Plan Review Details - Permit 05011466
Plan Review Stops For Permit 05011466
Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2005-06-08 Cont ID  
Sent By mwennerg Date 2005-06-08 Time 14:54 Rev Time 0.00
Received By mwennerg Date 2005-06-08 Time 14:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-05-03 Cont ID  
Sent By mwennerg Date 2005-05-03 Time 14:52 Rev Time 0.00
Received By mwennerg Date 2005-05-03 Time 14:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-03-30 Cont ID  
Sent By mwennerg Date 2005-03-30 Time 15:00 Rev Time 0.00
Received By mwennerg Date 2005-03-30 Time 15:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-03-03 Cont ID  
Sent By nmccray Date 2005-03-03 Time 15:44 Rev Time 0.00
Received By nmccray Date 2005-03-03 Time 15:44 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-02-02 Cont ID  
Sent By nmccray Date 2005-02-02 Time 10:54 Rev Time 0.00
Received By nmccray Date 2005-02-02 Time 10:48 Sent To  
Notes
2005-02-02 00:00:00DENIED:
  
 1) ADDITIONAL PERMIT APPLICATION AND
 FEES ARE REQUIRED FOR THE FIRE
 SUPPRESSION SYSTEM.
  
 2) PLEASE SEE ADDITIONAL COMMENTS BY
 MECHANICAL PLAN REVIEW.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-05-04 Time 14:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-02 Cont ID  
Sent By adarroug Date 2005-05-02 Time 17:20 Rev Time 0.00
Received By adarroug Date 2005-05-02 Time 17:20 Sent To M
Notes
2005-05-02 00:00:00TO "PKRAUSS" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-17 Cont ID  
Sent By adarroug Date 2005-03-17 Time 15:14 Rev Time 0.00
Received By adarroug Date 2005-03-17 Time 15:14 Sent To FIRE
Notes
2005-03-17 00:00:00TO "F" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-23 Cont ID  
Sent By adarroug Date 2005-02-23 Time 16:14 Rev Time 0.00
Received By adarroug Date 2005-02-23 Time 16:14 Sent To M
Notes
2005-02-23 00:00:00TO "PK" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-28 Cont ID  
Sent By mjacobs Date 2005-01-28 Time 16:08 Rev Time 0.00
Received By mjacobs Date 2005-01-28 Time 16:08 Sent To M
Notes
2005-01-28 00:00:00TO "M/AC" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-06-08 Cont ID  
Sent By hmoser Date 2005-06-08 Time 15:01 Rev Time 0.00
Received By hmoser Date 2005-06-08 Time 15:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2005-05-02 Time   Rev Time 0.00
Received By hmoser Date 2005-05-02 Time 18:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-03-31 Cont ID  
Sent By pkrauss Date 2005-03-31 Time 11:10 Rev Time 0.35
Received By pkrauss Date 2005-03-31 Time 06:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-03-01 Cont ID  
Sent By pkrauss Date 2005-03-01 Time 16:15 Rev Time 0.40
Received By pkrauss Date 2005-03-01 Time 16:05 Sent To FIRE
Notes
2005-03-01 00:00:00PROVISO:
 PLEASE NOTE, TERMINATION OF GREASE
 EXHAUST DUCT SHALL BE A MINIMUM OF 2 FT
 HORIZONTAL DISTANCE BETWEEN VERTICAL
 DISCHARGE FANS & PARAPETS PROVIDED THAT
 THE PARAPET IS NOT HIGHER THAN THE TOP
 OF THE FAN DISCHARGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-02-01 Cont ID  
Sent By pkrauss Date 2005-02-01 Time 16:29 Rev Time 0.40
Received By pkrauss Date 2005-02-01 Time 16:29 Sent To FIRE
Notes
2005-02-01 00:00:00DENIED:
 1.PLEASE INDICATE DISTANCE FROM
 PROPERTY LINES, ADJACENT OR CONTIGUOUS
 BUILDINGS, AND FRESH AIR INTAKES IN
 ACCORDANCE WITH 2001 FBC(M)506.3.14.3.
  
 2.PROVIDE CLEARANCE TO COMBUSTIBLES
 PER 2001 FBC(M)506.3.8.
  
 3.PLAN SHEET 2 OF 2 GENERAL NOTES, #1
 INDICATES HOOD CONSTRUCTED WITH 18GA
 STAINLESS.NOTE #2 INDICATES GREASE
 DUCT 16GA STAINLESS.DISSIMILAR METALS,
 PLEASE CLARIFY.
  
 4.PLEASE NOTE PER 2001 FBC(M) 506.3.6,
 AIR VELOCITY WITHIN THE DUCT SYSTEM
 SHALL NOT BE LESS THAN 1,500 FPM BUT NOT
 GREATER THAN 2,500 FPM.
  
 ADDITIONAL PERMIT REQUIRED FOR THE FIRE
 SUPPRESSION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT(561)805-6719.