Plan Review Details - Permit 05011231
Plan Review Stops For Permit 05011231
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-07-18 Cont ID  
Sent By jwitmer Date 2005-07-18 Time 07:49 Rev Time 1.10
Received By jwitmer Date 2005-07-18 Time 07:49 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-01 Cont ID  
Sent By jwitmer Date 2005-06-01 Time 07:32 Rev Time 2.22
Received By jwitmer Date 2005-06-01 Time 06:58 Sent To  
Notes
2005-06-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05011231
 ADD: 7719 S DIXIE/7785
 CONT: PLAN REVIEW
 TEL: (954)426-5144
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION:DENIED
  
 PLANS APPEAR TO BE CODE COMPLIANT,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-31 Cont ID  
Sent By jwitmer Date 2005-01-31 Time 12:36 Rev Time 3.33
Received By jwitmer Date 2005-01-31 Time 12:35 Sent To  
Notes
2005-01-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05011231
 ADD:7785 S DIXIE HWY
 CONT:PLAN REVIEW/PALM BEACH 2000
 TEL: (954)927-4885
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) CORRECT ADDRESS ON PLANS, ELEVATIONS
 TO 7785 FOR THE UNIT NUMBER, THE SITE
 ADDRES IS 7719 S DIXIE.
  
 3) F102.1* FIRE DISTRICT, NO TYPE VI
 CONSTRUCTION IS ALLOWED IN THE FIRE
 DISTRICT. NO COMBUSTIBLE WALLS, SEE
 PARAPET WALLS, AND WALL SECTIONS OF
 TOWER.
 SHEET A-9 THROU A-12 INDICATE THE USE OF
  
 RIB LATH FASTENING AS PER NOTE# 2,
 CORRECT SEE:2504.2.2 INSTALLATION
 OF EXTERIOR LATHING AND FRAMING SHALL
 COMPLY WITH ASTM C-1063. COMPLY WITH
 VERTICAL & HORIZONTAL FASTENING FOR RIB
 LATH.
  
 4) SHEET A-13 DETAIL# 3, INDICATES THE
 USE OF VINYL SOFFIT VENT AT 2 5/8" WIDE
 STRIP. PROVIDE CALCULATION SHOWING
 COMPLIANCE WITH 2309.7.1. INDICATE HOW
 MUCH OF THE VENT IS OPEN PER FOOT.
  
 5) SHEET A-14 DETAILS 1&2 REVISE:
 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 6) SAME DETAILS AS LISTED ABOVE, THE
 COMMENT THAT THE TAPCON IS TO A MINIMUM
 OF 3" INTO CONCRETE CORRECT? THE TAPCON
 HAS TO TRAVEL A 1 1/4" THROUGH THE BLOCK
 SHELL BEFORE HITTING THE 3,000 PSI
 CONCRETE?
  
 7) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 WWW.FLORIDABUILDING.ORG
  
 8)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) SLIDING WINDOW UNIT
 B) ARCHED WINDOWS
 C) TRUSS ANCHORS
  
 9)STORM SHUTTERS FL BLD CODE 2001
 SECTION 103.6, 1606.1.4, 1707.4 &
 3401.7.2.4. PROCEDURES: 1(B) A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING
 REQUIREMENTS, WALL PRES- SURE ZONES,
 SLAT TYPES, ETC., SHALL BE SUBMITTED AT
 TIME OF PERMIT APPLICATION TO FACILITATE
 PLAN REVIEW AND PERMIT ISSUANCE.
 HIGHLIGHT THE PRODUCT APPROVAL
 INDICATING THE TYPE OF DETAIL USED AND
 THE TYPE OF FASTENER WITH TYPE OF
 MATERIAL OF THE STRUCTURE.
  
 10) VALUE LOW ON THE PERMIT, CALCULATED
 VALUE IS $304,406.00.
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-14 Cont ID  
Sent By dpalmer Date 2005-12-14 Time 11:41 Rev Time 0.00
Received By dpalmer Date 2005-12-14 Time 11:29 Sent To  
Notes
2005-12-14 00:00:00REDLINED 600.5
  
 VOIDED SHEETS IN FILE SET OK, VOIDED IN
 ERROR, RE-SIGNED AND DATED PLANS.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-02-09 Cont ID  
Sent By dpalmer Date 2005-02-09 Time 17:34 Rev Time 0.50
Received By dpalmer Date 2005-02-09 Time 17:30 Sent To  
Notes
2005-02-09 00:00:00REDLINED CORRECTION RO ART 210.8(B)3)
 SHOWN AS 210.8(8)3) ON PLANS.
  
 PLANS OK, STAMPED.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-01-31 Cont ID  
Sent By mamini Date 2005-01-31 Time 09:11 Rev Time 1.00
Received By mamini Date 2005-01-31 Time 09:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-03-16 Cont ID  
Sent By mwennerg Date 2005-03-16 Time 15:29 Rev Time 0.00
Received By mwennerg Date 2005-03-16 Time 15:28 Sent To  
Notes
2005-03-16 00:00:001) PLEASE BE ADVISED THAT ANY DOOR IN A
 MEANS OF EGRESS WITH AN OCCUPANT LOAD OF
 GREATER THAN 100 SHALL BE PROVIDED WITH
 PANIC HARDWARE UNLESS OTHERWISE
 PERMITTED.
  
 2) THE ADDRESS NUMBER MUST BE DISPLAYED
 ON THE FRONT OF THE BUILDING WITH
 NUMBERS AT LEAST 6" IN HEIGHT
 CONTRASTING TO THE BACKGROUND.
  
  
 MIKE WENNERGREN, ACTING CAPTAIN
 WPBFR(561) 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-11-30 Cont ID  
Sent By adarroug Date 2005-11-30 Time 13:42 Rev Time 0.00
Received By adarroug Date 2005-11-30 Time 13:42 Sent To E
Notes
2005-11-30 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-11-17 Cont ID  
Sent By adarroug Date 2005-11-17 Time 16:41 Rev Time 0.00
Received By adarroug Date 2005-11-17 Time 16:41 Sent To P
Notes
2005-11-17 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 13:13 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 13:13 Sent To B
Notes
2005-07-07 00:00:00TO "JWITMER" DESK/FROM PLAN REVIEW TO
 PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-11 Cont ID  
Sent By shill Date 2005-06-11 Time 10:29 Rev Time 0.00
Received By shill Date 2005-06-11 Time 10:29 Sent To  
Notes
2005-06-11 00:00:00ON INCOMING DESK
 CHECK W/JW BEFORE CALLING CONTR FOR
 PICKUP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 14:42 Rev Time 0.00
Received By shill Date 2005-06-10 Time 14:42 Sent To P
Notes
2005-06-10 00:00:00TO PAUL S DESK (PLUMBING LAST REVIEW)
 TAKEN OFF OF BOARD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-17 Cont ID  
Sent By adarroug Date 2005-05-17 Time 14:18 Rev Time 0.00
Received By adarroug Date 2005-05-17 Time 14:18 Sent To  
Notes
2005-05-27 00:00:00TO "COMM" BD#54
2005-05-17 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-26 Cont ID  
Sent By mjacobs Date 2005-03-16 Time 16:42 Rev Time 0.00
Received By adarroug Date 2005-01-26 Time 07:42 Sent To  
Notes
2005-01-26 00:00:00TO "COMM BD#56

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-02-10 Cont ID  
Sent By pkrauss Date 2005-02-10 Time 14:01 Rev Time 2.00
Received By pkrauss Date 2005-02-10 Time 11:35 Sent To  
Notes
2005-02-10 00:00:00PLAN CHECK - PLANS INCLUDE HVAC, HOOD
 FIRE SUPPRESSION AND WALK-IN
 COOLER/FREEZER.ADDITIONAL PERMITS
 REQUIRED FOR THE HOOD, FIRE SUPPRESSION
 AND WALK-IN COOLER/FREEZER.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-12-12 Cont ID  
Sent By jleech Date 2005-12-12 Time 15:00 Rev Time 0.00
Received By jleech Date 2005-12-12 Time 15:00 Sent To  
Notes
2005-12-12 00:00:00GAS REVISION OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-11 Cont ID  
Sent By pschmitz Date 2005-06-11 Time 07:19 Rev Time 0.00
Received By pschmitz Date 2005-06-11 Time 07:19 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-02-22 Cont ID  
Sent By kstevens Date 2005-02-22 Time 10:56 Rev Time 4.50
Received By kstevens Date 2005-02-22 Time 09:01 Sent To  
Notes
2005-02-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) PLANS SHALL BE ROUTED TO FDBR,
 DIVISION OF BUSINESS REGULATION, HOTEL
 AND RESTURANT DIVISION FOR REVIEW.
 RESUBMIT WITH EACH SET OF PLANS STAMPED,
 AND WORK SHEETS ATTACHED. SECTION
 101.4.7.
 2) GREASE INTERCEPTORS SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE,
 WASTE ORD. #2838-96. (561) 837-4074 OR
 FAX (561) 659-7458. SUBMIT WORK SHEET
 FORM MR. COMPO WITH PLANS WHEN
 RESUBMITTING.
 3) SHT P-1 FLOOR PLAN FOR GREASE PIPING
 SHOWS THE FIRST FLOOR DRAIN AS "WC-3"
 NOT "FD" PLEASE CORRELATE RISER DIAGRAM
 AND FLOOR PLAN.
 4) SHT P-1 FLOOR PLAN AND GREASE PIPING
 ISOMETRIC. FS-1, (INDIRECT WASTE FROM
 ITEM #7) AND FD-2 SHALL CONNECT TO THE
 VENTED DRAIN LINE SEPARATELY. SECTION
 912.2.4.
 5) SHT P-2 SECTION 606.1(4) FULL OPEN
 VALVES ARE REQUIRED ON THE TOP OV EVERY
 WATER DOWN-FEED PIPE.
 6) SHT P-2 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PLANS/PERMIT:
 A. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. THESE
 VALVES AND UNIONS SHALL BE SHOWN ON THE
 GAS RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-03-01 Cont ID  
Sent By mmclean Date 2005-03-01 Time 09:21 Rev Time 0.00
Received By mmclean Date 2005-03-01 Time 09:21 Sent To  
Notes
2005-03-01 00:00:00JOSH LONG, SENIOR PLANNER 822-1449
 APPROVED PLANS.