| 2005-02-08 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05011202 |
| | ADD: 6450 SPARROW HAWK DRIVE |
| | CONT: RIF GROUP |
| | TEL: (561)239-5790 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | FL S S 481.219(2)(3) THE HEADER STRIP |
| | FOR THE ARCHITECT FIRM JEFFERY |
| | SILBERSTEIN ARCHITECT & ASSOCIATES, |
| | INC. |
| | DOES NOT HAVE THE FIRMS CERTIFICATE OF |
| | AUTHORIZATION IN THE HEADERSTRIP. |
| | |
| | 2) SHEET A-2.0 MASTER BEDROOM EGRESS |
| | WINDOW# 10 IS A FIXED GLASS PANEL. THE |
| | ADJOINING WINDOW# 3 MEETS THE EGRESS |
| | REQUIREMENTS, CORRECT. |
| | |
| | 3) SHEET A-2.0 ALSO INDICATES A DEN ON |
| | THE ZERO LOTLINE SIDE OF THE HOUSE, |
| | THERE IS ALSO A ATRIUM AND EXTERIOR |
| | DOORWAY, THE DEN CANBE USED FOR A |
| | SLEEPING ROOM REQUIRING A SECOND MEANS |
| | OF EGRESS THROUGH THE ATRIUM, NOTHING ON |
| | THE SURVEY INDICATES A ANY ACCESS/EGRESS |
| | EASEMENTS ON THE ZEERO LOT LINE SIDE OF |
| | THE HOUSE. THE ELECTRICAL PLAN ALSO |
| | INDICATES SMOKE DETECTORS AND ARK FAULT |
| | CIRCUIT BREAKERS WHICH ARE REQUIRED FOR |
| | |
| | BEDROOMS OR SLEEPING ROOMS. |
| | IF NOT USSED AS A SLEEPING ROOM THE |
| | SURVEY DOESN'T INDICATE A ACCESS |
| | EASEMENT FOR MAINTENCE OF THE ATRIUM, IN |
| | EITHER CASE A ACCESS/EGRESS EASEMENT |
| | SHALL BE REQUIRED. |
| | |
| | 4)ONLY ONE SOILS REPORT SIGNED AND |
| | SEALED THE SECOND IS A COPY, |
| | PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 5) THE PRODUCT SUBMITTALS FOR WINDOWS |
| | AND GLAZED DOORS INDICATES "NO LARGE |
| | MISSLE TESTING". FL BLD CODE |
| | 1606.1.5: COMPONENTS & CLADDING, PROVIDE |
| | 2 COPIES(3 IF THRESH- OLD OR RESIDENT |
| | INSPECTOR) OF PRODUCT TESTING |
| | REPORTS,MISSING REPORTS ARE AS FOLLOWS: |
| | A) STORM SHUTTERS |
| | PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| | FOR ALL NON-IMPACT GLAZING.FBC |
| | 1606.1.4. |
| | |
| | 6)FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE.SEE EXAMPLE SHEET. |
| | |
| | 7)THE FRONT ENTRY DOOR INDICATES |
| | GLAZING, THE PRODUCT APPROVAL SUBMITTED |
| | FOR THIS DOOR INDICATES STORM SHUTTERS |
| | ARE REQUIRED.FBC 1005.4.5 (GLITCH |
| | AMENDMENTS JULY 1, 2003) REQUIRES AT |
| | LEAST ONE MEANS OF ESCAPE FROM A |
| | DWELLING WHEN SHUTTERED FOR IMPACT |
| | PROTECTION. THE MEANS OF ESCAPE SHALL BE |
| | WITHIN THE FIRST FLOOR OF THE DWELLING |
| | AND CAN NOT BE LOCATED IN A GARAGE. |
| | OCCUPANTS IN ANY PART OF THE DWELLING |
| | SHALL HAVE ACCESS TO IT WITHOUT HAVING |
| | TO PASS THROUGH A LOCKABLE DOOR NOT |
| | UNDER THEIR CONTROL. INDICATE HOW |
| | COMPLIANCE WILL BE ACHIEVED. |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |