Plan Review Details - Permit 05011266
Plan Review Stops For Permit 05011266
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-25 Cont ID  
Sent By shill Date 2005-03-25 Time 13:26 Rev Time 0.00
Received By shill Date 2005-03-25 Time 13:26 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-09 Cont ID  
Sent By shill Date 2005-03-09 Time 11:43 Rev Time 1.00
Received By shill Date 2005-03-09 Time 11:43 Sent To  
Notes
2005-03-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)HAVE THE PLANS STAMPED FOR IMPACT
 FEE REVIEW, 233-5025.
  
 2.)THE TEST REPORT SUBMITTED FOR THE
 EXTERIOR DOOR IS NOT THE TEST REPORT ON
 THE WEBSITE FOR FL1589.PLEASE PROVIDE
 TWO COPIES OF THE TEST REPORT FROM THE
 STATE WEBSITE AND FLORIDA STATE PRODUCT
 APPROVAL.WWW.FLORIDABUILDING.ORG

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-31 Cont ID  
Sent By shill Date 2005-01-31 Time 16:35 Rev Time 0.50
Received By shill Date 2005-01-31 Time 16:20 Sent To  
Notes
2005-01-31 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE SINKS (INCLUDING KITCHENETTE
 107) ARE TO COMPLY WITH FBC11-4.24.
 PROVIDE A DETAIL.INCLUDE KNEE
 CLEARANCE UNDER THE SINK AT 107.
  
 2.)TEST REPORT AND FLORIDA OR LOCAL
 PRODUCT APPROVAL REQUIRED FOR THE NEW
 EXTERIOR DOOR.
 WWW.FLORIDABUILDING.ORG.
  
 3.)WHAT WAS IN THE NEW AREA
 PREVIOUSLY?CHANGE OF USE REQUIRES
 IMPACT FEE ASSESSMENT, 233-5025.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-03-25 Cont ID  
Sent By dpalmer Date 2005-03-25 Time 11:07 Rev Time 0.30
Received By dpalmer Date 2005-03-25 Time 11:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-01 Cont ID  
Sent By dpalmer Date 2005-03-01 Time 07:33 Rev Time 0.25
Received By dpalmer Date 2005-03-01 Time 07:22 Sent To  
Notes
2005-03-01 00:00:00********* UNSAT 2ND REVIEW *********
  
 PLEASE SEE SOME ITEMS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE ONE NEW COMMENT.
  
 1)NOTE: NOTE #1 NO, PLEASE SEE REDLINED
 PLANS FOR ITEMS NOT CIRCUITED.
 PLEASE SEE RESPONSE LETTER MENTIONS TO
 SEE REVISED "A-1"??
  
 2)NOTE: NOTE #2 NO, PLEASE SEE 600.5 FOR
 REQUIRED SIGN CIRCUIT. NO OTHER ITEMS
 INCLUDING "SHOW WINDOW" RECEPTS ARE
 PERMITTED ON SIGN CIRCUIT.
 PLEASE SEE RESPONSE LTR MENTIONS TO SEE
 A-1?
  
 3)NOTE: NOTE #3, OK, PANELS HAVE BEEN
 RE-LABLED ON PLANS.
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 OK.
  
 NEW NOTE:
  
 1)NOTE: PLEASE SEE HAND WRITTEN ITEMS ON
 PLANS WHICH ARE SIGNED, DATED AND SEALED
 BY AN ARCH /ENG ARE NOT PERMITTED.
 FS 481.221, 471.025
  
 2)NOTE: PLEASE SEE A NOTTICE TO FS
 553.80(2)(B) IS GIVEN AT THIS TIME, THIS
 IS ONLY A NOTICE.
  
  
 PLEASE SEE ONE SET OF PLANS HAVE THE
 ABOVE ITEMS REDLINED FOR AREAS OF NOTES.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-02-01 Cont ID  
Sent By dpalmer Date 2005-02-01 Time 09:29 Rev Time 0.25
Received By dpalmer Date 2005-02-01 Time 09:29 Sent To  
Notes
2005-02-01 00:00:00*****UNSAT *****
  
 1)NOTE: PLEASE SHOW CIRCUITING FOR
 LIGHTING IN FRONT TENANT SPACE.
  
 2)NOTE: PLEASE VERIFIFY SHOW WINDOW
 RECEPTS REQUIRED PER 210.62.
 RECEPTS ARE SHOWN ABOVE WINDOWS WHICH
 MENTIONS FOR SIGN? PLEASE SEE 600.5, NO
 OTHER MAY BE ON SIGN CIRCUIT.
  
 3)NOTE: PLEASE SHOW LOCATION OF NEW
 PANEL "B", THIS COULD NOT BE LOCATED ON
  
 PLANS.
  
 4)NOTE: PLEASE SEE CONDUIT SIZES ON
 PANEL SCHEDULE FOR FEEDERS AND CORRELATE
 WITH RISER DIAGRAM.
 215.5
  
 5)NOTE: PLEASE SEE LOAD CALCULATIONS ARE
 NOT SHOWN FOR NEW PANEL "B", ONLY SHOWS
 CONNECTED LOAD.
 PLEASE VERIFY CONTINUOUS LOADS AT 125%.
 215.03,230.42 ETC.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE BE AWARE OF ANY POSSIBLE COMMENTS
 FROM OTHER REVIEWERS WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-02-09 Cont ID  
Sent By mcarsill Date 2005-02-09 Time 16:31 Rev Time 0.00
Received By mcarsill Date 2005-02-09 Time 16:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-24 Cont ID  
Sent By adarroug Date 2005-03-24 Time 09:25 Rev Time 0.00
Received By adarroug Date 2005-03-24 Time 09:25 Sent To  
Notes
2005-03-24 00:00:00TO "COMM" BD#60

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 11:26 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 11:26 Sent To  
Notes
2005-02-28 00:00:00TO "COMM" BD#29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-26 Cont ID  
Sent By mjacobs Date 2005-02-17 Time 16:41 Rev Time 0.00
Received By kstevens Date 2005-01-26 Time 11:21 Sent To  
Notes
2005-01-26 00:00:00TO "COMM BD#26"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-02-07 Cont ID  
Sent By pkrauss Date 2005-02-07 Time 14:56 Rev Time 0.20
Received By pkrauss Date 2005-02-07 Time 14:49 Sent To  
Notes
2005-02-07 00:00:00NO MECHCANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
 PLEASE PROVIDE PLANS, EQUIPMENT
 SCHEDULE, AND ENERGY CALCULATIONS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-03-16 Cont ID  
Sent By kstevens Date 2005-03-16 Time 17:25 Rev Time 0.50
Received By kstevens Date 2005-03-16 Time 17:25 Sent To  
Notes
2005-03-16 00:00:00PLUMBING FIXTURES SHALL BE INSTALLED ON
 EXISTING PLUMBING STUBOUTS PER
 APPLICATION. ALL ACCESSIBLITY
 REQUIREMENTS ADDRESSED, KSTEVENS

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-02-17 Cont ID  
Sent By kstevens Date 2005-02-17 Time 16:27 Rev Time 0.82
Received By kstevens Date 2005-02-17 Time 16:27 Sent To  
Notes
2005-02-17 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 1) SUBMIT DETAILS FOR THE FOLLOWING
 ACCESSIBILITY REQUIREMENTS:
 A) EXPOSED PIPES AND SURFACES 11-4.19.4
 (BELOW FOR KITCHENETTE SINK)
 B) HEIGHT 11-4.24.2
 C) KNEE CLEARANCE 11-4.24.3
 D) SINK DEPTH 11-4.24.4
 E) CLEAR FLOOR SPACE 11-4.24.5 (FORWARD
 APPROACH REQUIRED, MAXIMUM 19"
 UNDERNEATH THE SINK.
 F) EXPOSED PIPES AND SURFACES 11-4.24.6
 G) FAUCETS 11-4.24.7
 H) SHOW A 5' TURNING AREA FOR EGRESS IN
 KITCHENETTE
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]