| Plan Review Stops For Permit 05011469 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-08-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-08-04 |
Time |
16:39 |
Rev Time |
0.75 |
| Received By |
mjacobs |
Date |
2005-08-04 |
Time |
16:28 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-06-20 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-06-20 |
Time |
10:30 |
Rev Time |
3.50 |
| Received By |
mjacobs |
Date |
2005-06-20 |
Time |
06:55 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-05-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-05-06 |
Time |
14:18 |
Rev Time |
3.00 |
| Received By |
mjacobs |
Date |
2005-05-06 |
Time |
11:24 |
Sent To |
PC |
|
| Notes |
| 2005-05-06 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT:05011469 | | | ADD:1112 FLORIDA AVE | | | CONT:CASTLE CONSTRUCTION INC. | | | TEL: (561)818-6996 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW:2ND | | | ACTION:DENIED | | | | | | 1) IMPACT FEES. THE PLANS SHALL BE TAKEN | | | TO PALM BEACH COUNTY BUILDING DEPARTMENT | | | FOR IMPACT FEE ASSESSMENT. THEY SHALL BE | | | STAMPED AT THAT OFFICE AND A COPY OF THE | | | PAID RECEIPT SUBMITTED TO THE CITY OF | | | WEST PALM BEACH DEPT OF CONSTRUCTION | | | SERVICES BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2 ) FBC 13-103.0ENERGY CODE COMPLIANCE | | | SHALL BE DEMONSTRATED BY SUBMITTAL OF | | | APPROPRIATE CODE COMPLIANCE FORMS | | | | | | 3) PRODUCT APPROVALS ARE REQUIRED ALONG | | | WITH STATE COVER SHEET FOR ALL PRODUCTS | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | BUILDING PLAN REVIEW | | | MYRON JACOBS | | | TEL: (561)805-6726 | | | FAX: (561)659-8026 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-02-18 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-02-18 |
Time |
08:31 |
Rev Time |
2.00 |
| Received By |
alange |
Date |
2005-02-17 |
Time |
16:36 |
Sent To |
Z |
|
| Notes |
| 2005-02-18 00:00:00 | DENIED | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 3.PRODUCT APPPROVALS REQUIRED WITH | | | QUALITY ASSURANCE FOR ALL EXTERIOR | | | DOORS, ROOFING, LITELS, STRAPS AND | | | TIE-DOWNS. | | | | | | 4.SHOW SIZE AND LOCATION OF ATTIC | | | ACCESS.FBC 2309.6 | | | | | | 5.SHOW LOCATION OF GRADE ON B A/4 | | | | | | 6.R VALUES ON ENERGY CALCS DO NOT | | | MATCH PLANS. | | | | | | 7.SIGN OWNER/AGENT ON ENERGY CALCS. | | | | | | 8. TABLE 2306.1 PALM BEACH COUNTY | | | AMENDMENTS | | | ROOF SHEATHING NAILING REQUIREMENTS | | | | | | ZONE 1 & 28D COMMON | | | 6" EDGES & 6" INTERMEDIATES | | | | | | ZONE 38DCOMMON | | | 4" EDGES & 6" INTERMEDIATES | | | SHOW ROOF SHEATHING COMPLYING WITH THIS | | | SECTION. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2005-06-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-06-14 |
Time |
10:59 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-06-14 |
Time |
10:38 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-06-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-06-02 |
Time |
11:25 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2005-06-02 |
Time |
08:01 |
Sent To |
P |
|
| Notes |
| 2005-06-02 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE AIC CALCULATIONS PER 110.9. | | | THIS IS THE THIRD REQUEST FOR SAME. CALL | | | WITH QUESTIONS. | | | | | | 2} INDICATE LOCATION OF SERVICE | | | EQUIPMENT. THIS INCLUDES PANELS. | | | | | | 3} THE DRYER CALC MUST COMPLY WITH | | | 220.18. | | | | | | 4} PLEASE SEE ARTICLE 905.2.2 FBC FOR | | | LOCATION, AND TYPE PERMITTED PER | | | LOCATION, OF SMOKE DETECTORS. ALSO | | | ARTICLE 8-1.4.2 NFPA-72.STAIRWELL AND | | | KITCHEN ISSUES. | | | | | | 5} NOTE #13 REGARDING GFI'S SHOULD BE | | | REWORDED TO SHOW COMPLIANCE WITH 680.22, | | | POOL RECEPTACLES, AND 210.8(A)(6), | | | KITCHEN COUNTERTOP RECEPTACLES, OR BE | | | REMOVED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-04-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-01 |
Time |
09:16 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
2005-04-01 |
Time |
09:16 |
Sent To |
P |
|
| Notes |
| 2005-04-01 00:00:00 | ********** UNSAT 2ND REVIEW *********** | | | | | | PLEASE SEE SOME NOTES FROM PREVIOUS | | | REVIEW DONE BY BILL TROBAUGH STILL NEED | | | TO BE ADDRESSED. | | | | | | PLEASE ALSO SEE "NEW NOTES AT BOTTOM OF | | | PLANS. | | | | | | 1)NOTE: NOTE #1, YES, THE RISER DIAGRAM | | | NOW HAS CONDUIT AND CONDUCTOR SIZES, | | | HOWEVER PLEASE SEE SEC'S ARE TOO SMALL | | | FOR 400A SERVICE PROVIDED. | | | PLEASE SEE MIN SEC'S TO BE PER 310.16, | | | PER 240.4 | | | PLEASE ALSO SHOW CONDUCTORS FROM GUTTER | | | TO MAINS. | | | | | | 2)NOTE: NOTE #2, NO, PLEASE SEE 250.66 | | | FOR MIN SIZE FOR GROUNDING ELECTRODE | | | CONDUCTOR. PLEASE SEE MIN 1/0. | | | | | | 3)NOTE: NOTE #3,NO, PLEASE SUBMIT PER | | | PREVIOUS NOTES. 110.9 | | | | | | 4)NOTE: NOTE #4 OK. | | | | | | 5)NOTE: NOTE #5 OK. | | | | | | 6)NOTE: NOTE #6 NO, PLEASE SEE NOTE #13. | | | PLEASE ALSO SEE NEW NOTES. | | | | | | 7)NOTE: NOTE #7 OK | | | | | | 8)NOTE: NOTE #8 OK. | | | PLEASE ALSO SEE NEW NOTES AT BOTTOM. | | | | | | 9)NOTE: NOTE #9 OK. | | | | | | 10)NOTE: NOTE #10 OK. | | | | | | 11)NOTE: NOTE #11 NO, PLEASE SEE | | | PREVIOUS COMNMENTS, PLEASE SEE 220.18 | | | MIN VA REQUIRED. | | | PLEASE ALSO SEE PANEL SCHEDULES DO NOT | | | INDICATE DRYER(S) AT ALL?? | | | | | | 12)NOTE: NOTE #12 OK. | | | | | | 13)NOTE: NOTE #13 OK. | | | | | | 14)NOTE: NOTE #14 OK. | | | | | | 15)NOTE: NOTE #15 NO, PLEASE SEE RECEPTS | | | ADDED , HOWEVER STILL DO NOT INDICATE | | | GFI'S. | | | | | | 16)NOTE: NOTE #15, NO, PLEASE SEE | | | 210.8A6, THIS WAS IN SECOND PART OF | | | NOTE. PLEASE SEE SYMBOL SCHEDULE, PLEASE | | | ADJUST SYMBOLS TO CORRELATE WITH PLANS | | | AND SEPARATE SYMBOLS FOR GFI /HALF | | | SWICTHED RECEPTS. | | | | | | 17)NOTE: NOTE #17 OK. | | | | | | 18)NOTE: NOTE #18, NO, PLEASE SEE | | | PREVIOUS NOTE. | | | | | | ** NEW NOTES** | | | | | | 1)NOTE: PLEASE SEE GFI NOTE/ NOTE #13, | | | MENTIONS ALL INDICATED RECEPTS TO BE | | | WP(WEATHER PROOF)? | | | PLEASE SEE MENTIONS RECETPS WITHIN 15' | | | OF POOL? PLEASE SEE CODE REQUIRES | | | WITH-IN 20', | | | PLEASE SEE REQUIREMENTS FOR RECEPTS | | | WITH-IN 6'/4' OF SINK CHANGED IN THE 93 | | | NEC. | | | PLEASE SEE 2002 NEC 210.8 | | | | | | 2)NOTE: PLEASE SEE THERE ARE MANY ITEMS | | | LISTED ON PANEL SCHEDULES WHICH DO NOT | | | INDICATE OCP, AWG ETC. | | | | | | 3)NOTE: PLEASE SEE PANEL SCHEDULE | | | INDICATES TWO WATER HEATERS? | | | | | | 4)NOTE: PLEASE SEE PLANS INDICATE "SPA | | | TUB", DOES THIS CONTAIN ELEC MOTOR? IF | | | SO , PLEASE INDICATE GFI PROTECTION PER | | | 680.71 | | | | | | 5)NOTE: PLEASE SEE NUMEROUS DEVICE | | | REQUIRED TO BE SHOWN AS GFI PER 210.8 | | | | | | 6)NOTE: PLEASE SEE COPY OF FS | | | 553.80(2)(B) ATTACHED WITH RESPECT TO | | | DESIGN PROFESSIONAL. | | | IF PLANS COME BACK WITH ANY OF THE SAME | | | COMMENTS FROM THE FIRST TWO REVIEWS NOT | | | ADDRESSED, A 4X FEE SHALL BE ACCESSED | | | FOR THE PLAN REVIEW PORTION OF THE | | | PREMIT FEE.(30%) | | | | | | | | | PLEASE SE SURE TO REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-02-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-02-03 |
Time |
13:05 |
Rev Time |
2.00 |
| Received By |
btrobaug |
Date |
2005-02-03 |
Time |
09:53 |
Sent To |
P |
|
| Notes |
| 2005-02-03 00:00:00 | | | | | | | | | | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SHOW CONDUIT AND CONDUCTOR SIZES FOR | | | THE SERVICE RISER EQUIPMENT, QUOTED CODE | | | ARTICLES ARE UNACCEPTABLE PER 104.2.1 | | | FBC. | | | | | | 2} SHOW GROUNDING PER 250 ON THE RISER. | | | | | | 3} GIVE AIC CALCULATIONS AND RATINGS FOR | | | EQUIPMENT PER 110.9. | | | | | | 4} SHOW LOCATION OF ALL SERVICE | | | EQUIPMENT ON THE PLANS. PLEASE SEE | | | 230.70 CWPB FOR DISCONNECT | | | REQUIREMENTS. | | | | | | 5} LOCATE THE CONDENSING UNIT ON THE | | | PLAN FOR COMPLIANCE OF 210.63 AND | | | 440.14. | | | | | | 6} REFERRING TO NOTE #13 IN THE | | | ELECTRICAL NOTES, PLEASE ALSO SEE | | | 210.8(A)(6) RE:KITCHEN RECEPTACLES. | | | | | | 7} THE OCP FOR 15KW OF HEAT IS INCORRECT | | | ON THE PANEL SCHEDULE. PLEASE CORRELATE | | | WITH MECHANICAL CONTRACTOR. THIS AHU IS | | | EXCEPTIONALLY LARGE FOR THE THE | | | RESIDENCE SIZE.SAME COMMENT FOR "A/C | | | COMPRESSOR UNIT" | | | | | | 8} WATER HEATER HAS #8 CONDUCTORS FED | | | FROM A 20 AMP BREAKER. PLEASE CORRECT. | | | | | | 9} THE DISHWASHER HAS #10 CONDUCTORS ON | | | A 20 AMP BREAKER, ALTHOUGH NOT A | | | VIOLATION, THE INSTALLATION MUST BE AS | | | REVIEWED PLANS. | | | | | | 10} CIRCUITS 14-19 LABLED "GENERAL | | | LIGHTING" #14 CONDUCTORS ON A 20 AMP OCP | | | ARE IN VIOLATION OF 310.16. | | | | | | 11} THE DRYER CALCULATION MUST COMPLY | | | WITH 220.18 FOR THE CALCULATION | | | (5KW.)SHOWN TWICE IN THE SAME CALC, ONCE | | | @ 4500, P[LEASE CORRELATE. | | | | | | 12} NOTE #2 IN THE "GENERAL ELECTRICAL | | | NOTES" REFERS TO TW WIRE. PLEASE NOTE | | | THAT THE 60O TABLE MUST BE USED FOR | | | THESE CONDUCTORS IF THIS NOTE REMAINS ON | | | THE PLAN. | | | | | | 13} THE LAUNDRY CIRCUIT MUST COMPLY WITH | | | 220.16(B)(1500W). | | | | | | 14} THERE IS NO LOW VOLTAGE SYSTEMS | | | SHOWN ON THE PLAN. IF THESE SYSTEMS ARE | | | ADDED AT A LATTER DATE THEY WILL REQUIRE | | | SEPERATE PLANS, REVIEWS AND | | | APPLICATIONS. | | | | | | 15} PLEASE ADD AND SHOW LOCATIONS OK | | | REQUIRED OUTSIDE RECEPTACLES PER | | | 210.52(E) & 210.8(A)(3). | | | | | | 16) CHECK KITCHEN COUNTERTOP RECEPTACLE | | | SPACING PER 210.52(C)(1). ALSO SEE | | | 210.8(A)(6). | | | | | | 17} PLACE A SMOKE DETECTOR AT THE | | | STAIRWELL ON THE 2ND FLOOR PER 905.2.2 | | | FBC. | | | | | | 18} THE DESIGNER OF RECORD MUST TAKE | | | RESPONSIBILITY FOR THE DRAWINGS PER | | | 104.2.1 FBC AND 61G15.23.002 FAC. | | | | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-01-28 |
|
|
Cont ID |
|
| Sent By |
ptjomsto |
Date |
2005-01-28 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
ptjomsto |
Date |
2005-01-28 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2005-01-28 00:00:00 | | | | HISTORIC APPROVED 1/21/05 BY S PILAND |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-05-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-10 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-10 |
Time |
17:06 |
Sent To |
P |
|
| Notes |
| 2006-05-10 00:00:00 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-08-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-01 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-01 |
Time |
10:08 |
Sent To |
B |
|
| Notes |
| 2005-08-01 00:00:00 | TO "MJACOBS" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-05-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-24 |
Time |
18:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-24 |
Time |
18:21 |
Sent To |
E |
|
| Notes |
| 2005-05-24 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-03-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-29 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-29 |
Time |
13:24 |
Sent To |
E |
|
| Notes |
| 2005-03-29 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-01-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-28 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-28 |
Time |
16:24 |
Sent To |
E |
|
| Notes |
| 2005-01-28 00:00:00 | TO "E" BOX. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-05-05 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-05-05 |
Time |
11:19 |
Rev Time |
1.00 |
| Received By |
prafter |
Date |
2005-05-05 |
Time |
11:19 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-02-14 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-02-14 |
Time |
12:21 |
Rev Time |
1.00 |
| Received By |
prafter |
Date |
2005-02-14 |
Time |
12:21 |
Sent To |
B |
|
| Notes |
| 2005-02-14 00:00:00 | A/C MECH. | | | | | | NO A/C PLANS OR EQUIPMENT INFORMATION | | | SUPPLYED WITH PLANS. | | | | | | PAT RAFTER 561/805/6728 . |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2006-05-15 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-05-15 |
Time |
10:46 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2006-05-15 |
Time |
10:46 |
Sent To |
PC |
|
| Notes |
| 2006-05-15 00:00:00 | ******REVISION DENIED****** | | | FBC-2001 PLUMBING, AND CITY OF WEST PALM | | | BEACH AMENDMENTS TO FBC-2001, CHAPTER 1 | | | ADMINISTRATION | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR A PLUMBING REVISION: | | | | | | 1. PER CITY AMENDMENTS 104.2.2 DESIGN | | | PROFESSIONAL. THE DESIGN PROFESSIONAL | | | SHALL AFFIX HIS OR HER SEAL, PRINT NAME, | | | SIGN NAME, AND DATE SAID DRAWINGS. NOTE: | | | ORIGINAL DRAWINGS HAD AN ENGINEER SEAL | | | ON PLUMBING ISOMETRICS THUS ANY | | | REVISIONS SHALL HAVE AN ENGINEER SEAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2005-06-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-06-13 |
Time |
11:23 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-06-13 |
Time |
11:23 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-04-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-04-14 |
Time |
17:27 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2005-04-14 |
Time |
17:27 |
Sent To |
M |
|
| Notes |
| 2005-04-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT A-5 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | | MEET CODE REQUIREMENTS. CORRECT THE | | | FOLLOWING: | | | A) NO TRAP FOR THE WATER CLOSET AS IT | | | HAS AN INTEGRAL TRAP. SECTION 1002.1 | | | B) SHOW THE TRAP AND STANDPIPE ON THE | | | WASH MACHINE SECTIONS 901.2.1 & 1002.1. | | | C) WASH MACHINE SHALL NOT DISCHARGE | | | INTO THE WET-VENTED BATHROOM GROUP. | | | SECTION 909.1 | | | D) LAV ON SEPARATE WALL FROM W/M | | | SECTION 104.2.1. | | | E) 2ND FLOOR BATHROOMS DO NOT REFLECT | | | THE FLOOR PLAN. SECTION 104.2.1. | | | 2) SEE ATTACHED SHEET SHOWING AN EXAMPLE | | | OF A SANT. RISER DIAGRAM THAT MEETS THE | | | CODE REQUIREMENTS AND REFLECTS THE FLOOR | | | PLAN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-02-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-02-11 |
Time |
16:23 |
Rev Time |
0.85 |
| Received By |
kstevens |
Date |
2005-02-11 |
Time |
16:23 |
Sent To |
M |
|
| Notes |
| 2005-02-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | | | | 1) SHT A-5 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | | MEET CODE REQUIREMENTS. | | | A) KITCHEN SINK IS NOT SHOWN ON RISER. | | | SECTION 104.2.1. | | | B) A TRAP IS REQUIRED FOR THE WASH | | | MACHINE. SECTION 1002.1. | | | C) A STANDPIPE IS REQUIRED FOR THE WASH | | | MACHINE. SECTION 1002.1. | | | D) A CLEANOUT IS REQUIRED, 4' ABOVE THE | | | FLOOR AT THE WASH MACHINE STACK. SECTION | | | 708.10. | | | E) WASH MACHINE AND W/C FOR POWDER ROOM | | | ARE ON A COMMON WALL. THE SANT. RISER | | | INDICATES THAT THE FIXTURES ARE ON | | | DIFFERENT WALLS. RISER SHALL REFLECT THE | | | FLOOR PLAN. | | | F) BATH #2 SHALL BE SHOWN AS DIRECTLY | | | ABOVE THE POWDER ROOM ON THE FIRST FLOOR | | | ON THE FLOOR PLAN, BUT IS SHOWN ON THE | | | OTHER END OF THE HOUSE ON THE RISER. | | | SECTION 104.2.1. | | | G) CLEANOUT LINE UPSTREAM OF BATH #2 IS | | | PIPED TO WHAT LOCATION? PLEASE CLARIFY. | | | SECTION 104.2.1. | | | H) MASTER BATH SHOWS A SHOWER, THEN A | | | W/C, THEN A TUB, THEN A LAV. FLOOR PLAN | | | SHOWS A TUR, A W/C THEN A LAV. PLEASE | | | HAVE SANT. RISER DIAGRAM REFLECT THE | | | FLOOR PLAN AND SHOW HOW THE PIPING WILL | | | BE INSTALLED. SECTION 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-02-22 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-02-22 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-02-22 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2005-02-22 00:00:00 | CALLED CONTR FOR P/U FILE C MM |
|
|