Plan Review Details - Permit 05011482
Plan Review Stops For Permit 05011482
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-06-19 Cont ID  
Sent By shill Date 2006-06-19 Time 13:59 Rev Time 0.00
Received By shill Date 2006-06-19 Time 13:59 Sent To  
Notes
2006-06-19 00:00:00REVISED S1, A4 DATED 6/5/6

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-04-12 Cont ID  
Sent By shill Date 2006-04-12 Time 18:38 Rev Time 0.00
Received By shill Date 2006-04-12 Time 18:38 Sent To  
Notes
2006-04-12 00:00:00PROVISO - SEPARATE PERMIT DOORS,
 WINDOWS, ROOF

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-02-16 Cont ID  
Sent By shill Date 2006-02-16 Time 10:36 Rev Time 1.00
Received By shill Date 2006-02-16 Time 09:59 Sent To  
Notes
2006-02-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS LIST:
  
 1.)WHEN RESUBMITTING, PROVIDE TWO
 COLLATED SETS.REPLACE ONLY SHEETS
 WHICH HAVE CHANGED.
  
 PLEASE PREPARE TWO COLLATED STAPLED SETS
 FOR PERMIT ISSUANCE.YOUR SITE PLAN,
 MECHANICAL SHEET, ELECTRIC SHEET ARE IN
 ONE PACKAGE MARKED "OLD" AND THE
 ARCHITECTURAL AND STRUCTURAL SHEETS ARE
 IN ANOTHER INCOMPLETE SET.
  
 2.)ADDRESSED.
  
 3.)SEE PREVIOUS LISTS.FLORIDA STATE
 OR LOCAL PRODUCT APPROVAL REQUIRED IN
 ADDITION TO THE NOAS PROVIDED.ANY
 ITEMS NOT SUBMITTED PROPERLY PRIOR TO
 ISSUANCE WILL REQUIRE SEPARATE PERMITS.
  
 NOT ADDRESSED.FLORIDA STATE PRODUCT
 APPROVALS MAY BE AVAILABLE AT
 WWW.FLORIDABUILDING.ORG
  
 NEW COMMENT
  
 4.)THE NOC HAS EXPIRED (OVER 90 DAYS
 WITHOUT COMMENCING WORK), FS713.13(2).
 PLEASE REFILE THE NOC.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-12-12 Cont ID  
Sent By shill Date 2005-12-12 Time 11:05 Rev Time 0.00
Received By shill Date 2005-12-12 Time 09:55 Sent To  
Notes
2005-12-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)WHEN RESUBMITTING, PROVIDE TWO
 COLLATED SETS.REPLACE ONLY SHEETS
 WHICH HAVE CHANGED.
  
 2.)THE PACKAGE MARKED "CONTRACTOR
 COPY" IS MISSING FROM THE PACKAGE.THIS
 MUST STAY IN THE PACKAGE UNTIL ISSUANCE.
 PROVIDE A SECOND COPY OF THE REQUIRED
 DOCUMENTS.
  
 3.)SEE PREVIOUS LISTS.FLORIDA STATE
 OR LOCAL PRODUCT APPROVAL REQUIRED IN
 ADDITION TO THE NOAS PROVIDED.ANY
 ITEMS NOT SUBMITTED PROPERLY PRIOR TO
 ISSUANCE WILL REQUIRE SEPARATE PERMITS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-08-27 Cont ID  
Sent By shill Date 2005-08-27 Time 16:35 Rev Time 2.00
Received By shill Date 2005-08-27 Time 16:14 Sent To  
Notes
2005-08-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE NOC IS EXPIRED, OVER 90 DAYS
 WITHOUT COMMENCING WORK, FS713.13(2).
  
 2.)THE BEDROOM WINDOW NOW SHOWS A
 53X50 SINGLE OPENING CASEMENT.THIS IS
 A DOUBLE OPENING; SEE PRODUCT APPROVAL.
 PROVIDE INFORMATION FROM THE
 MANUFACTURER SHOWING COMPLIANCE WITH
 FBC1005.4.3.THIRD REQUEST.
  
 3.)SHEET A2 TYPICAL ROOF NAILING NOTE
 HAS BEEN REVISED TO 6" OC THROUGHOUT.
 THIS IS STILL NONCOMPLIANT FOR ZONE 3.
 THIRD CORRECTION.
  
 4.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE
 NOAS PROVIDED, FAC9B72L.
 WWW.FLORIDABUILDING.ORG.
  
 A 4X FEE HAS BEEN CHARGED AS REQUIRED BY
 FS553.80(2)(B).
  
 WHEN RESUBMITTING, PLEASE REPLACE SHEETS
 WHICH HAVE CHANGED AND SUBMIT OLD SHEETS
 SEPARATELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-05 Cont ID  
Sent By shill Date 2005-08-05 Time 13:44 Rev Time 2.00
Received By shill Date 2005-08-05 Time 11:16 Sent To PC
Notes
2005-08-05 00:00:00PERMIT #05011482
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.) PROVIDE A COPY OF A SURVEY FOR THIS
 PROPERTY.
  
 4.) SEE PREVIOUS LIST, ITEM #6.
 EMERGENCY EGRESS REQUIRED, FBC
 1005.4.SHOW WINDOW SIZE AND TYPE FOR
 OFFICE/GUEST BEDROOM.A NOTE WAS PLACED
 ON THE PLAN "NEW WINDOWS TO BE EGRESS".
 THIS DID NOT ADDRESS THE REQUEST FOR A
 WINDOW SIZE AND TYPE TO SHOW COMPIANCE
 WITH FBC1005.4.
  
 5.) SEE PREVIOUS LIST, ITEM #7, THE ROOF
 SHEATHING NAILING NOTE (SHEET SP)
 CONFLICTS WITH 2-A4 AND IS
 NOT COMPLIANT FOR ZONE 4, FBC*TABLE
 2306.1.SHEET SP HAS BEEN REVISED TO
 HAVE A NAILING PATTERN OF 12/6, A2 IS
 6/6 EXCEPT FOR GABLES AT 4/6.THERE ARE
 NO GABLES ON THE PLAN.THE NAILING
 SHOULD BE A MINIMUM OF 6/6 IN ZONES 1
 AND 2, 4/6 IN ZONE 3.CHECK ALL SHEETS
 AND REVISE ALL AFFECTED DETAILS AND
 NOTES TO BE COMPLIANT WITH THE MINIMUM
 REQUIREMENTS OF FBC*2306.1.
  
 6.) THE "ENERGY CALC REQUIREMENTS" FOR
 THE BLOCK WALLS ON SHEET SP DO NOT MEET
 THE MINIMUM REQUIREMENTS OF THE ENERGY
 CALCS PREPARED BY EARTHSMART.
  
 7.) IF SHUTTERS ARE TO BE A PART OF THIS
 PERMIT, COMPLETE THE SHUTTER ANCHORING
 SCHEDULE AS WELL AS A PLAN SHOWING WHICH
 OPENINGS ARE TO BE SHUTTERED AS WELL AS
 SHOWING THE MEANS OF ESCAPE FBC1005.4.5.
 NOTE THAT OCCUPANTS MUST BE ABLE TO
 ACCESS THE MEANS OF ESCAPE WITHOUT
 PASSING THROUGH A GARAGE OR A LOCKABLE
 DOOR NOT UNDER THEIR CONTROL.
  
 8.) SEE PREVIOUS LIST, ITEM #16, FLORIDA
 STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO TEST REPORTS, FAC9B72.
 WWW.FLORIDABUILDING.ORG.PLEASE PRINT
 THE STATE PRODUCT APPROVAL, IF
 AVAILABLE, AND CLEARLY INDICATE ON THAT
 APPROVAL WHICH PRODUCT YOU ARE USING.
  
 9.)FOR THE FLAT ROOF, PLEASE CIRCLE
 THE APPROVED ASSEMBLY YOU ARE GOING TO
 INSTALL.
  
 ANY PRODUCT APPROVALS NOT SUBMITTED
 PROPERLY PRIOR TO ISSUANCE WILL REQUIRE
 SEPARATE PERMITS.
  
 10.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE IS REQUIRED TO BE
 CHARGED IF THE COMMENTS ARE NOT PROPERLY
 ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-22 Cont ID  
Sent By shill Date 2005-02-22 Time 16:49 Rev Time 3.00
Received By shill Date 2005-02-18 Time 16:38 Sent To PC
Notes
2005-02-22 00:00:00PERMIT #05011482
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.) ENERGY CALCS REQUIRED, FBC13-101.2.
  
 4.) PROVIDE A COPY OF A SURVEY FOR THIS
 PROPERTY.
  
 5.) THE ARCHITECT'S SEAL IS TO BE DATED,
 FAC61G1-16.003.
  
 6.) EMERGENCY EGRESS REQUIRED, FBC
 1005.4.SHOW WINDOW SIZE AND TYPE FOR
 OFFICE/GUEST BEDROOM.
  
 7.) THE ROOF SHEATHING NAILING NOTE
 (SHEET SP) CONFLICTS WITH 2-A4 AND IS
 NOT COMPLIANT FOR ZONE 4, FBC*TABLE
 2306.1.
  
 8.) THE INFORMATION PROVIDED IN ENERGY
 CALC REQUIREMENTS, SHEET SP, CONFLICTS
 WITH THE DETAILS ON THE PLAN.ALSO NOTE
 THAT IF A FORM 600C IS USED FOR ENERGY
 CALCS, THE INSULATION SPECIFIED DOES NOT
 MEET THE MINIMUM PRESCRIPTIVE
 REQUIREMENTS.
  
 9.) SAFETY GLASS REQUIRED IN M.BATH
 (A1), FBC2405.1.PLEASE NOTE ON THE
 PLAN.IMPACT GLASS IS COMPLIANT.
  
 10.) THE SHUTTER PRODUCT APPROVALS
 SUBMITTED ARE NOT NECESSARY AS ALL
 PRODUCTS ARE IMPACT, AND IMPACT WAS
 SPECIFIED ON THE PLAN.IF YOU WOULD
 LIKE TO INSTALL THE SHUTTERS OVER THE
 IMPACT RESISTANT PRODUCTS, PROVIDE A
 SHUTTER ANCHORING SCHEDULE, SEE
 ATTACHED.
  
 11.) THE SOFFIT VENTS ARE TO COMPLY WITH
 FBC2309.7.
  
 12.) INDICATE THE DISTANCE FROM GRADE TO
 THE BOTTOM OF THE FLOOR JOISTS,
 FBC2304.3.
  
 13.) SHOW CRAWL SPACE VENTILATION,
 FBC1804.6.3.1.
  
 14.) 1-A5, STATES "TOP OF FTG ELEVATION
 IS A MINIMUM OF 8? BELOW ADJACENT
 GRADE."DO YOU MEAN BOTTOM OF FOOTING?
 THE BOTTOM IS REQUIRED TO BE MINIMUM OF
 12" BELOW GRADE, FBC1804.1.3.PLEASE
 CLARIFY.
  
 15.) FOOTING B, S1, SHOWS A 12" FOOTER
 DEPTH ALTHOUGH THE NOTE (AND OTHER
 DETAILS) INDICATE 18".BOTTOM OF
 FOUNDATION TO BE A MINIMUM OF 12" BELOW
 GRADE, FBC1804.1.3.THE TOP OF SLAB IS
 TO BE 4" ABOVE GRADE, FBC*1804.1.7.
  
 16.) FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO TEST
 REPORTS, FAC9B72.
 WWW.FLORIDABUILDING.ORG.PLEASE PRINT
 THE STATE PRODUCT APPROVAL, IF
 AVAILABLE, AND CLEARLY INDICATE ON THAT
 APPROVAL WHICH PRODUCT YOU ARE USING.
  
 17.) SPECIFY A DESIGN PRESSURE FOR THE
 ROOF.
  
 18.) PRODUCT APPROVAL REQUIRED FOR THE
 CUSTOM GARAGE DOOR.SEE
 WWW.FLORIDABUILDING.ORG, FAC9B72.
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-08-29 Cont ID  
Sent By btrobaug Date 2007-08-29 Time 16:06 Rev Time 0.00
Received By btrobaug Date 2007-08-29 Time 15:54 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-07-06 Cont ID  
Sent By btrobaug Date 2007-07-06 Time 10:21 Rev Time 0.00
Received By btrobaug Date 2007-07-06 Time 09:26 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-12-05 Cont ID  
Sent By btrobaug Date 2006-12-05 Time 09:34 Rev Time 0.75
Received By btrobaug Date 2006-12-05 Time 08:27 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-12-02 Cont ID  
Sent By btrobaug Date 2005-12-02 Time 14:44 Rev Time 0.50
Received By btrobaug Date 2005-12-02 Time 14:03 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2005-11-22 Cont ID  
Sent By btrobaug Date 2005-11-22 Time 06:49 Rev Time 0.50
Received By btrobaug Date 2005-11-22 Time 06:04 Sent To P
Notes
2005-11-22 00:00:00 
 THERE ARE NO REVISIONS DESIGNATED ON THE
 PLANS SUBMITTED, AND NO DATE ON THE
 ARCHITECTS SEAL. THE TITLE BLOCK ON ALL
 SHEETS HAVE THE SAME DATE.
  
 THERE IS NO ELECTRICAL REVIEW ON THIS
 RESUB. PLEASE BE MORE SPECIFIC ON THE
 ELECTRICAL RESUB, IF ONE IS NEEDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-02 Cont ID  
Sent By btrobaug Date 2005-08-02 Time 08:42 Rev Time 0.50
Received By btrobaug Date 2005-08-02 Time 08:41 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-10 Cont ID  
Sent By btrobaug Date 2005-02-10 Time 08:59 Rev Time 0.50
Received By btrobaug Date 2005-02-09 Time 16:26 Sent To M
Notes
2005-02-10 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 I SPOKE WITH THE OWNER/CONTRACTOR WHO
 INDICATED HE WANTS TO INSTALL AN
 UPGRADED SERVICE. PLEASE PROVIDE THE
 FOLLOWING FOR REVIEW.
  
 1} A RISER DIAGRAM FOR ALL ELECTRICAL
 EQUIPMENT.
  
 2} PROPSED LOCATIONN OF ALL EQUIPMENT ON
 THE DRAWING.
  
 3} PLEASE INCLUDE THE AIC RATINGS PER
 110.9. CONTACT FPL FOR FAULT CURRENT AT
 THEIR TRANSFORMER SERVING THE
 RESIDENCE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2007-08-23 Cont ID  
Sent By adarroug Date 2007-08-23 Time 15:50 Rev Time 0.00
Received By adarroug Date 2007-08-23 Time 15:49 Sent To E
Notes
2007-08-23 15:50:18TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2007-06-27 Cont ID  
Sent By adarroug Date 2007-06-27 Time 14:52 Rev Time 0.00
Received By adarroug Date 2007-06-27 Time 14:52 Sent To E
Notes
2007-06-27 14:53:16TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-01-23 Cont ID  
Sent By adarroug Date 2007-01-23 Time 10:22 Rev Time 0.00
Received By adarroug Date 2007-01-23 Time 10:22 Sent To M
Notes
2007-01-23 10:22:49TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-01-05 Cont ID  
Sent By adarroug Date 2007-01-05 Time 12:41 Rev Time 0.00
Received By adarroug Date 2007-01-05 Time 12:41 Sent To M
Notes
2007-01-05 12:42:11TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-12-26 Cont ID  
Sent By adarroug Date 2006-12-26 Time 11:32 Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 11:32 Sent To M
Notes
2006-12-26 11:32:34TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 15:38 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 15:38 Sent To M
Notes
2006-12-17 15:39:16TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status   Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 19:19 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 19:19 Sent To E
Notes
2006-11-29 19:19:47SENT TO BILL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 13:15 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 13:15 Sent To B
Notes
2006-06-08 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-04-06 Cont ID  
Sent By adarroug Date 2006-04-06 Time 11:22 Rev Time 0.00
Received By adarroug Date 2006-04-06 Time 11:22 Sent To P
Notes
2006-04-06 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-02-08 Cont ID  
Sent By adarroug Date 2006-02-08 Time 16:38 Rev Time 0.00
Received By adarroug Date 2006-02-08 Time 16:38 Sent To P
Notes
2006-02-08 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-11-17 Cont ID  
Sent By adarroug Date 2005-11-17 Time 18:08 Rev Time 0.00
Received By adarroug Date 2005-11-17 Time 18:08 Sent To E
Notes
2005-11-17 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-17 Cont ID  
Sent By adarroug Date 2005-08-17 Time 15:56 Rev Time 0.00
Received By adarroug Date 2005-08-17 Time 15:56 Sent To B
Notes
2005-08-17 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-01 Cont ID  
Sent By adarroug Date 2005-08-01 Time 09:51 Rev Time 0.00
Received By adarroug Date 2005-08-01 Time 09:51 Sent To E
Notes
2005-08-01 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 12:34 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 12:34 Sent To Z
Notes
2005-07-21 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-04 Cont ID  
Sent By adarroug Date 2005-02-04 Time 09:40 Rev Time 0.00
Received By adarroug Date 2005-02-04 Time 09:40 Sent To E
Notes
2005-02-04 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 10:51 Rev Time 0.00
Received By mjacobs Date 2005-01-31 Time 10:51 Sent To Z
Notes
2005-01-31 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2007-01-23 Cont ID  
Sent By tgordon Date 2007-01-23 Time 15:29 Rev Time 0.25
Received By tgordon Date 2007-01-23 Time 15:29 Sent To  
Notes
2007-01-23 15:32:04REVISION TO MECHANICAL PLANS AND ENERGY CAL'S.
 *** PROVISO ***
 1) PROVIDE COMBUSTION AIR FOR GAS CLOTHES DRYER, PER
 2004 FBC?R M1701.1.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2007-01-05 Cont ID  
Sent By tgordon Date 2007-01-05 Time 13:43 Rev Time 0.30
Received By tgordon Date 2007-01-05 Time 13:43 Sent To  
Notes
2007-01-05 13:51:07MECHANICAL REVISION
 *** DENIED ***
 1) MECHANICAL PLANS ARE SEALED BY AN ARCHITECT, ONLY BE
 CAN MAKE CHANGES TO THE PLANS, AND WHITE OUT MAY NOT BE
 USED ON PLANS.
  
 2) PLANS DO NOT SHOW HOW THE RETURN AIR PLENUM IS GOING
 TO RETURN AIR TO THE AIR HANDLER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-12-27 Cont ID  
Sent By tgordon Date 2006-12-27 Time 08:37 Rev Time 0.30
Received By tgordon Date 2006-12-27 Time 08:37 Sent To  
Notes
2006-12-27 08:49:30MECHANICAL REVISION
 *** DENIED ***
 1) PLEASE PROVIDE COMBUSTION AIR FOR GAS CLOTHES DRYER,
 PER 2004 FBC/R M1701.1.
  
 2) RETURN AIR GRILL IN MUD ENTRY WILL NOT WORK IF THE
 DOORS ARE CLOSED, PLEASE MOVE TO DINNING ROOM, PER 2004
 FBC/R M1602.4.
  
 3) 9" RETURN AIR DUCT TO MASTER SUITE IS TO SMALL FOR
 535 CFM'S OF SUPPLY AIR, AND NEEDS TO BE 12".
 BALANCED RETURN AIR.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-12-18 Cont ID  
Sent By tgordon Date 2006-12-18 Time 16:16 Rev Time 0.30
Received By tgordon Date 2006-12-18 Time 16:16 Sent To  
Notes
2006-12-18 16:22:03*** DENIED ***
 1) REVISIONS TO THE MECHANICAL PLANS CAN ONLY BE DONE
 BY THE ARCHITECT OF RECORDS (EDWARD H. SHEAHAN) AND
 PLANS AND ENERGY CALCULATION WILL REQUIRE HIS SEAL AND
 SIGNATURE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2005-11-23 Cont ID  
Sent By tgordon Date 2005-11-23 Time 10:50 Rev Time 0.15
Received By tgordon Date 2005-11-23 Time 10:50 Sent To E
Notes
2005-11-23 00:00:00MECH. PLANS HAD PASSED ON 8-3-05.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-03 Cont ID  
Sent By rregueir Date 2005-08-03 Time 18:39 Rev Time 0.00
Received By rregueir Date 2005-08-03 Time 18:39 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-02-15 Cont ID  
Sent By prafter Date 2005-02-15 Time 11:42 Rev Time 1.50
Received By prafter Date 2005-02-15 Time 11:42 Sent To P
Notes
2005-02-15 00:00:00MECH. A/C REVIEW.
  
 1. PROVIDE FL. ENERGY CALCULATIONS FOR
 RENOVATED BULDING. FBC/CHAPTER 13
 /101.5.1 .
 2.PROVIDE FOR COMBUSTION AIR FOR GAS
 DRYER IN LND/ROOM, TO CONFORM WITH 2001
 FBC/M SECTION 702 THROUGH 705 FOR SIZING
 AND INSTALLATION.NOTE;SUBMIT GAS
 DRYER INFORMATION FOR GAS BTU/PER HR
 RATING.
 3.R/A AIR DUCTS ARE NOT SIZED.
 4. MAIN SUPPLY AIR DUCTS NOT SIZED.
 5. PROVIDE FOR R/A OUT OF BEDROOM,
 OFFICE/GBRM. 2001 FBC/M 601.4 BALANCED
 RETURN AIR.
  
 PAT RAFTER 561/805/6728 .
 PLEASE CALL IF THEAR ENY QUESTIONS.

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-04-07 Cont ID  
Sent By jleech Date 2006-04-07 Time 14:00 Rev Time 0.00
Received By jleech Date 2006-04-07 Time 14:00 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-02-10 Cont ID  
Sent By jleech Date 2006-02-10 Time 12:04 Rev Time 0.50
Received By jleech Date 2006-02-10 Time 12:04 Sent To B
Notes
2006-02-10 00:00:00DENIED;
 PLUMBING PLANS WERE NOT CORRECTED FROM
 LAST REVIEW 11/22/05.
 1.TUB SHOWER AND SINK IN GARAGE ARE NOT
 VENTED TO FBC-2001 CHAPTER 9.
 2.CLEANOUTS ARE REQUIRED WHEN DRAINAGE
 SYSTEM EXITS THE HOUSE. SEE FBC-2001
 SEC. 708.3.5. CLEANOUTS REQUIRED AT
 KITCHEN, TUB, SHOWER AND BATHROOM DRAIN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-11-22 Cont ID  
Sent By jleech Date 2005-11-22 Time 15:04 Rev Time 0.75
Received By jleech Date 2005-11-22 Time 15:02 Sent To M
Notes
2005-11-22 00:00:00DENIED;
 PLUMBING PLAN WAS CHANGED FROM LAST
 REVIEW 8/3/05. TUB AND SHOWER ARE NOT
 VENTED. CLEANOUTS REQUIRED AT JUNCTION
 OF BUILDING DRAIN AND BUILING SEWER.
 SEC708.3.5.
 SINK IN GARAGE IS NOT VENTED.
 PLUMBING REVIEW BY
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-03 Cont ID  
Sent By jleech Date 2005-08-03 Time 09:16 Rev Time 0.25
Received By jleech Date 2005-08-03 Time 09:16 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-02-17 Cont ID  
Sent By jleech Date 2005-02-17 Time 15:44 Rev Time 0.50
Received By jleech Date 2005-02-17 Time 15:44 Sent To B
Notes
2005-02-17 00:00:00DENIED;
 1.PAGE P-1 NOTE 20 WATER TEST ON
 DRAINAGE PIPE IS 5' NOT 3'.
 2.TWO WAY CLEANOUTS ARE REQUIRED WHEN
 DRAINAGE PIPES EXIT HOUSE.
 3.TUB AND SHOWER ARE NOT VENTED,
 4.SINK IN GARAGE REQUIRES A VENT AND
 CANNOT BE PART OF THE WET VENT SYSTEM OF
 A BATHROOM GROUP. SEC 909.1
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2005-07-29 Cont ID  
Sent By mmclean Date 2005-07-29 Time 17:28 Rev Time 0.00
Received By mmclean Date 2005-07-28 Time 17:55 Sent To I
Notes
2005-07-29 00:00:00NOTE: MUST PULL SEPERATE PERMIT FOR
 WALL/GATE/FENCE WITH UTILITIES EASEMENT
 APPROVAL.
  
 NOTE: MUST PULL SEPERATE PERMIT FOR
 POOL/SPA/DECK/SCREEN ENCLOSURE.
  
 APPROVAL DOES NOT INCLUDE
 FENCE/WALL/GATE/POOL/SPA/DECK/SCREEN
 ENCLOSURE.
2005-07-28 00:00:00NEED TO HAVE SECOND OPINION ON PLANS

Review Stop Z ZONING
Rev No 1 Status F Date 2005-02-03 Cont ID  
Sent By mmclean Date 2005-02-03 Time 10:50 Rev Time 0.00
Received By mmclean Date 2005-02-03 Time 10:50 Sent To I
Notes
2005-02-03 00:00:00DENIED
 1. NEED TO PROVIDE TWO COPY OF SURVEY
 (SIGNED & SEAL).
 2.DRIVEWAY DIMENSION SHOULD BE PROVIDED
 (WIDTH & LENGTH (MUST MEET 1000SQ FT OR
 75% OF LANDSCAPE WITHIN THE FIRST 25FT
 FRONT SETBACK).
 3. MUST PULL SEPERATE PERMIT FOR
 POOL/DECK/SCREEN ENCLOSURE.
 4. MUST PULL SEPERATE PERMIT FOR
 PRIVACY
 WALL WITH CITY OF WEST PALM BEACH
 UTILITY DEPT APPROVAL.WALL MUST BE
 DRAWN TO SCALE.
 5. TRELLIS MUST BE DRAWN TO SCALE, WITH
 THE HEIGHT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 CONSTRUCTION SVCS
 805-6720