Plan Review Details - Permit 05011505
Plan Review Stops For Permit 05011505
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-01-25 Cont ID  
Sent By jgomez Date 2006-01-25 Time 17:42 Rev Time 0.33
Received By jgomez Date 2006-01-25 Time 17:42 Sent To PC
Notes
2006-01-25 00:00:00INTERIOR BEARING WALL REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-12-30 Cont ID  
Sent By jgomez Date 2005-12-30 Time 16:13 Rev Time 75.00
Received By jgomez Date 2005-12-30 Time 16:13 Sent To PC
Notes
2005-12-30 00:00:00BUILDING REVISION SIGNED AND SEALED ON
 12-14-05.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-08-17 Cont ID  
Sent By jgomez Date 2005-08-17 Time 17:53 Rev Time 0.50
Received By jgomez Date 2005-08-17 Time 17:53 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-07-22 Cont ID  
Sent By pkrauss Date 2005-07-20 Time 10:27 Rev Time 0.00
Received By rmcdouga Date 2005-07-22 Time 12:14 Sent To  
Notes
2005-07-01 00:00:00DENIED
  
 1) PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR SIMPSON HETAL 20 AND LUS
 210 CONNECTORS.
  
 2) THE TWO HETAL-20 CONNECTORS HAVE A
 UPLIFT CAPACITY OF 2500#. THE UPLIFT
 LISTED IN THE SCHEDULE ON A7, FOR GRF IS
 4596# AND GRA IS 2782# WHICH EXCEED THE
 CAPACITY OF THE CONNECTORS. PLEASE
 CORRECT.
  
 3) GIRDER TRUSSES GRE AND GRC SPECIFIED
 ON THE SECOND FLOOR FRAMING PLAN ARE NOT
 LISTED IN THE SCHEDULE ON A7.
  
 4) FBC 1707.4.4.2 REQUIRES WINDOW AND
 AND DOOR ASSEMBLIES TO BE FASTENED
 THROUGH 1X BUCKS INTO THE STRUCTURAL
 SUBSTRATE. THE NOTES ON THE BUCK DETAILS
 ON A11 SPECIFY ATTACHMENT TO THE 1X
 BUCKS. PLEASE CORRECT.
  
 5) PROVIDE DETAILS FOR THE BALCONY AND
 STAIR GUARDRAILS SHOWING COMPLIANCE WITH
 FBC 1015 AND 1608.2.
  
 6) THE TYPICAL STAIR DETAIL ON SHEET A10
 DOESN'T MATCH STAIRS SHOWN ON PLANS. THE
 UPPER STAIR IS MISSING ONE STEP. THE
 NUMBER OF RISERS AND TREADS IS NOT
 CONSISTENT. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-03 Cont ID  
Sent By jgomez Date 2005-06-03 Time 10:06 Rev Time 2.50
Received By jgomez Date 2005-06-03 Time 10:06 Sent To PC
Notes
2005-06-03 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- PROVIDE STRUCTURAL BUCK DETAILS FOR
 SWING DOOR AT GARAGE. SEE PRODUCT
 APPROVAL FOR SIZE REQUIRED.
 **NOTE: IT'S THE DESIGNER OF RECORD THE
 ONE WHO PROVIDES THIS INFORMATION NOT
 THE PRODUCT APPROVAL. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001 AND SECTION
 1707.4.4.2 FBC 2001.
  
 2- SECTION 1/A6 IS INCOMPLETE. IS
 MISSING 2ND FLOOR FRAMING ON THE OTHER
 SIDE OF THE WALL. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 3- A) PROVIDE UPLIFT CALCULATIONS FOR
 ROOF TRUSSES TO CLARIFYWHY UPLIFT
 CALCULATIONS SHOWN ON PLANS ARE THE SAME
 FOR THE FIRST STORY ROOF AS THE ONES FOR
 THE SECOND STORY ROOF. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 B) CLARIFY WHY USING CONNECTORS ON
 SECOND FLOOR ROOF THAT DON'T PROVIDE
 RESISTANCE FOR LATERAL LOADS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 C) CLARIFY WHY USING STRONGER CONNECTORS
 FOR ROOF AT FIRST FLOOR THAN AT SECOND
 FLOOR ROOF. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 4- SHEET A6: UNABLE TO FIND SIMPSON
 LUSC212 AND LUS212 CONNECTORS IN THE
 SIMPSON CATALOGUE. WHERE WERE THEY TAKEN
 FROM? PROVIDE COMPLETE CONNECTOR
 INFORMATION AND PRODUCT APPROVAL. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 5- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR: A) USP CONNECTORS
 SPECIFIED ON PLANS.
  
 B) GARAGE DOORS. DRAWINGS SUBMITTED ARE
 NOT LEGIBLE.
  
 6-A) ON FIRST SUBMITTAL PACKAGE THERE
 WAS A PRODUCT APPROVAL FOR RAILING
 SYSTEM TO BE USED IN THE HOUSE. IT WAS
 NOT GOOD BECAUSE IT WAS TO BE ANCHORED
 TO CONCRETE SLAB. NOW, THERE IS NO
 SUBMITTAL FOR RAILINGS NOW.
 PROVIDE COMPLETE SPECS AND DETAILS FOR
 CONSTRUCTION OF RAILING SYSTEMS. SPECIFY
 ALL CONNECTORS, ETC. DESIGN TO COMPLY
 WITH SEC. 1608.2 FBC 2001.
  
 B) TYPICAL STAIR DETAIL ON SHEET A10
 DOESN'T MATCH STAIRS SHOWN ON PLANS.
 LOOK AT FIRST AND LAST STEP. ALSO, NEED
 TO SPECIFY ALL FRAMING CONNECTORS FOR
 POSTS ETC.
 AND, REVISE CONNECTOR TO BE ATTACHED TO
 MASONRY. NEED TO SPECIFY MASONRY
 CONNECTOR. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 7- SECTIONS SHOWN ON SHEET A11 DON'T
 APPLY TO THIS PROJECT. PROVIDE SECTIONS
 THAT APPLY. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-18 Cont ID  
Sent By jgomez Date 2005-02-18 Time 16:47 Rev Time 3.00
Received By jgomez Date 2005-02-18 Time 16:47 Sent To  
Notes
2005-02-18 00:00:00BUILDING REVIEW CHECKLIST:
 1- WHEN APPLYING FOR BUILDING PERMIT,
 PLEASE PAY IMPACT FEES AND BRING BACK
 STAMPED DRAWINGS AND PAID RECEIPT.
 ALSO, PROVIDE COPY OF RECORDED NOTICE OF
 COMMENCEMENT.
  
 2- CLARIFY IF USING IMPACT GLAZING OR
 STORM SHUTTERS. BOTH PACKAGES WERE
 SUBMITTED. IF USING STORM SHUTTERS,
 THEN, PROVIDE COMPLETE INFORMATION.
  
 3- REVISE HANDRAIL HEIGHT SHOWN ON STAIR
 DETAIL. SHEET A10. HANDRAIL NEED TO BE
 BETWEEN 34" AND 38" (NOT 42"). SECTION
 1007.5.1 FBC 2001 EXCEPTION #3.
 **NOTE: GUARDRAIL AND HANDRAIL ARE NOT
 THE SAME.
  
 4-SPECIFY ROOF TILE FASTENING AS REQ'D
 BY SEC. 104.2.1.1 CITY AMENDMENTS TO FBC
  
 5- GARAGE DOOR SIZE SPECIFIED ON DOOR
 SCHEDULE IS NOT THE SAME AS SHOWN ON
 ELEVATIONS. REVISE AS REQUIRED.
  
 6- PROVIDE SURVEY WITH LAYOUT THAT
 MATCHES PLANS SUBMITTED.
  
 7- OWNER/AGENT NEEDS TO SIGN AND DATE
 THE ENERGY CALCULATIONS FORM.
  
 8- PROVIDE SOIL TEST REPORT.
  
 9- PROVIDE STRUCTURAL BUCK DETAILS FOR
 SWING AND SLIDING GLASS DOORS. (SEE
 PRODUCT APPROVAL FOR SIZE OF BUCK REQ'D)
 SECTION 104.2.1.2 SECTION 104.2.1.2 OF
 CITY AMENDMENTS TO FBC 2001 AND SECTION
 1707.4.4.2 FBC 2001.
  
 10- SPECIFY DRAFSTOPPING MATERIALS AND
 LOCATION ON 2ND FLOOR FRAMING PLAN AS
 REQUIRED BY SEC. 2305.2.2(1) FBC 2001.
  
 11- PLEASE, PROVIDE ONLY THE DETAILS
 THAT APPLY TO THIS PROJECT TO EXPEDITE
 AND CLARIFY REVIEW PROCESS.
  
 12- PROVIDE COMPLETE WALL SECTION/DETAIL
 AT EAST WALL SHOWING HOW ARE ROOF
 TRUSSES STRUCTURALLY SUPPORTED ON
 LEDGER. SPECIFY ALL FASTENERS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 13- PROVIDE UPLIFT CALCULATIONS FOR ROOF
 TRUSSES(INCLUDING LATERAL FORCES) AND
 EXPLAIN WHY USING CONNECTORS ON 2ND
 FLOOR ROOF TRUSSESTHAT DON'T
 PROVIDE RESISTANCE TO LATERAL FORCES.
 (*NOTE: IT'S THE DESIGNER OF RECORD
 RESPONSIBILITY TO CALCULATE THE LOADS
 NOT THE TRUSS ENGINEER*. REVISE NOTES ON
 SHEETS A6 AND A7).
  
 14- PROVIDE SMOKE DETECTOR IN FIRST FL.
 CLOSE TO THE STAIRS AS REQ'D BY SECTION
 905.2.2 FBC 2001.
  
 15- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR: A) DOUBLE ENTRY DOORS AS
 SHOWN ON PLANS.
 B) 8'-0" HIGH SWING DOORS AS SHOWN ON
 PLANS (NOT 7'-0"HIGH AS SUBMITTED)
 C) RAILING SYSTEM TO BE INSTALLED IN
 FRAMED FLOORS, NOT CONCRETE SLAB.
 PROVIDE COMPLETE DETAILS FOR WOOD FRAMED
  
 FLOORS AS SHOWN ON PLANS.
 D) GARAGE DOOR INCLUDING DRAWINGS OF
 MODEL TO BE INSTALLED.
 E) FIXED WINDOWS.
  
 16- SHEET A1: A) REVISE DETAIL F1. NEED
 FOOTING TO BE 12 MIN. BELOW GRADE (NOT
 8"). SEC. 1804.1.3 FBC 2001.
 B) SPECIFY REQUIRED DEPTH BELOW GRADE
 ON DETAIL F3. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 17- SHEET A6: BUCKETS SPECIFIED FOR
 BALCONY CONSTRUCTION ARE WOOD TO WOOD
 JOIST HANGERS. NEED BUCKET WITH
 SPECIFICATIONS TO BE INSTALLED ON
 CONCRETE BLOCK WALL. (ALSO, WHERE ARE
 LUSC 212-3 CONNECTORS ON SIMPSON
 CATALOGUE?)
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 18- SHEET A7: SPECIFY CONNECTORS FOR
 HAND FRAMED HIPS AND VALLEY RAFTERS.
 SECTION 104.2.1.2 CITY AMENDMENTS TO FBC
  
 19- DETAILS/SECTIONS ON SHEET A11 DON'T
 APPLY TO THIS PROJECT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-05-08 Cont ID  
Sent By btrobaug Date 2006-05-08 Time 07:44 Rev Time 0.75
Received By btrobaug Date 2006-05-08 Time 06:41 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-12-19 Cont ID  
Sent By btrobaug Date 2005-12-19 Time 11:06 Rev Time 0.50
Received By btrobaug Date 2005-12-19 Time 07:34 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-08-03 Cont ID  
Sent By btrobaug Date 2005-08-03 Time 17:57 Rev Time 0.33
Received By btrobaug Date 2005-08-03 Time 17:24 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-22 Cont ID  
Sent By btrobaug Date 2005-07-22 Time 12:21 Rev Time 0.33
Received By btrobaug Date 2005-07-22 Time 12:16 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-05-11 Cont ID  
Sent By btrobaug Date 2005-05-11 Time 13:19 Rev Time 0.50
Received By btrobaug Date 2005-05-11 Time 13:13 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-08 Cont ID  
Sent By btrobaug Date 2005-02-08 Time 15:00 Rev Time 0.50
Received By btrobaug Date 2005-02-07 Time 15:28 Sent To M
Notes
2005-02-08 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PANEL "B" IS SHOWN AS MLO IN THE
 NOTES, HAS NO OCP IN METER MAIN, AND NO
 APPEARANT DISCONNECTING MEANS PER
 225.32.
  
 2} THERE ARE 75 RECESSED LIGHTS IN THE
 LOAD CALCS, BUT ONLY 24 ON PLANS. PLEASE
 CORRELATE.
  
 3} ELECTRIC WATER HEATER IS SHOWN ON THE
 PLAN, DOES NOT APPEAR ON THE PANEL
 SCHEDULE. ALSO CALCULATE PER 442.13.
  
 4} A SMOKE DETECTOR IS REQUIRED PER
 8-1.4.1.6.2 NFPA-72, OUTSIDE SLEEPING
 AREA, "IMMEDIATE VICINITY".
  
 5} ISLAND RECEPTACLES REQUIRED TO BE GFI
 PER 210.8(A)(6).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-05-06 Cont ID  
Sent By adarroug Date 2006-05-06 Time 15:09 Rev Time 0.00
Received By adarroug Date 2006-05-06 Time 15:09 Sent To E
Notes
2006-05-06 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 11:18 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 11:18 Sent To B
Notes
2006-01-22 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 16:23 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 16:23 Sent To E
Notes
2005-12-16 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-12-13 Cont ID  
Sent By adarroug Date 2005-12-13 Time 10:43 Rev Time 0.00
Received By adarroug Date 2005-12-13 Time 10:43 Sent To M
Notes
2005-12-13 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-03 Cont ID  
Sent By adarroug Date 2005-08-03 Time 12:57 Rev Time 0.00
Received By adarroug Date 2005-08-03 Time 12:57 Sent To E
Notes
2005-08-03 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-08 Cont ID  
Sent By adarroug Date 2005-07-08 Time 16:17 Rev Time 0.00
Received By adarroug Date 2005-07-08 Time 16:17 Sent To M
Notes
2005-07-08 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-24 Cont ID  
Sent By adarroug Date 2005-06-24 Time 13:30 Rev Time 0.00
Received By adarroug Date 2005-06-24 Time 13:30 Sent To M
Notes
2005-06-24 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-10 Cont ID  
Sent By adarroug Date 2005-05-10 Time 10:01 Rev Time 0.00
Received By adarroug Date 2005-05-10 Time 10:01 Sent To E
Notes
2005-05-10 00:00:00TO "BTROBAUG" DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-04 Cont ID  
Sent By adarroug Date 2005-02-04 Time 15:56 Rev Time 0.00
Received By adarroug Date 2005-02-04 Time 15:56 Sent To E
Notes
2005-02-04 00:00:00TO "E"/ SF RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 09:12 Rev Time 0.00
Received By mjacobs Date 2005-01-31 Time 13:06 Sent To Z
Notes
2005-01-31 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 8 Status N Date 2005-12-20 Cont ID  
Sent By tgordon Date 2005-12-20 Time 08:42 Rev Time 0.20
Received By tgordon Date 2005-12-20 Time 08:42 Sent To B
Notes
2005-12-20 00:00:00MECH. CONTRACTOR SUBMITTED APPROVED
 MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2005-12-14 Cont ID  
Sent By tgordon Date 2005-12-14 Time 11:32 Rev Time 0.30
Received By tgordon Date 2005-12-14 Time 11:32 Sent To  
Notes
2005-12-14 00:00:00MECH. PLANS SUBMITTED BY MECH.
 CONTRACTOR 12-14-05.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2005-12-13 Cont ID  
Sent By tgordon Date 2005-12-13 Time 15:55 Rev Time 0.30
Received By tgordon Date 2005-12-13 Time 15:55 Sent To  
Notes
2005-12-13 00:00:00*** DEINED ***
 1) FROM REVIEW ON 7-20-05 MECHANICAL
 CONTRACTOR NEEDS TO APPLY FOR MECHANICAL
 PERMIT, OR HAVE YOUR ENGINEER (LUIS A.
 LOPEZ) MAKE REVISIONS AND SEAL PLANS.
 SEE ATTACH REVIEW FROM 7-20-05.
 2) NEED TO SUBMIT 2 SETS OF PLANS.
 3) NEED JOB LOCATION ON PLANS.
 4) PLEASE SHOW DRAIN LINES ON PLANS.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2005-07-20 Cont ID  
Sent By pkrauss Date 2005-07-20 Time 10:24 Rev Time 0.30
Received By pkrauss Date 2005-07-20 Time 10:24 Sent To B
Notes
2005-07-20 00:00:00PER CONVERSATION WITH GENERAL
 CONTRACTOR.MECHANICAL CONTRACTOR TO
 SUBMIT PLANS WITH MECHANICAL PERMIT
 APPLICATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2005-07-19 Cont ID  
Sent By rregueir Date 2005-07-19 Time 16:50 Rev Time 0.00
Received By rregueir Date 2005-07-19 Time 16:50 Sent To B
Notes
2005-07-19 00:00:00DENIED:4TH REQUEST
 ----------------------------------------
 1) SPARE BEDROOMS ON 1ST AND 2ND
 FLOORS (PAGES M1 & M2) SHOW 7" ROUND
 FLEX DUCTS SERVING CLOSETS TO DELIVER 15
 CFM EACH.DUCT IS TOO LARGE FOR THIS
 APPLICATION.THIS DUCT SIZE WILL ALSO
 CAUSE R/A TRANSFER DUCTS TO BE
 UNDERSIZED PER FBC,M 601.4.
  
 2) R/A TRANSFER DUCT IN OFFICE (PAGE M2)
 TO BE MINIMUM 12" ROUND PER FBC,M 601.4.
  
 PLEASE REVISE AND RESUBMIT.
  
 RONALD J REGUEIRO
 561-805-6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-06-28 Cont ID  
Sent By pkrauss Date 2005-06-28 Time 11:14 Rev Time 0.35
Received By pkrauss Date 2005-06-28 Time 09:22 Sent To  
Notes
2005-06-28 00:00:00DENIED: 3RD REQUEST
  
 1.PROVIDE DETAIL FOR THE DUCT
 CONNECTION TO AHU LOCATED ON THE FIRST
 FLOOR.PLAN SHEET A2 & M1 INDICATE A
 24" X 24" R/A GRILLE.PLEASE CLARIFY
 DESIGN, CLOSET CANNOT BE USED AS A
 RETURN AIR PLENUM WITH THE DOOR OPENINGS
 INTO THE GARAGE (CARBON MONOXIDE).2001
 FBC(M) 603.9 & 602.
  
 2.PLEASE NOTE RETURN AIR JUMPERS
 SHALL BE SIZED IN ACCORDANCE WITH 2001
 FBC(M)601.4 EXCEPTION #1 & 3.THE
 SECOND FLOOR SPARE BEDROOMS SHALL BE A
 MINIMUM OF 12" AND THE MASTER SUITE
 SHALL BE A MINIMUM OF 14".PLEASE
 REVISE.
  
 3.PLAN SHEET M2 INDICATES RETURN AIR
 BACK TO THE AHU THROUGH A LOUVERED DOOR.
 THE DOOR SCHEDULE ON PLAN SHEET A3, DOOR
 #5TO THE AHU-2 CLOSET INDICATES A
 SOLID CORE DOOR.PLEASE REVISE.
  
 4.PROVIDE AN EQUIPMENT SCHEUDLE AS
 DICTATED BY THE ENERGY CALCULATIONS.
  
 PLEASE NOTE, THE FLOOR PLAN IN THE
 GARAGE AREA ON PLAN SHEET E1 DOES NOT
 CORRELATE WITH A2 & M1 WITH RESPECT TO
 LOCATION OF THE AHU & 80 GAL EWH.
 PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-05-28 Cont ID  
Sent By hmoser Date 2005-05-28 Time 08:23 Rev Time 0.00
Received By hmoser Date 2005-05-28 Time 08:06 Sent To B
Notes
2005-05-28 00:00:00PLAN DENIED
 1) AIRHANDLER LOCATED IN GARAGE CAN NOT
 HAVE RETURN AIR IN UTIL.ROOM
 SECTION 610.1.ABC.3.7 CHAPTER 13 FEC
 2) UTIL.ROOM HAS SOLID WOOD DOOR.PLEASE
 SHOW HOW RETURN AIR GETS BACK TO
 AIRHANDLER ON PLAN (DOOR SCHEDULE PAGE
 A2 #4)
 3) PLEASE SHOW RETURN AIR DUCT SIZES IN
 BED ROOMS PER SECTION 604.1 FBC(M)
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-02-14 Cont ID  
Sent By pkrauss Date 2005-02-14 Time 08:41 Rev Time 0.40
Received By pkrauss Date 2005-02-14 Time 08:30 Sent To P
Notes
2005-02-14 00:00:00DENIED:PLAN CHECK ONLY
  
 PLEASE CLARIFY RETURN AIR INTO THE AHU
 LOCATEDIN THE GARAGE AREA.PROVIDE
 DETAIL OF THE DUCT CONNECTION.
  
 PLEASE NOTE, WATER HEATER LOCATED IN THE
 GARAGE SHALL BE PROTECTED FROM DAMAGE
 PER 2001 FBC(M)303.4.
  
 PLEASE INDICATE TERMINATION OF DRYER
 EXHAUST DUCT.SHOW COMPLIANCE WITH 2001
 FBC(M)504.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-12-20 Cont ID  
Sent By jleech Date 2005-12-20 Time 08:22 Rev Time 0.33
Received By jleech Date 2005-12-20 Time 08:22 Sent To M
Notes
2005-12-20 00:00:00REVISED RISER DIAGRAM

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-08-12 Cont ID  
Sent By jleech Date 2005-08-12 Time 12:42 Rev Time 0.50
Received By jleech Date 2005-08-12 Time 12:42 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-05-28 Cont ID  
Sent By kstevens Date 2005-05-28 Time 07:25 Rev Time 0.50
Received By kstevens Date 2005-05-28 Time 07:25 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-02-14 Cont ID  
Sent By kstevens Date 2005-02-14 Time 18:03 Rev Time 0.51
Received By kstevens Date 2005-02-14 Time 18:03 Sent To B1
Notes
2005-02-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT SP1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS.
 A) FIRST FLOOR BATHROOMS SHOW TUBS ON
 THE FLOOR PLAN, BUT SHOW SHOWERS ON THE
 SANT. RISER DIAGRAM. SECTION 104.2.1.
 B) ALL SHOWERS, TUBS, BIDET, & WASH
 MACHINE REQUIRE A TRAP. SECTION 901.2.1.
 C) STANDPIPE FOR THE WASH MACHINE SHALL
 BE UPSTREAM OF THE TRAP. PLEASE SHOW ON
 THE RISER DIAGRAM. SECTION 104.2.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2006-06-01 Cont ID  
Sent By mmclean Date 2006-06-01 Time 16:47 Rev Time 0.00
Received By mmclean Date 2006-06-01 Time 16:47 Sent To B
Notes
2006-06-01 00:00:00REVISION OF PROPOSED DRIVEWAY.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-22 Cont ID  
Sent By mmclean Date 2005-08-22 Time 16:18 Rev Time 0.00
Received By mmclean Date 2005-08-22 Time 16:18 Sent To  
Notes
2005-08-22 00:00:00APPROVING RE-STAMPING OF SURVEY MM

Review Stop Z ZONING
Rev No 1 Status P Date 2005-02-04 Cont ID  
Sent By mmclean Date 2005-02-04 Time 15:13 Rev Time 0.00
Received By mmclean Date 2005-02-04 Time 15:13 Sent To I
Notes
2005-02-04 00:00:00NOTE,
 1. MUST PULL SEPERATE PERMIT FOR
 POOL/DECK/SCREEN ENCLOSURE.
 2.POOL SETBACK MUST BE A MIN OF 5FT IN
 REAR & NOTHING CAN BE BUILT IN UTILITY
 EASEMENT.