Plan Review Details - Permit 05011534
Plan Review Stops For Permit 05011534
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-12 Cont ID  
Sent By lsmith Date 2005-04-12 Time 08:43 Rev Time 0.50
Received By lsmith Date 2005-04-12 Time 08:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-08 Cont ID  
Sent By lsmith Date 2005-03-08 Time 11:40 Rev Time 0.50
Received By lsmith Date 2005-03-08 Time 11:40 Sent To  
Notes
2005-03-08 00:00:00BUILDING PLAN REVIEW: FAILED
  
 SEE NOTE #1 FIRST REVIEW: NEED METHOD OF
 PROTECTING THE OPENINGS FROM THE HOUSE
 TO THE POOL PER FBC424.
  
  
 ANY QUESTIONS PLEASE CALL"
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-15 Cont ID  
Sent By lsmith Date 2005-02-15 Time 10:04 Rev Time 1.00
Received By lsmith Date 2005-02-15 Time 10:04 Sent To  
Notes
2005-02-15 00:00:00BUILDING PLAN REVIEW FAILED
  
 1. SUBMIT ON THE PLANS THE METHOD OF
 PROTECTING THE OPENINGS FROM THE HOUSE
 TO THE POOL AS PER FBC 424. (ALARMS ON
 DOORS & WINOWS, BABY BARRIER, POOL
 COVER, ETC)
  
 2. THE VALUE OF THE POOL HAS BEEN
 CALCULATED PER MARSHALL SWIFT COST
 GUIDELINES. ADDITIONAL FEES OF 238.26
 ARE DUE BEFORE A PERMIT CAN BE ISSUED.
  
 3. SUBMIT A RECORED NOTICE OF
 COMMENCEMENT BEFORE A PERMIT IS ISSUED.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-12 Cont ID  
Sent By btrobaug Date 2005-04-12 Time 08:18 Rev Time 0.50
Received By btrobaug Date 2005-04-12 Time 08:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-02 Cont ID  
Sent By btrobaug Date 2005-03-02 Time 14:42 Rev Time 0.33
Received By btrobaug Date 2005-03-02 Time 14:33 Sent To Z
Notes
2005-03-02 00:00:001} INDICATE THE SIZE OF THE EXISTING
 SERVICE ON THE LOAD CALC. THE PERSON
 RESPONSIBLE FOR THE CALC MUST PRINT NAME
 AND SIGN SAME PER 104.2.1 FBC.
  
 2} PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND
 CONDUIT SIZE AND TYPE, PANEL RATING AND
 OCP,PANEL SCHEDULE AND COMPUTED LOAD,
 ETC.
  
 ALSO NOTE THAT AN ELECTRICAL CONTRACOR
 IS REQUIRED FOR THE SCOPE OF THIS WORK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-07 Cont ID  
Sent By btrobaug Date 2005-02-07 Time 10:29 Rev Time 0.33
Received By btrobaug Date 2005-02-07 Time 09:55 Sent To P
Notes
2005-02-07 00:00:00 
  
 THE TYPE OF POOL HEATER HAS BEEN CHANGED
 FROM GAS TO ELECTRIC, THIS REQUIRES A
 LOAD CALCULATION FROM THE ENGINEER. ALSO
 SPECIFICATIONS FOR THE EQUIPMENT BEING
 INSTALLED MUST BE SUBMITTED FOR REVIEW.
  
 THE SCHEMATIC INDICATES A GAS HEATER,
 PLEASE CHANGE DRAWING TO CORRELATE WITH
 THE SCOPE OF WORK.
  
 THE ENGINEER OBVIOUSLY WAS NOT AWARE OF
 THESE CHANGES. PLEASE SEND THE PLAN BACK
 TO MR. RICE FOR HIS APPROVAL. NOTE
 CHANGES TO SEALED PLANS CAN ONLY BE MADE
 BY THE ENGINEER OF RECORD PER 471.025
 FS.
  
 AN ELECTRICAL PERMIT IS REQUIRED FOR
 THIS WORK.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-04-08 Cont ID  
Sent By adarroug Date 2005-04-08 Time 16:05 Rev Time 0.00
Received By adarroug Date 2005-04-08 Time 16:05 Sent To E
Notes
2005-04-08 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-03 Cont ID  
Sent By adarroug Date 2005-03-03 Time 10:07 Rev Time 0.00
Received By adarroug Date 2005-03-03 Time 10:07 Sent To P
Notes
2005-03-03 00:00:00TO KSTEVENS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 09:04 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 09:04 Sent To E
Notes
2005-02-28 00:00:00TO "BT" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-04 Cont ID  
Sent By adarroug Date 2005-02-04 Time 09:10 Rev Time 0.00
Received By adarroug Date 2005-02-04 Time 09:09 Sent To Z
Notes
2005-02-04 00:00:00TO "Z"BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 14:18 Rev Time 0.00
Received By mjacobs Date 2005-01-31 Time 14:17 Sent To Z
Notes
2005-01-31 00:00:00TO "Z" BOX.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-03-07 Cont ID  
Sent By gsalfeld Date 2005-03-07 Time 15:49 Rev Time 0.50
Received By gsalfeld Date 2005-03-07 Time 15:49 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-02-12 Cont ID  
Sent By pschmitz Date 2005-02-12 Time 07:17 Rev Time 0.00
Received By pschmitz Date 2005-02-12 Time 07:16 Sent To B1
Notes
2005-02-12 00:00:00PLUMBING PLAN REVIEW FBC 2001,DENIED
 THE POOL HEATER HAS BEEN CHANGED FROM
 GAS TO ELECTRIC HEAT PUMP.
 DELETE ALL REFERENCE TO GAS HEATER.
 PROVIDE MANFACTUREES SPECIFICATIONS FOR
 HEAT PUMP.
 ALL CHANGES TO BE INITALED BY ENGINEER
 OF RECORD.
 END OF COMMENTS561-805-6692

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-02 Cont ID  
Sent By mmclean Date 2005-02-03 Time 15:57 Rev Time 0.00
Received By mmclean Date 2005-02-03 Time 15:57 Sent To I
Notes
***NONE***