| 2005-02-14 00:00:00 | DENIED |
| | |
| | 1.SUBMIT EAST ELEVATIONS PLANS SO THAT |
| | FBC TABLE 600 ISSUES CAN BE ADDRESSED. |
| | |
| | 2.SUBMIT INFORMATION ON HOW BUILDING |
| | WILL BE TIED DOWN TO NEW STEM WALLS. |
| | |
| | 3.SEPERATE PERMITS REQUIRED FOR |
| | PLUMBING, ELECTRICAL, MECHANICAL AND |
| | DRIVEWAY AND SIDEWALKS. |
| | |
| | 4.SUBMIT TWO COPIES OF A SOILS REPORT. |
| | |
| | 5.THE BOTTOM OF FOOTING SHALL EXTEND |
| | NO LESS THAN 12" BELOW GRADE. |
| | FBC 1804.1.3 |
| | |
| | 6.TERMITE TREATING OF SOILS REQUIRED. |
| | SHOW REQUIREMENT ON PLANS. |
| | |
| | 7.FBC 3401.7.2.6 WHEN REPAIRS AND |
| | ALTERATIONS AMOUNTING TO MORE THAN 50% |
| | OF THE VALUE OF THE EXISTING STRUCTURE |
| | ARE MADE DURING ANY 12 MONTH PERIOD, THE |
| | BUILDING SHALL BE MADE TO CONFORM TO THE |
| | REQUIREMENTS FOR A NEW BUILDING. |
| | PLEASE SHOW ON PLANS HOW COMPLIANCE WILL |
| | BE MADE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | ART LANGE |
| | BUILDING PLANS EXAMINER |
| | 805-6672 |
| | |