mwennerg Date 2005-10-05 Time 15:17 Sent To  
Notes
2005-10-05 00:00:00******OK******
  
 AS PER THE FIRST FIRE REVIEW, IF
 BUILDING IS FIRE SPRINKLER PROTECTED,
 SEPARATE SHOP DRAWINGS AND PERMIT IS
 REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-03-02 Cont ID  
Sent By nmccray Date 2005-03-02 Time 10:03 Rev Time 0.00
Received By nmccray Date 2005-03-02 Time 09:57 Sent To  
Notes
2005-03-02 00:00:00DENIED:
  
 1) PLEASE INDICATE THE OCCUPANCY OF THIS
 BUILDING.
  
 2) WHAT WILL BE STORED IN THIS
 STRUCTURE?
  
 3) WILL THIS BUILDING BE FIRE SPRINKLER
 PROTECTED. IF SO SEPARATE PLAN AND
 PERMIT ARE REQUIRED.
  
 4) BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-03-03 Cont ID  
Sent By adarroug Date 2007-03-03 Time 16:43 Rev Time 0.00
Received By adarroug Date 2007-03-03 Time 16:43 Sent To P
Notes
2007-03-03 16:43:49TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-02-08 Cont ID  
Sent By adarroug Date 2007-02-08 Time 08:47 Rev Time 0.00
Received By adarroug Date 2007-02-08 Time 08:46 Sent To E
Notes
2007-02-08 08:48:14TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-01-10 Cont ID  
Sent By adarroug Date 2007-01-10 Time 09:40 Rev Time 0.00
Received By adarroug Date 2007-01-10 Time 09:40 Sent To B
Notes
2007-01-10 09:40:31TO "SHILL" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-01-10 Cont ID  
Sent By adarroug Date 2007-01-10 Time 09:11 Rev Time 0.00
Received By adarroug Date 2007-01-10 Time 09:11 Sent To B
Notes
2007-01-10 09:11:53TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 08:58 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 08:58 Sent To E
Notes
2006-09-18 00:00:00TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 16:47 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 16:46 Sent To B
Notes
2006-08-03 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 14:45 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 14:45 Sent To  
Notes
2006-06-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-23 Cont ID  
Sent By adarroug Date 2006-02-23 Time 15:35 Rev Time 0.00
Received By adarroug Date 2006-02-23 Time 15:35 Sent To  
Notes
2006-03-21 00:00:00TO COMM BOARD #31
2006-02-23 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-15 Cont ID  
Sent By adarroug Date 2005-09-15 Time 14:10 Rev Time 0.00
Received By adarroug Date 2005-09-15 Time 14:10 Sent To  
Notes
2005-09-20 00:00:00TO "COMM" BD#2
2005-09-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-25 Cont ID  
Sent By adarroug Date 2005-02-25 Time 15:44 Rev Time 0.00
Received By adarroug Date 2005-02-25 Time 15:44 Sent To P
Notes
2005-02-25 00:00:00TO KSTEVENS DESK
 TAKEN OF BD#16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-10 Cont ID  
Sent By adarroug Date 2005-02-10 Time 14:40 Rev Time 0.00
Received By adarroug Date 2005-02-10 Time 14:40 Sent To  
Notes
2005-02-10 00:00:00TO "COMM" BD#16

Review Stop P PLUMBING
Rev No 6 Status P Date 2007-03-13 Cont ID  
Sent By pschmitz Date 2007-03-13 Time 10:33 Rev Time 0.00
Received By pschmitz Date 2007-03-13 Time 10:32 Sent To  
Notes
2007-03-13 10:33:05REVISION FOR VENTS

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-06-22 Cont ID  
Sent By pschmitz Date 2006-06-22 Time 10:10 Rev Time 0.00
Received By pschmitz Date 2006-06-22 Time 10:09 Sent To  
Notes
2006-06-22 00:00:00SEPERATE PERMIT FOR IRRIGATIION.

Review Stop P PLUMBING
Rev No 4 Status N Date 2006-05-18 Cont ID  
Sent By pschmitz Date 2006-05-17 Time 14:26 Rev Time 0.00
Received By pschmitz Date 2006-05-17 Time 14:26 Sent To  
Notes
2006-05-18 00:00:00MEET WITH LEO 5-17-06 WENT OVER PREVIOUS
 PLAN REVIEW COMMENTS
 1)RELOCATED WATER COOLER, NEXT SERVICE
 SINK, WHICH WILL ALOW FOR REQUIRED CLEAR
 FLOOR SPACE.
 2)RPZ IS EXISTING.
 3) PLUMBING RISER HAS BEEN CORRECTED TO
 INCLUDE SERVICE SINK.
 4) LINCENSED IRRIGATIOIN CONTRACTOR WILL
 BE RESPONSIBLE FOR THE PERMIT.
 QUESTIONS CONTACT PAUL SCHMITZ
 561-805-6692

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-03-25 Cont ID  
Sent By pschmitz Date 2006-03-25 Time 12:13 Rev Time 0.00
Received By pschmitz Date 2006-03-25 Time 12:13 Sent To  
Notes
2006-03-25 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
 1) PREVIOUS NOTE,SHOW CLEAR FLOOR SPACE
 FOR THE WATER COLLER.
  
 ?11-4.15 DRINKING FOUNTAINS AND WATER
 COOLERS.
  
 ?11-4.15.1 MINIMUM NUMBER. DRINKING
 FOUNTAINS OR WATER COOLERS REQUIRED
 TO BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.15.
  
 ?11-4.15.2 SPOUT HEIGHT. SPOUTS SHALL
 BE NO HIGHER THAN 36 INCHES (915
 MM), MEASURED FROM THE FLOOR OR GROUND
 SURFACES TO THE SPOUT OUTLET (SEE
 FIGURE 11-27(A)).
  
 ?11-4.15.3 SPOUT LOCATION. THE SPOUTS
 OF DRINKING FOUNTAINS AND WATER
 COOLERS SHALL BE AT THE FRONT OF THE
 UNIT AND SHALL DIRECT THE WATER FLOW
 IN A TRAJECTORY THAT IS PARALLEL OR
 NEARLY PARALLEL TO THE FRONT OF THE
 UNIT.THE SPOUT SHALL PROVIDE A FLOW
 OF WATER AT LEAST 4 INCHES (100 MM)
 HIGH SO AS TO ALLOW THE INSERTION OF A
 CUP OR GLASS UNDER THE FLOW OF
 WATER.ON AN ACCESSIBLE DRINKING
 FOUNTAIN WITH A ROUND OR OVAL BOWL, THE
 SPOUT MUST BE POSITIONED SO THE FLOW
 OF WATER IS WITHIN 3 INCHES (75 MM)
 OF THE FRONT EDGE OF THE FOUNTAIN.
  
 ?11-4.15.4 CONTROLS. CONTROLS SHALL
 COMPLY WITH ?11-4.27.4.UNIT
 CONTROLS SHALL BE FRONT MOUNTED OR
 SIDE MOUNTED NEAR THE FRONT EDGE.
  
 ?11-4.15.5 CLEARANCES.
  
 ?11-4.15.5(1) WALL- AND POST-MOUNTED
 CANTILEVERED UNITS SHALL HAVE A
 CLEAR KNEE SPACE BETWEEN THE BOTTOM
 OF THE APRON AND THE FLOOR OR
 GROUND AT LEAST 27 INCHES (685 MM)
 HIGH, 30 INCHES (760 MM) WIDE, AND
 17 INCHES TO 19 INCHES (430 MM TO
 485 MM) DEEP (SEE FIGURE 11-27(A)
 AND FIGURE 11-27(B)).SUCH UNITS
 SHALL ALSO HAVE A MINIMUM CLEAR
 FLOOR SPACE 30 INCHES BY 48 INCHES
 (760 MM BY 1220 MM) TO ALLOW A
 PERSON IN A WHEELCHAIR TO APPROACH
 THE UNIT FACING FORWARD.
  
 ?11-4.15.5(2) FREE-STANDING OR
 BUILT-IN UNITS NOT HAVING A CLEAR
 SPACE UNDER THEM SHALL HAVE A CLEAR
 FLOOR SPACE AT LEAST 30 INCHES BY
 48 INCHES (760 MM BY 1220 MM) THAT
 ALLOWS A PERSON IN A WHEELCHAIR TO
 MAKE A PARALLEL APPROACH TO THE UNIT
 (SEE FIGURE 11-27(C) AND
 FIGURE 11-27(D)).THIS CLEAR FLOOR
 SPACE SHALL COMPLY WITH ?11-4.2.4.
  
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-10-22 Cont ID  
Sent By pschmitz Date 2005-10-22 Time 13:19 Rev Time 0.00
Received By pschmitz Date 2005-10-22 Time 13:19 Sent To  
Notes
2005-10-22 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW BUILDING "B"
 DENIED
 PREVIOUS PLAN REVIEW NOTES, PLEASE
 PROVIDE A TRANSMITTAL LETTER, ADDRESSING
 COMMENTS FORM EACH PLAN REVIEWER.
 THIS WILL HELP EXPIDITE YOUR PLAN REVIEW
 PREVIIOUS PLAN REVIEW NUMBERS TO REMAIN
 THE SAME.
 1) NOT ADDRESSED
 2) NEED INFORMATION FROM NOTE 1, TO
 ADDRESS NOTE 2.
 3) OK, NOTE ON SHT D-1, EX BACK FLOW.
 4) NEED INFORMATION FROM NOTE 1TO
 ADDRESS NOTE 4.
 NEW NOTES:
 A) SHT D-1 PLUMBING RISER DETAIL.
 SECOND SINK ON RISER IS NOT SHOWN ON
 REST ROM DETAIL.
 B)SHOW LOCATION OF REST ROOM ON PLANS.
 C)SEPERATE PLANS AND PERMIT REQUIRED,F
 FOR IRIGATION
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-01 Cont ID  
Sent By kstevens Date 2005-03-01 Time 10:26 Rev Time 1.00
Received By kstevens Date 2005-03-01 Time 10:26 Sent To FIRE
Notes
2005-03-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) INDICATE THE OCCUPANCY OF THE
 BUILDING AS THIS WILL SET THE
 REQUIREMENTS FOR MINIMUM FIXTURE
 REQUIREMENTS. FURTHER COMMENTS MAY BE
 ADDED DEPENDING ON THE RESPONSE FROM
 THIS COMMENT. SECTION 104.2.1.
 2) AT THE MINIMUM A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1, AND POSSIBLY A
 SERVICE SINK.
 3) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
 4) THE FOLLOWING INFORMATION IS REQUIRED
 TO SHOW COMPLIANCE WITH CHAPER 11:
 A) CLEAR FLOOR SPACE 11-4.16.2.
 B) HEIGHT & CLEARANCES 11-4.19.2. - 29"
 CLEARANCE REQUIRED. 28" CLEARANCE SHOWN
 0N PLANS.
 C) CLEAR FLOOR SPACE 11-4.19.3
 D) EXPOSED PIPES & SURFACES 11-4.19.4 -
 INDICATE IF THE PIPES WILL BE INSULATED
 OR IF THE PIPES ARE FRAMED AND COVERED
 WITH A PANEL.
 E) FAUCETS 11-4.19.5
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 2006-06-29 Cont ID  
Sent By mmclean Date 2006-06-29 Time 15:36 Rev Time 0.00
Received By mmclean Date 2006-06-29 Time 15:35 Sent To B
Notes
2006-06-29 00:00:00OK PER SHIRLEY GRAHAM

Review Stop Z ZONING
Rev No 4 Status F Date 2006-04-20 Cont ID  
Sent By credford Date 2006-04-20 Time 10:15 Rev Time 0.00
Received By credford Date 2006-04-20 Time 10:14 Sent To  
Notes
2006-04-20 00:00:00APRIL 20, 2006 - FAILED
  
 1.LANDSCAPE PLAN DOES NOT MATCH SITE
 PLAN.
  
 2.PLANTING HOLE INSTRUCTIONS ARE
 MISSING.
  
 3.NOTES REGARDING RENEWAL OF SUPPORTS
 MISSING.
  
  
 CAROLYN A. REDFORD
 EXT. (561) 822-1449

Review Stop Z ZONING
Rev No 2 Status P Date 2005-12-02 Cont ID  
Sent By mmclean Date 2005-12-02 Time 15:36 Rev Time 0.00
Received By mmclean Date 2005-12-02 Time 15:36 Sent To  
Notes
2005-12-02 00:00:00INFORMAL APPROVED BY RANDALL G AND
 SIGNED OFF BY SHIRLEY GRAHAM.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-02-08 Cont ID  
Sent By mmclean Date 2005-02-08 Time 16:08 Rev Time 0.00
Received By mmclean Date 2005-02-08 Time 16:08 Sent To B
Notes
2005-02-08 00:00:00PLANS WERE FOUND FILED AND GIVEN TO ME
 BY LUIS MARTINEZ TO REVIEW.SPOKE WITH
 GRACE WHO HAD MET WITH OWNER AND TOLD
 THEM THAT THEY NEEDED TO DO AN INFORMAL
 SITEPLAN REVIEW.MUST CALL PLANNING &
 ZONING AT 822-1435 TO MEET WITH GRACE OR
 ANOTHER PLANNER TO START THE PROCESS AND
 APPROVAL FOR INFORMAL, BEFORE PLANS CAN
 BE REVIEWED BY THE OTHER TRADES.PLANS
 GIVEN TO LUIS MARTINEZ.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 CONSTRUCTION SERVICES
 805-6720