| Plan Review Stops For Permit 05011266 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-03-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-03-25 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-03-25 |
Time |
13:26 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-03-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-03-09 |
Time |
11:43 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-03-09 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2005-03-09 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)HAVE THE PLANS STAMPED FOR IMPACT | | | FEE REVIEW, 233-5025. | | | | | | 2.)THE TEST REPORT SUBMITTED FOR THE | | | EXTERIOR DOOR IS NOT THE TEST REPORT ON | | | THE WEBSITE FOR FL1589.PLEASE PROVIDE | | | TWO COPIES OF THE TEST REPORT FROM THE | | | STATE WEBSITE AND FLORIDA STATE PRODUCT | | | APPROVAL.WWW.FLORIDABUILDING.ORG |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-01-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-01-31 |
Time |
16:35 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-01-31 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2005-01-31 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THE SINKS (INCLUDING KITCHENETTE | | | 107) ARE TO COMPLY WITH FBC11-4.24. | | | PROVIDE A DETAIL.INCLUDE KNEE | | | CLEARANCE UNDER THE SINK AT 107. | | | | | | 2.)TEST REPORT AND FLORIDA OR LOCAL | | | PRODUCT APPROVAL REQUIRED FOR THE NEW | | | EXTERIOR DOOR. | | | WWW.FLORIDABUILDING.ORG. | | | | | | 3.)WHAT WAS IN THE NEW AREA | | | PREVIOUSLY?CHANGE OF USE REQUIRES | | | IMPACT FEE ASSESSMENT, 233-5025. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-03-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-03-25 |
Time |
11:07 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-03-25 |
Time |
11:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-03-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-03-01 |
Time |
07:33 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-03-01 |
Time |
07:22 |
Sent To |
|
|
| Notes |
| 2005-03-01 00:00:00 | ********* UNSAT 2ND REVIEW ********* | | | | | | PLEASE SEE SOME ITEMS FROM PREVIOUS | | | REVIEW STILL NEED TO BE ADDRESSED. | | | PLEASE ALSO SEE ONE NEW COMMENT. | | | | | | 1)NOTE: NOTE #1 NO, PLEASE SEE REDLINED | | | PLANS FOR ITEMS NOT CIRCUITED. | | | PLEASE SEE RESPONSE LETTER MENTIONS TO | | | SEE REVISED "A-1"?? | | | | | | 2)NOTE: NOTE #2 NO, PLEASE SEE 600.5 FOR | | | REQUIRED SIGN CIRCUIT. NO OTHER ITEMS | | | INCLUDING "SHOW WINDOW" RECEPTS ARE | | | PERMITTED ON SIGN CIRCUIT. | | | PLEASE SEE RESPONSE LTR MENTIONS TO SEE | | | A-1? | | | | | | 3)NOTE: NOTE #3, OK, PANELS HAVE BEEN | | | RE-LABLED ON PLANS. | | | | | | 4)NOTE: NOTE #4 OK. | | | | | | 5)NOTE: NOTE #5 OK. | | | | | | NEW NOTE: | | | | | | 1)NOTE: PLEASE SEE HAND WRITTEN ITEMS ON | | | PLANS WHICH ARE SIGNED, DATED AND SEALED | | | BY AN ARCH /ENG ARE NOT PERMITTED. | | | FS 481.221, 471.025 | | | | | | 2)NOTE: PLEASE SEE A NOTTICE TO FS | | | 553.80(2)(B) IS GIVEN AT THIS TIME, THIS | | | IS ONLY A NOTICE. | | | | | | | | | PLEASE SEE ONE SET OF PLANS HAVE THE | | | ABOVE ITEMS REDLINED FOR AREAS OF NOTES. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | INSERT ONLY NEW SHEETS INTO TWO COMPLETE | | | SETS FOR REVIEW AND STAMPING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-02-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-02-01 |
Time |
09:29 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-02-01 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2005-02-01 00:00:00 | *****UNSAT ***** | | | | | | 1)NOTE: PLEASE SHOW CIRCUITING FOR | | | LIGHTING IN FRONT TENANT SPACE. | | | | | | 2)NOTE: PLEASE VERIFIFY SHOW WINDOW | | | RECEPTS REQUIRED PER 210.62. | | | RECEPTS ARE SHOWN ABOVE WINDOWS WHICH | | | MENTIONS FOR SIGN? PLEASE SEE 600.5, NO | | | OTHER MAY BE ON SIGN CIRCUIT. | | | | | | 3)NOTE: PLEASE SHOW LOCATION OF NEW | | | PANEL "B", THIS COULD NOT BE LOCATED ON | | | | | | PLANS. | | | | | | 4)NOTE: PLEASE SEE CONDUIT SIZES ON | | | PANEL SCHEDULE FOR FEEDERS AND CORRELATE | | | WITH RISER DIAGRAM. | | | 215.5 | | | | | | 5)NOTE: PLEASE SEE LOAD CALCULATIONS ARE | | | NOT SHOWN FOR NEW PANEL "B", ONLY SHOWS | | | CONNECTED LOAD. | | | PLEASE VERIFY CONTINUOUS LOADS AT 125%. | | | 215.03,230.42 ETC. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE BE AWARE OF ANY POSSIBLE COMMENTS | | | FROM OTHER REVIEWERS WHICH MAY HAVE AN | | | AFFECT ON ELECTRICAL PLANS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2005-02-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-02-09 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-02-09 |
Time |
16:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-03-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-24 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-24 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2005-03-24 00:00:00 | TO "COMM" BD#60 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-02-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-28 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-28 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2005-02-28 00:00:00 | TO "COMM" BD#29 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-01-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-02-17 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2005-01-26 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2005-01-26 00:00:00 | TO "COMM BD#26" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-02-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-02-07 |
Time |
14:56 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2005-02-07 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2005-02-07 00:00:00 | NO MECHCANICAL PLANS OR CONTRACTOR | | | INDICATED WITH PERMIT APPLICATION. | | | PLEASE PROVIDE PLANS, EQUIPMENT | | | SCHEDULE, AND ENERGY CALCULATIONS WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2005-03-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-03-16 |
Time |
17:25 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-03-16 |
Time |
17:25 |
Sent To |
|
|
| Notes |
| 2005-03-16 00:00:00 | PLUMBING FIXTURES SHALL BE INSTALLED ON | | | EXISTING PLUMBING STUBOUTS PER | | | APPLICATION. ALL ACCESSIBLITY | | | REQUIREMENTS ADDRESSED, KSTEVENS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-02-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-02-17 |
Time |
16:27 |
Rev Time |
0.82 |
| Received By |
kstevens |
Date |
2005-02-17 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2005-02-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | | | | 1) SUBMIT DETAILS FOR THE FOLLOWING | | | ACCESSIBILITY REQUIREMENTS: | | | A) EXPOSED PIPES AND SURFACES 11-4.19.4 | | | (BELOW FOR KITCHENETTE SINK) | | | B) HEIGHT 11-4.24.2 | | | C) KNEE CLEARANCE 11-4.24.3 | | | D) SINK DEPTH 11-4.24.4 | | | E) CLEAR FLOOR SPACE 11-4.24.5 (FORWARD | | | APPROACH REQUIRED, MAXIMUM 19" | | | UNDERNEATH THE SINK. | | | F) EXPOSED PIPES AND SURFACES 11-4.24.6 | | | G) FAUCETS 11-4.24.7 | | | H) SHOW A 5' TURNING AREA FOR EGRESS IN | | | KITCHENETTE | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|