Plan Review Details - Permit 05011473
Plan Review Stops For Permit 05011473
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-03-01 Cont ID  
Sent By rmcdouga Date 2005-03-01 Time 11:23 Rev Time 0.00
Received By rmcdouga Date 2005-03-01 Time 07:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-07 Cont ID  
Sent By rmcdouga Date 2005-02-07 Time 10:21 Rev Time 0.00
Received By rmcdouga Date 2005-02-07 Time 10:21 Sent To  
Notes
2005-02-07 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SHEET A-2 HAS REVISION #6 WHICH IS
 NOT SHOWN ON THE APPROVED MASTERED SET
 ON FILE. PLANS ISSUED UNDER THE MASTER
 ARE REQUIRED TO HAVE NO CHANGES FROM
 THE
 MASTER. REVISIONS WILL HAVE TO BE MADE
 AFTER THE PERMIT IS ISSUED AND WILL
 APPLY TO THAT PARTICULAR PERMIT FOR
 WHICH IT IS SUBMITTED AND APPROVED.
  
 3) SUBMIT ENERGY CALCULATION FORMS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-04-13 Cont ID  
Sent By dpalmer Date 2006-04-13 Time 14:53 Rev Time 0.00
Received By dpalmer Date 2006-04-13 Time 14:53 Sent To PC
Notes
2006-04-13 00:00:00REDLINED 250.56

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-04-06 Cont ID  
Sent By dpalmer Date 2006-04-06 Time 07:07 Rev Time 0.00
Received By dpalmer Date 2006-04-06 Time 07:07 Sent To PC
Notes
2006-04-06 00:00:00*********UNSAT ***********
  
 1) NOTE: PLEASE SEE ALL SHEETS ARE TO BE
 SIGNED, DATED AND SEALED BY THE
 ARCHITECT OF RECORD.
 FS 481.221
  
 2) NOTE: PLEASE SEE MIN GEC HAS NOW BEEN
 CHANGED TO A #4.
 THE GEC, SHALL BE SIZED PER 250.66, A #2
 SHALL BE INSTALLED FROM THE FOOTER
 STEEL.
 ** ORIG PLANS CALLED FOR 2-COPPER GRNDS
 RODS, 1/0 AWG MIN.
 250.66,250.64,250.68.
 PLEASE SEE THE GROUNDING ELECTRODE
 SYSTEMS ON MANY PREVIOUS PLANS HAVE BEEN
 REDLINED, HOWEVER PLANS NEED TO BE
 CORRECTED AT THIS TIME FOR ALL FUTURE
 REVISIONS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANREVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-01-23 Cont ID  
Sent By dpalmer Date 2006-01-23 Time 07:44 Rev Time 0.00
Received By dpalmer Date 2006-01-23 Time 07:44 Sent To  
Notes
2006-01-23 00:00:00PLANS REDLINED.
  
  
 PLEASE SEE MIN GEC HAS NOW BEEN CHANGED
 TO A #4.
 THE GEC, SHALL BE SIZED PER 250.66, A #2
 SHALL BE INSTALLED FROM THE FOOTER
 STEEL.
  
 ** ORIG PLANS CALLED FOR 2-COPPER GRNDS
 RODS, 1/0 AWG MIN.
  
  
 250.66,250.64,250.68.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-25 Cont ID  
Sent By dpalmer Date 2005-12-25 Time 13:06 Rev Time 0.00
Received By dpalmer Date 2005-12-25 Time 13:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-30 Cont ID  
Sent By dpalmer Date 2005-11-30 Time 15:23 Rev Time 0.00
Received By dpalmer Date 2005-11-30 Time 15:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-03-01 Cont ID  
Sent By rmcdouga Date 2005-03-01 Time 11:22 Rev Time 0.00
Received By rmcdouga Date 2005-03-01 Time 11:22 Sent To  
Notes
2005-03-01 00:00:00PASSED UNDER MASTER # 04041127

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-01 Cont ID  
Sent By rmcdouga Date 2005-03-01 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2005-03-01 Time 11:20 Sent To  
Notes
2005-03-01 00:00:00PASSED UNDER MASTER # 04041127.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-04-12 Cont ID  
Sent By adarroug Date 2006-04-12 Time 15:46 Rev Time 0.00
Received By adarroug Date 2006-04-12 Time 15:46 Sent To E
Notes
2006-04-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-04-05 Cont ID  
Sent By adarroug Date 2006-04-05 Time 11:18 Rev Time 0.00
Received By adarroug Date 2006-04-05 Time 11:18 Sent To E
Notes
2006-04-05 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-01-31 Cont ID  
Sent By adarroug Date 2006-01-31 Time 16:52 Rev Time 0.00
Received By adarroug Date 2006-01-31 Time 16:52 Sent To E
Notes
2006-01-31 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-17 Cont ID  
Sent By adarroug Date 2006-01-17 Time 17:21 Rev Time 0.00
Received By adarroug Date 2006-01-17 Time 17:21 Sent To E
Notes
2006-01-17 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-22 Cont ID  
Sent By adarroug Date 2005-11-22 Time 10:35 Rev Time 0.00
Received By adarroug Date 2005-11-22 Time 10:35 Sent To E
Notes
2005-11-22 00:00:00TO "DPALMER"DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-23 Cont ID  
Sent By adarroug Date 2005-02-23 Time 14:35 Rev Time 0.00
Received By adarroug Date 2005-02-23 Time 14:35 Sent To B
Notes
2005-02-23 00:00:00TO "RMCDOUGAL DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-03 Cont ID  
Sent By adarroug Date 2005-02-03 Time 10:09 Rev Time 0.00
Received By adarroug Date 2005-02-03 Time 10:09 Sent To E
Notes
2005-02-03 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 10:17 Rev Time 0.00
Received By mjacobs Date 2005-01-31 Time 10:17 Sent To Z
Notes
2005-01-31 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-03-01 Cont ID  
Sent By rmcdouga Date 2005-03-01 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2005-03-01 Time 11:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-03-01 Cont ID  
Sent By rmcdouga Date 2005-03-01 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2005-03-01 Time 11:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-02-02 Cont ID  
Sent By mmclean Date 2005-02-02 Time 14:49 Rev Time 0.00
Received By mmclean Date 2005-02-02 Time 14:49 Sent To I
Notes
***NONE***