Plan Review Details - Permit 05011539
Plan Review Stops For Permit 05011539
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-05-09 Cont ID  
Sent By jhiggins Date 2005-05-09 Time 14:40 Rev Time 0.00
Received By jhiggins Date 2005-05-09 Time 14:40 Sent To  
Notes
2005-05-09 00:00:005163 TYLERLAKES BLVD IS ASSIGNED
 SPECIFICALLY TO THIS PCN; THE HAVERHILL
 ADDRESS WAS THE SITUS ADDRESS FOR THE
 COMMERCE PARK IN GENERAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2006-05-09 Cont ID  
Sent By shill Date 2006-05-09 Time 14:46 Rev Time 0.00
Received By shill Date 2006-05-09 Time 14:46 Sent To  
Notes
2006-05-09 00:00:00****CORRECTIONS****
 ****RESTAMP****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THE ENGINEER'S SIGNATURE IS A
 PHOTOCOPY, STEEL BUILDING STRUCTURALS.
 THIS MUST BE AN ORIGINAL WET SIGNATURE
 PER FBPE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2006-05-09 Cont ID  
Sent By shill Date 2006-05-09 Time 14:46 Rev Time 0.00
Received By shill Date 2006-05-09 Time 14:46 Sent To  
Notes
2006-05-09 00:00:00RESTAMP, BUILDING PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2006-04-19 Cont ID  
Sent By shill Date 2006-04-19 Time 10:38 Rev Time 0.00
Received By shill Date 2006-04-19 Time 10:37 Sent To  
Notes
2006-04-19 00:00:00****CORRECTIONS****
 ****THIRD DENIED RESTAMP****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS LIST:
  
 1.-2.)ADDRESSED
  
 3.)SHEET P101 IS NOT IN OUR APPROVED
 SET.SUBMIT FOR REVIEW.
  
 NOT ADDRESSED.THIRD REQUEST.
  
 4.)THE STRUCTURAL SHEETS FOR VP
 BUILDINGS WERE NOT IN THE SET SUBMITTED
 FOR RESTAMP.
  
 NOT ADDRESSED.
  
 NEW COMMENTS:
  
 5.-7.)ADDRESSED.
  
 8.)I HAD REQUESTED THAT ELECTRIC
 SHEETS WHICH HAVE BEEN REVISED NOT BE
 SUBMITTED FOR RESTAMP.THIS REQUEST WAS
 DISREGARDED.ONLY SUBMIT THE MOST
 CURRENT APPROVED DRAWINGS FOR RESTAMP.
  
 NOT ADDRESSED, ELECTRIC SHEETS
 SUBMITTED.
  
 9.)ADDRESSED.
  
 THIRD REVIEW NEW COMMENTS:
  
 10.)SOME SHEETS HAVE A REVISION DATE
 OF 4/1/05, OUR APPROVED SET HAS 6/14/05
 FOR THOSE SHEETS.
  
 11.)THE METAL STRUCTURALS HAVE NOT
 BEEN SUBMITTED FOR RESTAMP.NEITHER HAS
 THE GARAGE.DO YOU HAVE AN APPROVED SET
 OF THOSE PLANS?
  
 12.)PRIOR TO SUBMITTING FOR RESTAMP A
 FOURTH TIME, CONTRACTOR IS TO MAKE AN
 APPOINTMENT WITH APRIL PICARILLO,
 561-805-6658.CHECK ALL SHEETS.THE
 PLANS SUBMITTED FOR RESTAMP ARE TO MATCH
 THE PLANS IN OUR FILE.OTHERWISE, IT IS
 NOT A RESTAMP, IT IS A REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2006-03-23 Cont ID  
Sent By shill Date 2006-03-23 Time 16:48 Rev Time 0.00
Received By shill Date 2006-03-23 Time 16:48 Sent To  
Notes
2006-03-23 00:00:00****CORRECTIONS****
 ****RESTAMP****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)ALL SHEETS ARE TO BE SIGNED,
 SEALED, DATED ORIGINALS, FAC61G15.
  
 THE ARCHITECT'S SEAL IS NOT DATED,
 FAC61G1-16.
  
 2.)THE MECHANICAL SHEETS SUBMITTED
 HAVE A REVISION DATE OF 6/14/05, BUT THE
 ISSUED PERMIT SET IS DATED 4/01/05.
 EITHER SUBMIT THESE SHEETS AS A REVISION
 OR SUBMIT CORRECT REVISION DATE.
  
 NOT ADDRESSED.SAME SHEETS SUBMITTED.
  
 3.)SHEET P101 IS NOT IN OUR APPROVED
 SET.SUBMIT FOR REVIEW.
  
 NOT ADDRESSED.
  
 4.)THE STRUCTURAL SHEETS FOR VP
 BUILDINGS WERE NOT IN THE SET SUBMITTED
 FOR RESTAMP.
  
 NOT ADDRESSED.
  
 NEW COMMENTS:
  
 5.)LANDSCAPE SHEETS WERE SUBMITTED.
 WE DO NOT HAVE ANY LANDSCAPE SHEETS IN
 THE APPROVED PERMIT PACKAGE.
  
 6.)SHEETS A301, 302, 303, 402, 501,
 502 WERE MISSING FROM THE RESTAMP
 PACKAGE.
  
 7.)THE COVER SHEET DOES NOT HAVE A
 TITLE BLOCK FAC61G16.
  
 8.)I HAD REQUESTED THAT ELECTRIC
 SHEETS WHICH HAVE BEEN REVISED NOT BE
 SUBMITTED FOR RESTAMP.THIS REQUEST WAS
 DISREGARDED.ONLY SUBMIT THE MOST
 CURRENT APPROVED DRAWINGS FOR RESTAMP.
  
 9.)THE FOLLOWING SHEETS HAVE BEEN
 STAMPED: CIVILS, S110, S501, F101.IT
 IS NOT NECESSARY TO SUBMIT THESE SHEETS
 AGAIN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2006-03-23 Cont ID  
Sent By shill Date 2006-03-23 Time 07:51 Rev Time 0.00
Received By shill Date 2006-03-23 Time 07:51 Sent To  
Notes
2006-03-23 00:00:00****CORRECTIONS****
 ****STORAGE RACK SUBMITTAL****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)ALL SUBMITTALS AND SHOP DRAWINGS
 ARE TO BE REVIEWED BY DESIGNER OF
 RECORD.WHEN RESUBMITTING, INDICATE
 THAT THIS IS A SUBMITTAL RATHER THAN A
 REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-12-25 Cont ID  
Sent By shill Date 2005-12-25 Time 13:32 Rev Time 1.50
Received By shill Date 2005-12-25 Time 13:03 Sent To  
Notes
2005-12-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
  
 1.)ALL SHEETS ARE TO BE SIGNED,
 SEALED, DATED ORIGINALS, FAC61G15.
  
 2.)THE MECHANICAL SHEETS SUBMITTED
 HAVE A REVISION DATE OF 6/14/05, BUT THE
 ISSUED PERMIT SET IS DATED 4/01/05.
 EITHER SUBMIT THESE SHEETS AS A REVISION
 OR SUBMIT CORRECT REVISION DATE.
  
 3.)SHEET P101 IS NOT IN OUR APPROVED
 SET.SUBMIT FOR REVIEW.
  
 4.)THE STRUCTURAL SHEETS FOR VP
 BUILDINGS WERE NOT IN THE SET SUBMITTED
 FOR RESTAMP.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-11-21 Cont ID  
Sent By shill Date 2005-11-21 Time 10:40 Rev Time 0.50
Received By shill Date 2005-11-21 Time 10:39 Sent To PC
Notes
2005-11-21 00:00:00REVISED A101, A102, SKYLIGHT PRODUCT
 APPROVAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-08-05 Cont ID  
Sent By shill Date 2005-08-05 Time 08:01 Rev Time 0.50
Received By shill Date 2005-08-05 Time 08:01 Sent To PC
Notes
2005-08-05 00:00:00PROVISO - SEPARATE PERMIT SKYLIGHTS
 +61/-61PSF

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-07-25 Cont ID  
Sent By shill Date 2005-07-25 Time 16:20 Rev Time 3.00
Received By shill Date 2005-07-25 Time 08:11 Sent To  
Notes
2005-07-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PLEASE PROVIDE THE IMPACT FEE
 RECEIPT FOR THE WAREHOUSE/OFFICE
 BUILDING.
  
 2.)SEE PREVIOUS LIST IN REGARDS TO
 RESIDENT INSPECTOR PROGRAM.PLANS
 APPEAR CODE COMPLIANT, BUT AN APPROVED
 INSPECTION SCHEDULE MUST BE ON FILE WITH
 THE CITY PRIOR TO PERMIT ISSUANCE.
 PLEASE CONTACT HAROLD PISKURA,
 561-805-6711.
  
 3.)PROVISO ? SEPARATE PERMIT FOR
 SKYLIGHTS TO MEET +61/-61 PSF OR REVISE
 DESIGN PRESSURE ON PLAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-05-10 Cont ID  
Sent By shill Date 2005-05-10 Time 14:21 Rev Time 5.00
Received By shill Date 2005-05-10 Time 09:50 Sent To  
Notes
2005-05-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) SEE THE PREVIOUS LIST IN REGARDS TO
 ITEMS 2, 3 AND 5.THE CONTRACTOR?S
 STATEMENT IS ACKNOWLEDGED THAT THESE
 ITEMS WILL BE ADDRESSED PRIOR TO
 ISSUANCE.
  
 2.)THE ADDRESS FOR THIS PARCEL WILL BE
 5163 TYLERLAKES BLVD AS THE MAIN
 ENTRANCE IS ON TYLERLAKES.IF MY
 UNDERSTANDING IS NOT CORRECT PLEASE
 CONTACT JOHN HIGGINS TO HAVE THE ADDRESS
 REVISED, 561-822-1239. PLEASE REVISE THE
 APPLICATION TO REFLECT THE CORRECT
 ADDRESS.
  
 2.)PLEASE BE ADVISED THAT THREE COPIES
 OF ALL PLAN DOCUMENTS ARE REQUIRED.THE
 ADDITIONAL COPY IS FOR THE RESIDENT
 INSPECTOR.
  
 3.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 4.)PLEASE HAVE THE ENGINEER
 RESPONSIBLE FOR THE STRUCTURAL CALCS
 READ FAC61G15.23.002.THE TITLE BLOCK
 IS NOT COMPLIANT.THERE IS ANOTHER
 ENGINEER?S NAME (WILLIAM H. SCHMIDT,
 STRUCTURAL ENGINEER) ON SOME OF THE
 CALCS CONTAINED IN THE BOOK TITLED
 ?STRUCTURAL CALCULATIONS FOR FRITO-LAY
 WEST PALM BEACH, FL?.IF SEALING AN
 INDEX OR COVER SHEET IN LIEU OF SEALING
 EACH SHEET, THE COVER SHEET SHOULD
 CONTAIN MORE INFORMATION THAN JUST THE
 JOB NAME.THE PRINTED NAME AND LICENSE
 NUMBER OF THE PERSON SEALING THE
 DOCUMENT SHOULD INCORPORATED INTO EACH
 SHEET.A TITLE BLOCK IS STILL REQUIRED
 ON EACH SHEET EVEN IF ONLY THE COVER
 SHEET IS SEALED.PLEASE READ THE
 SECTION AND SUBMIT CALCS WHICH ARE
 COMPLIANT WITH THE BOARD RULES.THERE
 MAY BE OTHER REQUIREMENTS WHICH I HAVE
 NOT SPECIFICALLY REFERRED TO.
  
 5.)THE STRUCTURAL CALCS ?SQUARE
 FOOTING DESIGN? HAS A 1.33 DURATION
 FACTOR.THE ?GENERAL FOOTING? HAS A
 1.33 SHORT TERM INCREASE.PAGE CP5 ACI
 FACTORS REFERS TO THE 1.3 SHORT TERM
 INCREASE.SHEET G1 WIND SPEED CALC ALSO
 USES 1.3 AS A MULTIPLIER; UNCLEAR TO ME
 WHAT THIS NUMBER IS.I WAS UNABLE TO
 FIND EITHER THE SHORT TERM OR THE
 DURATION FACTOR LOAD INCREASES IN
 ACI318-02.PLEASE CLARIFY.
  
 6.)THE CALCS FOR THE STEEL BUILDING
 ALSO REQUIRES A TITLE BLOCK.
  
 7.)PLEASE HAVE MR. MARK VANNICE, PE
 READ FAC61G15-23.002.THE ROOF DECK
 CALCS ARE INCLUDED ON THE COVER SHEET
 SEALED BY MR. GURLEY, BUT HAS AN INK
 SEAL (AS WELL AS BEING SIGNED AND DATED)
 BY MR. VANNICE.IT IS NOT CLEAR WHO IS
 RESPONSIBLE FOR THESE CALCS.THE SEAL
 IS TO BE A RAISED SEAL AND A TITLE BLOCK
 IS REQUIRED IF MR. VANNICE IS
 RESPONSIBLE.
  
 8.)STRUCTURAL DRAWINGS FOR THE STEEL
 BUILDING INDICATE WIND DESIGN PRESSURE
 OF COMPONENTS AND CLADDING AS 49PSF
 INTERIOR, 40PSF EDGE.SAME NUMBER FOR
 POSITIVE AND NEGATIVE?SEE ASCE7-98,
 FBC CHAPTER 16; USUALLY THE EDGES ARE
 SUBJECT TO GREATER PRESSURE THAN THE
 INTERIOR.PLEASE CLARIFY.
  
 9.)FOR THE MODIFIED ROOF PRODUCT
 APPROVAL, PLEASE REMOVE SHEETS WHICH DO
 NOT APPLY TO THIS JOB SO THAT CODE
 COMPLIANCE CAN BE DETERMINED.PLEASE
 KEEP SHEETS 1-6, 35-36.ALSO INCLUDE
 THE ONE TWO SHEETS OF WHICHEVER APPROVED
 ASSEMBLY (FROM SHEETS 7 THROUGH 34) THAT
 YOU ARE USING.PLEASE NOTE THAT IF THE
 ASSEMBLY REFERS TO PRODUCT LIMITATION
 #9, ENHANCED FASTENING FOR CORNER ZONES
 CANNOT BE USED.
  
 10.) IT IS NOT CLEAR IF THE ACCESSIBLE
 ROUTE IS COMPLIANT.AT THE ACCESSIBLE
 ENTRANCE FOR THE OFFICE, GRADING &
 DRAINAGE PLAN, ELEVATIONS FOR THE
 SIDEWALK ARE GIVEN, 22.25 AND 21.75.
 THEY APPEAR TO BE APPROXIMATELY 8? APART
 (IS THE DISTANCE GREATER?), GIVING A
 SLOPE OF 1:16 (5.2%).THEREFORE WOULD
 NEED TO SHOW COMPLIANCE AS A RAMP
 (GREATER THAN 1:20, 5%).PLEASE
 CLARIFY ACTUAL SLOPE. NOTE - CLARIFIED
 WITH ENGINEER, RAMP INDICATED ON PLAN -
 OKAY SMH
  
 11.) THE SEAL REQUIRES A DATE,
 FAC61G1-15 (ARCHITECTURAL SHEETS).
  
 12.)MONUMENT SIGN, A201 HAS INCORRECT
 ADDRESS.ALSO, THE SIGN REQUIRES A
 SEPARATE PERMIT.IT IS NOT NECESSARY TO
 REMOVE THE DETAIL FROM THE PLAN.
  
 13.)THE ROOF DESIGN PRESSURE IS 61,
 SKYLIGHT PRODUCT APPROVAL HAS A
 LIMITATION OF +52.5/-56.1.
  
 14.) THE SCALE ON A700 FOR THE SERVICE
 GARAGE SHOWS THE GARAGE AS APPROXIMATELY
 90? DEEP, REQUIRING TWO MEANS OF EGRESS.
 THIS DIMENSION IS NOT CONSISTENT WITH
 THE STRUCTURALS.PLEASE ADDRESS.
  
 15.) SUBMIT A PERMIT APPLICATION FOR THE
 GARAGE.THE PACKAGE CAN REMAIN ONE
 PACKAGE BUT TWO PERMIT NUMBERS MUST BE
 ASSIGNED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-14 Cont ID  
Sent By shill Date 2005-02-11 Time 11:52 Rev Time 5.00
Received By shill Date 2005-02-10 Time 11:42 Sent To  
Notes
2005-02-14 00:00:00PERMIT #05011539
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
  
 1. THE ADDRESS ON THE APPLICATION
 CONFLICTS WITH THE ADDRESS IN OUR
 RECORDS (5163 TYLERLAKES BOULEVARD).IF
 THERE ARE ANY QUESTIONS REGARDING
 ADDRESSING, PLEASE CONTACT JOHN HIGGINS,
 561-822-1239.
  
 2. A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3. IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025 FOR MORE
 INFORMATION.
  
 4. PROVIDE AN ORIGINAL SOILS
 INVESTIGATION REPORT (PHOTOCOPY
 PROVIDED), SIGNED AND SEALED AS PER
 FAC61G15-23.002.
  
 5. FBC*105.3, INSPECTION SERVICES.THE
 BUILDING OFFICIAL MAY MAKE, OR CAUSE TO
 BE MADE BY OTHERS, THE INSPECTIONS
 REQUIRED BY SECTION 105, IN ACCORDANCE
 WITH PART XII OF CHAPTER 468, FLORIDA
 STATUTES.HE/SHE MAY ACCEPT REPORTS OF
 INSPECTORS OF RECOGNIZED INSPECTION
 SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO
 THEIR QUALIFICATIONS AND RELIABILITY.A
 CERTIFICATE CALLED FOR BY ANY PROVISION
 OF THE TECHNICAL CODES SHALL NOT BE
 BASED ON SUCH REPORTS UNLESS THE SAME
 ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE
 OWNER TO EMPLOY AN INSPECTION SERVICE IN
 THE FOLLOWING INSTANCES SHOULD THE
 BUILDING SIZE, STYLE OR DESIGN DEMAND
 DETAILED, LENGTHY OR CONSTANT
 INSPECTIONS BEYOND THE NORMAL SCHEDULING
 ALLOWANCES FOR INSPECTIONS BY CITY
 STAFF:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I
 OR TYPE II CONSTRUCTION;
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS;
 3. WHERE THE CONCRETE DESIGN IS BASED ON
 COMPRESSIVE STRENGTH (F?C) IN EXCESS OF
 3000 PSI;
 4. FOR PILE DRIVING;
 5. FOR BUILDINGS WITH AREA GREATER THAN
 20,000 SQUARE FOOT;
 6. FOR BUILDINGS MORE THAN 2 STORIES IN
 HEIGHT;
 7. FOR BUILDINGS AND STRUCTURES OF
 UNUSUAL DESIGN OR METHODS OF
 CONSTRUCTION.
  
 PLEASE SEE THE CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 AND CONTACT HAROLD PISKURA, INSPECTION
 SERVICES MANAGER/ABO, 561-805-6711.
  
 6. PROVIDE A TITLE BLOCK FOR THE SEALED
 STRUCTURAL CALCS, FAC61G15-23.002.
  
 7. PROVIDE A SURVEY FOR THIS PROPERTY.
  
 8. THE NUMBER OF ACCESSIBLE PARKING
 SPACES IS TO COMPLY WITH
 FBC11-4.1.2(5)(A) (SITE PLAN).
  
 9. THE STRIPING FOR THE ACCESSIBLE
 PARKING SPACE DETAIL (TYPICAL PARKING
 STALLS, SITE PLAN) IS TO COMPLY WITH THE
 CITY OF WEST PALM BEACH STANDARD, SEE
 ATTACHED.PLEASE NOTE THAT THE STRIPING
 APPEARS CORRECT GRAPHICALLY BUT THE
 DIMENSION (12IN.) IS INCORRECT (SHOULD
 BE 16IN).
  
 10. CERTIFICATE OF AUTHORIZATION NUMBER
 IS TO BE ON THE TITLE BLOCK FOR THE
 HASKELL COMPANY, FAC61G1-16.003, 004.
  
 11. SEPARATE PERMIT REQUIRED FOR THE
 SERVICE GARAGE.
  
 12. THE SQUARE FOOT TOTALS ON THE SITE
 PLAN, SHEET A-100, AND THE ENERGY CALC
 ARE NOT CONSISTENT.
  
 13. SHEET A100, MEANS OF EGRESS, REFERS
 TO THE UBC.ALL REFERENCES ARE TO CITE
 GOVERNING CODE, FBC2001.PLEASE REVISE;
 ALSO AN ADDITIONAL OCCUPANCY
 CLASSIFICATION OF ASSEMBLY HAS BEEN
 ADDED THERE WHICH DOES NOT APPEAR IN THE
 OCCUPANCY SECTION.THE 15/SF DOES NOT
 COMPLY WITH FBC REQUIREMENTS FOR
 ASSEMBLY.
  
 14. SHEET A100, OCCUPANCY AND MEANS OF
 EGRESS, DECLARES STORAGE OCCUPANCY FOR
 THE WAREHOUSE, FBC312.IT APPEARS THAT
 WITH 225 PEOPLE PER SHIFT, THE PRINCIPAL
 USE IS NOT STORAGE.PLEASE CLARIFY.
  
 15. SHEET A100, OCCUPANCY AND MEANS OF
 EGRESS, DECLARES STORAGE OCCUPANCY FOR
 THE VEHICLE MAINTENANCE BUILDING,
 FBC312.PLEASE SEE FBC305.
  
 16. S110, STRUCTURAL NOTE J2 REFERS TO
 NEVADA; PLEASE REVISE TO FLORIDA.
  
 17. S110, STRUCTURAL NOTE K, REFERS TO
 UBC1701; PLEASE REVISE.
  
 18. PROVIDE THE MANEUVERING CLEARANCE
 FOR DOOR 119A, 127A, 127B, SHEET A-401,
 FBC CHAPTER 11 FIGURE 25.
  
 19. THE STAIR RAILS ALSO SERVE AS A
 GUARDRAIL AND ARE TO COMPLY WITH FBC1015
 (OVER 30? ABOVE GROUND), SHEET A502 AND
 ANY OTHER APPLICABLE DETAILS.
  
 20. PROVIDE DESIGN CRITERIA FOR THE
 HANDRAIL AND GUARDRAIL, A502,
 FBC1608.2.1 AND FBC1608.2.2
 RESPECTIVELY.
  
 21. PROVIDE A DETAIL FOR THE RAMP
 HANDRAIL AND GUARDRAIL.
  
 22. SHOW COMPLIANCE WITH FBC11-4.3.2,
 ACCESSIBLE ROUTE.IT APPEARS THAT THE
 CROSS SLOPE FOR THE SIDEWALK (GRADING &
 DRAINAGE PLAN) EXCEEDS THE 1:50 ALLOWED
 BY FBC11-4.3.7.
  
 23. PROVIDE THE INFORMATION REQUIRED BY
 FBC1606.1.7.NOTE THAT DESIGN PRESSURES
 FOR COMPONENTS AND CLADDING WERE NOT
 PROVIDED.
  
 24. THE VP STEEL STRUCTURALS (SHEET 8
 FOR VEHICLE MAINTENANCE BUILDING, SHEET
 23 FOR OFFICE/WAREHOUSE) SPECIFY A
 DESIGN PRESSURE OF 285PSF FOR ZONE 3.
 THIS EXCEEDS THE DESIGN PRESSURE OF THE
 ROOFING PRODUCT APPROVALS SUBMITTED.
 ADDRESS.
  
 25. ORIGINAL SIGNATURE AND DATE REQUIRED
 (VP STEEL STRUCTURALS).PHOTOCOPIES OF
 A SIGNATURE NOT ACCEPTABLE PER FBPE.
 ALSO SOME SHEETS WEREN?T SIGNED AND
 DATED; OTHERS WERE NOT SIGNED, SEALED
 AND DATED.ALL DOCUMENTS SUBMITTED BY
 AN ENGINEER FOR PUBLIC RECORD ARE TO
 BEAR AN ORIGINAL SEAL, SIGNATURE AND
 DATED FAC61G15-23.002.
  
 26. EACH SHEET IS TO HAVE A TITLE BLOCK
 WITH THE INFORMATION REQUIRED BY
 FAC61G15-23.002 (VP STEEL STRUCTURALS).
  
 27. FOR PRODUCT APPROVALS FL3600.4 AND
 FL3612.8 SUBMITTED, PROVIDE A COPY OF
 THE TEST REPORT AND INSTALLATION
 INSTRUCTIONS.
  
 28. INDICATE ON FL3612.8 WHICH PRODUCT
 YOU ARE INSTALLING.WINDOWS AND DOORS
 WHICH ARE NOT IMPACT REQUIRE IMPACT
 PROTECTION FBC1606.1.4.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-05-05 Cont ID  
Sent By dpalmer Date 2006-05-05 Time 13:20 Rev Time 0.00
Received By dpalmer Date 2006-05-05 Time 10:52 Sent To PC
Notes
2006-05-05 00:00:00REDLINED,
  
 LOCK OFF DEVICE SHALL BE APPROVED BY THE
 AHJ FOR EM LTS.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-11-16 Cont ID  
Sent By dpalmer Date 2005-11-16 Time 18:46 Rev Time 0.30
Received By dpalmer Date 2005-11-16 Time 18:37 Sent To  
Notes
2005-11-16 00:00:00REDLINED, ONLY WAREHOUSE AREAMEETS
 EXCEPTION OF UNINTERUTED AREAS.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-07 Cont ID  
Sent By dpalmer Date 2005-07-07 Time 16:40 Rev Time 1.25
Received By dpalmer Date 2005-07-07 Time 16:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-04-22 Cont ID  
Sent By dpalmer Date 2005-04-22 Time 13:05 Rev Time 2.00
Received By dpalmer Date 2005-04-21 Time 18:14 Sent To  
Notes
2005-04-22 00:00:00** UNSAT **
  
 PLEASE SEE SOME ITEMS FROM PREVIOUS
 REVIEW.
  
 1)NOTE: OK.
  
 2)NOTE: OK
  
 3)NOTE: NO, PLEASE SEE 250.32,250.50 FOR
 GROUNDING AT DETACHED BLDG. PLEASE SEE
 GROUNDING RISER FOR SERVICE BLDG SHOWS
 ATTACHMENT FOR GROUND RODS ONLY.
 PLEASE SEE ANY METAL CWP AND FOOTER
 STEEL IS ALSO REQUIRED.
  
 4)NOTE:OK
  
 5)NOTE: OK, HOWEVER PLEASE VERIFY WHERE
 NOTE IS LOCATED FOR EXCEPTION METHOD AND
 "LOCK-OFF TO BE PROVIDED. 700.12E
  
 6)NOTE: SUBMITTED SPECS HOWEVER, PLEASE
 SEE A CIRCUIT FOR A BATTERY CHARGER HAS
 NOT BEEN ADDED AT FIRE PUMP LOCATION??
 PLEASE SEESPECS FOR FIRE PUMP AND FIRE
 PUMP CONTROLLER. THIS SHOWS FULL LOAD
 CURRENT AND LOCKED ROTOR OTHER THAN WHAT
 IS REQUIRED UNDER NEC 430 TABLES.
 PLEASE KNOW, THE NEC SHALL BE USED FOR
 SIZING.
 PLEASE BE SURE A NOTE ON RISER DIAGRMA
 STATES REQUIREMENT FOR LOCKED ROTOR OCP.
  
 7)NOTE: OK
  
 8)NOTE: OK
  
 NEW NOTES:
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENT
 REQUESTED THAT GARAGE SERVICE BLDG BE
 UNDER SEPARATE PERMIT, HOWEVER RESPONSE
 LETTER MENTIONS PLANS REMOVED BUT THEY
 WERE NOT SUBMITTED UNDER SEPARATE
 PERMIT.
  
 2)NOTE:PLEASE CLARIFY FIRE RATING FOR IT
 ROOM. UNDER NFPA-75CHAPTER 3
 NEC 645.2
  
 3)NOTE: PLEASE SEE SIGNAGE WILL BE
 REQUIRED AT MAIN ENTRANCE FOR LOCATION
 OF ADDITIONAL KNOW BOX TO BE LOCATTED AT
 THE NEAREST ENTRANCE TO LOCATION OF MDP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-17 Cont ID  
Sent By dpalmer Date 2005-02-17 Time 14:42 Rev Time 2.50
Received By dpalmer Date 2005-02-17 Time 14:41 Sent To  
Notes
2005-02-17 00:00:00*********** UNSAT **********
  
 1)NOTE: PLEASE SEE MDP WHICH IS 277/480V
 IS FEEDING PANEL "RC"WHICH INDICATES
 120/208V
 215.5
  
 2)NOTE: PLEASE SEE 225.31,,32 ETC FOR
 MAIN DISCONNECTING MEANS REQUIRED AT
 DETACHED BLDG.
 PLEASE SEE PANEL"HC" SHOWN AS MLO.
  
 3)NOTE: PLEASE INCLUDE AND SHOW
 GROUNDING AT DETACHED BLDG PER 250.32
  
 4)NOTE: PLEASE PROVIDE GROUNDING DETAIL
 FOR GROUNDING ELECTRODE SYSTEM AND FOR
 ALL TRANSFORMERS. PLEASE SEE
 250.50,250.30 FOR REQUIRED ATTACHMENTS.
 PLEASE SEE FBC 104.2.1, CODE SHALL NOT
 BE REFERENCED IN WHOLE OR IN PART AND
 SHALL BE SPECIFIC.
  
 5)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE. PLEASE SEE SOME MISSING.
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF EM/EXT LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 6)NOTE: PLEASE PROVIDE ALL COMPLETE
 INFORMATION FOR FIRE PUMP, FIRE PUMP
 CONTROLLER. THIS IS TO INCLUDE ACTUAL
 SIZING OF THIS EQUIPMENT AT THIS TIME.
 PLEASE INCLUDE ALL MANUFACTURE SPEC/CUT
 SHEETS.
 PLEASE SHOW ALL SIZING INCLUDING LOCKED
 ROTOR AS REQUIRED UNDER 695.4B1
 THE OVERCURRENT PROTECTIVE DEVICE(S)
 SHALL BE SELECTED OR SET TO CARRY
 INDEFINITELY THE SUM OF THE LOCKED-ROTOR
 CURRENT OF THE FIRE PUMP MOTOR(S) AND
 THE PRESSURE MAINTENANCE PUMP MOTOR(S)
 AND THE FULL-LOAD CURRENT OF THE
 ASSOCIATED FIRE PUMP ACCESSORY EQUIPMENT
 WHEN CONNECTED TO THIS POWER SUPPLY.
 PLEASE PROVIDE INFORMATION FOR
 DISCONNECTING MEANS PER
 230.76,230.79,110.27 ETC.
  
 7)NOTE: PLEASE PROVIDE ALL WINDING LOAD
 CALCULATIONS AND INFORMATION FOR BLDG
 REVIEW OF LIGHT POLES, INCLUDING
 FIXTURES.
 MUST MEET FBC 140 MPH.
  
 8)NOTE: PLEASE SEE NOTE #15 ON
 SHEETEP101.
 IF THIS SYSTEM IS TO BE INCLUDED WITH
 THIS PERMIT PACKAGE, THEN SUBMIT ALL
 SPECS FOR DEVICES TO BE USED AND SUBMIT
 INFORMATION FOR EGRESS/ FAIL SAFE
 OPERATION ETC. PLEASE SEE FIRE REVIEW
 FOR THIS REQUIRED INFORMATION.
  
 PLEASE SEE MANY OF THE ABOVE ITEMS AND
 LOCATIONS OF THESE ITEMS ARE
 REDLINED/HIGH-LIGHTED ON ONE SET OF
 PLANS.
  
 PLEASE BE SURE TO SEE POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW . IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-04-06 Cont ID  
Sent By mamini Date 2005-04-06 Time 15:29 Rev Time 1.00
Received By mamini Date 2005-04-06 Time 15:29 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-02-03 Cont ID  
Sent By mamini Date 2005-02-03 Time 09:57 Rev Time 1.00
Received By mamini Date 2005-02-03 Time 09:57 Sent To  
Notes
2005-02-03 00:00:00FAILED:
  
 1. THE ISSUE OF THE 50' U.E. AND MAKING
 THE PROPOSED SEWER LINE PRIVET (S-4 AND
 ON) MUST BE RESOVLVE AND THE OUTCOME
 RECORDED.
 2. SHEET 9 OF 13, REVISE THE 8"X 2-1/2"
 DIRECT TAP AND BACKFLOWS ASSEMBLIES PER
 PUBLIC UTILITIES'S REQUIREMENTS.
 3. PLEASE ADDRESS AND IMPLEMENT
 COMMENTS FROM THE PUBLIC UTILITIES
 PRIOR TO THE NEXT SUBMITRAL.
 4. PLEASE VERIY THE PARKING STALLS
 DETAILS, THE OUT TO OUT DIMENSION FOR
 THE STRIPING SHOULD BE 1'-8", PER CITY
 REQUIREMENTS.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-11-16 Cont ID  
Sent By mwennerg Date 2005-11-16 Time 14:50 Rev Time 0.00
Received By mwennerg Date 2005-11-16 Time 14:50 Sent To  
Notes
2005-11-16 00:00:00REVISION DATED 9/23/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-07-26 Cont ID  
Sent By mwennerg Date 2005-07-26 Time 14:32 Rev Time 0.00
Received By mwennerg Date 2005-07-26 Time 14:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-05-18 Cont ID  
Sent By mwennerg Date 2005-05-18 Time 13:47 Rev Time 0.00
Received By mwennerg Date 2005-05-18 Time 13:47 Sent To  
Notes
2005-05-18 00:00:001) PLEASE REFER TO BUILDING COMMENTS IN
 REGARDS TO FAC REQUIREMENTS.
  
 2) IT IS UNDERSTOOD THAT AN APPROVED
 ADDRESS NUMBER WILL BE LOCATED ON THE
 BUILDING. PLEASE ILLUSTRATE THIS ON THE
 PLANS.
  
 3) PLEASE PROVIDE THE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL GUARDS AND
 RAILINGS.
  
 4) PLEASE SHOW THE LOCATIONS OF FIRE
 HYDRANTS. THE FIRE DEPARTMENT CONNECTION
 SHALL BE LOCATED WITHIN 150' FROM THE
 CLOSEST HYDRANT.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-03-10 Cont ID  
Sent By mcarsill Date 2005-03-10 Time 16:49 Rev Time 0.00
Received By mcarsill Date 2005-03-10 Time 16:49 Sent To  
Notes
2005-03-10 00:00:001. WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING, AND AFTER
 CONSTRUCTION.
  
 2. SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION.
  
 3. ELECTRONIC SWITCHES, CHAIN AND LOCKS
 WILL BE REQUIRED ON THE BACKFLOW
 DEVICE.
  
 4. CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 5. SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM AND FIRE
 SPRINKLER SYSTEM.
  
 6. KNOX-BOXES WILL BE REQUIRED FOR
 THE SITE.
  
 7. BUILDING ADDRESS REQUIRED ON THE
 BUILDING. 6" HIGH LETTERS REQUIRED.
  
 8. PLEASE PROVIDE DETAILS ON SECURITY
 DOOR LOCKS ON PAGE E-501.
  
 9. SOME DIRECTIONAL ARROWS ON AT LEAST
 TWO EXIT SIGNS ARE DIRECTING PERSONS
 INTO THE WAREHOUSE AREA.
  
 10. WHAT HAPPENS WHEN LOSS OF POWER
 OCCURS TO THE ELECTRONIC GATES. WHAT
 PROVISIONS HAVE BEEN MADE FOR FIRE
 AND PARAMEDICAL EQUIPMENT WHEN LOSS
 OF POWER OCCURS. MANUAL OPERATION
 WILL BE REQUIRED IF THE GATES
 REMAIN FAIL SECURE WHEN LOSS OF
 POWER OCCURS.
  
 11. MORE DETAILS NEEDED FOR STORAGE
 RACKS.
  
 12. PLEASE INDICATE OCCUPANT LOADS
 FOR THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-05-16 Cont ID  
Sent By adarroug Date 2006-05-16 Time 13:15 Rev Time 0.00
Received By adarroug Date 2006-05-16 Time 13:15 Sent To M
Notes
2006-05-16 00:00:00TO "HMOSER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-04-27 Cont ID  
Sent By adarroug Date 2006-04-27 Time 15:17 Rev Time 0.00
Received By adarroug Date 2006-04-27 Time 15:17 Sent To B
Notes
2006-04-27 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-04-27 Cont ID  
Sent By adarroug Date 2006-04-27 Time 12:13 Rev Time 0.00
Received By adarroug Date 2006-04-27 Time 12:13 Sent To E
Notes
2006-04-27 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-04-14 Cont ID  
Sent By adarroug Date 2006-04-14 Time 11:28 Rev Time 0.00
Received By adarroug Date 2006-04-14 Time 11:28 Sent To B
Notes
2006-04-14 00:00:00TO "SHILL" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-22 Cont ID  
Sent By dpalmer Date 2006-03-22 Time 16:18 Rev Time 0.00
Received By dpalmer Date 2006-03-22 Time 16:17 Sent To B
Notes
2006-03-22 00:00:00PLANS, TO SH'S DESK FOR RE-STAMP

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-02-06 Cont ID  
Sent By adarroug Date 2006-02-06 Time 14:32 Rev Time 0.00
Received By adarroug Date 2006-02-06 Time 14:32 Sent To B
Notes
2006-02-06 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-12-19 Cont ID  
Sent By adarroug Date 2005-12-19 Time 09:27 Rev Time 0.00
Received By adarroug Date 2005-12-19 Time 09:27 Sent To B
Notes
2005-12-19 00:00:00TO "SHILL" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-14 Cont ID  
Sent By adarroug Date 2005-10-14 Time 15:39 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 15:39 Sent To  
Notes
2005-11-14 00:00:00TO "COMM" BD#7
2005-10-14 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-30 Cont ID  
Sent By adarroug Date 2005-06-30 Time 16:54 Rev Time 0.00
Received By adarroug Date 2005-06-30 Time 16:54 Sent To  
Notes
2005-06-30 00:00:00TO "COMM" BD#64/PLANS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-06 Cont ID  
Sent By adarroug Date 2005-04-06 Time 10:45 Rev Time 0.00
Received By adarroug Date 2005-04-06 Time 10:45 Sent To  
Notes
2005-04-06 00:00:00TO "COMM" BD#37/PLANS ON "COMM" RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-03-11 Time 14:46 Rev Time 0.00
Received By adarroug Date 2005-01-31 Time 14:07 Sent To  
Notes
2005-01-31 00:00:00TO "COMM BD#40"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-05-25 Cont ID  
Sent By hmoser Date 2006-05-25 Time 09:46 Rev Time 0.00
Received By hmoser Date 2006-05-25 Time 09:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-07-25 Cont ID  
Sent By pkrauss Date 2005-07-22 Time 16:35 Rev Time 1.00
Received By pkrauss Date 2005-07-22 Time 16:35 Sent To  
Notes
2005-07-22 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 REQUIRED PER 2001 FBC(M)606.2.2.
  
 NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM - 2001
 FBC(M)602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-03 Cont ID  
Sent By pkrauss Date 2005-06-03 Time 15:00 Rev Time 1.00
Received By pkrauss Date 2005-06-03 Time 10:26 Sent To  
Notes
2005-06-06 00:00:00PROVISO:
 WAREHOUSE - PLEASE NOTE, FAN SHUTDOWN BY
 DUCT SMOKE DETECTORS REQUIRED IN SYSTEMS
 THAT SHARE A COMMON RETURN AIR PLENUMS
 WITH THE DESIGN CAPACITY GREATER THAN
 2,000 CFM. 2001 FBC,M 606.2.2.
  
 SEE COMMENTS #2 7 3 FROM SAMANTHA HILL,
 BUILDING PLAN REVIEW.
 #2 - 3 SETS OF PLANS REQUIRED.
 #3 - SIGNATURE ON THE ENERGY CALCS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-03-08 Cont ID  
Sent By pkrauss Date 2005-03-08 Time 16:53 Rev Time 1.45
Received By pkrauss Date 2005-03-08 Time 16:26 Sent To  
Notes
2005-03-08 00:00:00DENIED:
 1.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM PER
 2001 FBC/M 602.2.1.
  
 2.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) TABLE
 403.3.INDICATE ALL AREAS, SERVICE
 GARAGE, OFFICE, ETC.
  
 3.PLAN SHEET M-001 SPECIFICATION 15001
 E.INDICATES HEIGHT REQUIREMENT FOR
 STANDS.PLEASE NOTE THE REQUIREMENT
 DOES NOT INDICATE THAT THE HEIGHT
 REQUIREMENT IS FROM THE ROOF SURFACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-07-21 Cont ID  
Sent By kstevens Date 2005-07-21 Time 12:16 Rev Time 1.00
Received By kstevens Date 2005-07-21 Time 12:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-06-08 Cont ID  
Sent By kstevens Date 2005-06-08 Time 14:35 Rev Time 2.68
Received By kstevens Date 2005-06-08 Time 14:35 Sent To  
Notes
2005-06-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 CITY WPB CODE
  
 A. COMMENTS FROM PREVIOUS REVIEW:
 1. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERCVICE. SECTION 608.13.2 -
 ACTUALLY I SHOULD HAVE BEEN MORE CLEAR.
 RPZ BACKFLOWS ARE REQUIRED ON THE WATER
 SERVICE TO EACH BUILDING.
 2. SEPARATE PERMIT/PLANS REQUIRED FOR
 THE IRRIGATION. SECTION 104.3.1.1. -
 RESPONSE NOTED, BUT NO IRRIGATION PLANS
 WERE FOUND, AND THE INDEX OF SHEETS DOES
 NOT INDICATE AN IRRIGATION SHEET. PLEASE
 CLARIFY.
 3. SHT A-503 INDICATE WIDTH (30"), CLEAR
 FLOOR SPACE 11-4.24.5, (FORWARD APPROACH
 REQUIRED), EXPOSED PIPES AND SURFACES
 11-4.24.6, & FAUCETS 11-4.24.7. RESPONSE
 NOTED, BUT THESE REQUIREMENTS WERE NOT
 SHOWN.
 6. CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR THE SIZING OF THE OIL
 WATER SEPARATOR. WASTE ORD #2938-96.
 RESPONSE NOTED, BUT NO DETERMINATION
 WORKSHEET FROM MR. COMPO HAS BEEN
 SUBMITTED.
 8. SHT P102 INDICATE THE TYPE OF
 MATERIAL USED IN THE COMPRESSED AIR
 SYSTEM. SECTION 104.2.1. - RESPONSE
 NOTED, BUT SHEET P-001 WAS NOT SUBMITTED
 WHEN THE PERMIT WAS APPLIED FOR AND THE
 INFORMATION REQUIRESTED IS NOT SHOWN ON
 THE P-001 SHEET SUBMITTED THIS TIME.
 9. SHT P-601 SANT. RISER DIAGRAMM
 FIXTURE F6B (ICE MAKER) SHALL DRAIN TO
 AN INDIRECT WASTE RECEPTOR. SECTION 802.
 - RESPONSE NOTED, BUT THE WATER RISER
 DIAGRAM STILL INDICATES THAT THE FIXTURE
 IS AN ICE MAKER. PLEASE CORRELATE PLANS.
 - ALSO SHT P-601 HAS BEEN DELETED.
 ****************NEW COMMENT*************
 1B. ON PERMIT APPLICATION WHERE IT
 STATES "DESCRIBE PROJECT IN DETAIL" IT
 INDICATES A ONE STORY WAREHOUSE WITH AN
 ATTACHED 1 STORY OFFICE". WILL THE
 SERVICE GARAGE BE ON A SEPARATE PERMIT?
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-03-02 Cont ID  
Sent By kstevens Date 2005-03-02 Time 18:17 Rev Time 4.25
Received By kstevens Date 2005-03-02 Time 18:17 Sent To  
Notes
2005-03-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 CITY WPB CODE
  
 1) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2.
 2) SEPARATE PERMIT/PLANS REQUIRED FOR
 THE IRRIGATION. SECTION 104.3.1.1.
 3) SHT A-503 INDICATE WIDTH (30") AND
 KNEE CLEARANCE (27") ON DETAIL. SECTION
 11-4.24.3. CLEAR FLOOR SPACE 11-4.24.5
 (FORWARD APPROACH REQUIRED), EXPOSED
 PIPES AND SURFACES 11-4.24.6, & FAUCETS
 11-4.24.7.
 4) SHT A402 SUBMIT A DETAIL FOR MEN'S
 AND WOMEN'S TOILET ROOMS SHOWING
 COMPLIANCE WITH THE FOLLOWING.
 A) CLEAR FLOOR SPACE 11-4.16.2
 B) HEIGHT 11-4.16.3
 C) GRAB BARS 11-4.16.4
 D) HEIGHT 11-4.18.2
 E) CLEAR FLOOR SPACE 11-4.18.3
 F) FLUSH CONTROLS 11-4.18.4
 G) CLEAR FLOOR SPACE 11-4.19.3
 H) FAUCETS 11-4.19.7
 I) 5 FT. TURNING AREA IN TOILET ROOMS
 11-4.22.3.
 5) SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH:
 A) SPOUT HEIGHT 11-4.15.2
 B) CLEAR FLOOR SPACE 11-4.15.5
 6) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR THE SIZING OF THE
 OIL/WATER SEPARATOR. WASTE ORD #2938-96.
 (561) 837-4074 - E-MAIL [email protected].
 7) SHT P-101 WATER HEATER DETAIL,
 DIELECTRIC UNIONS ARE NOT APPROVED.
 DELETE FROM DETAIL OR CHANGE TO
 DIELECTRIC COUPLINGS.
 8) SHT P-102 INDICATE THE TYPE OF
 MATERIAL USED IN THE COMPRESSED AIR
 SYSTEM. SECTION 104.2.1.
 9) SHT P601 SANT. RISER DIAGRAM, FIXTURE
 F6B (ICE MAKER) SHALL DRAIN TO AN
 INDIRECT WASTE RECEPTOR. SECTION 802.
 10) SHT P-601 SERVICE GARAGE SANT. RISER
 DIAGRAM, HORIZONTAL DRY VENT DOWSTREAM
 FROM FIXTURE F1A (W/C) NOT APPROVED.
 SECTIONS 905.3/905.4.
 11) SHT P-601 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTOR IS REQUIRED AT THE ICE
 MAKER PER SECTION 604.9. WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING. PDI-WH 201.
 12) SHT P-601 WATER RISER DIAGRAM, THE
 VALVES REQUIRED BY SECTION 606.1(4),
 WATER DOWN-FEED LINES, SHALL BE SHOWN ON
 THE ISOMETRIC. SECTION 104.2.1.
 13) SUBMIT A PLUMBING LEGEND INDICATING
 ALL FIXTURE, AND WATER HAMMER
 DESIGNATIONS. SECTION 104.2.1.
 13) SHT M-101 HVAC ROOF PLAN, CONDENSATE
 SHALL NOT DRAIN INTO THE SANT. SYSTEM.
 CONDENSATE SHALL DRAIN SEPARATELY INTO A
 CATCH BASIN, DRYWELL, OR STORM DRAIN
 LINE IF DRAINING TO STORM SEWER. CITY
 CODE SECTION 90-125(5)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-01 Cont ID  
Sent By mmclean Date 2005-03-01 Time 09:20 Rev Time 0.00
Received By mmclean Date 2005-03-01 Time 09:20 Sent To  
Notes
2005-03-01 00:00:00JOSH LONG, SENIOR PLANNER 822-1449
 APPROVED.


Account Summary | Usage Policy | Privacy Policy