Plan Review Details - Permit 05011136
Plan Review Stops For Permit 05011136
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-11 Cont ID  
Sent By rmcdouga Date 2005-08-11 Time 06:51 Rev Time 0.00
Received By rmcdouga Date 2005-08-11 Time 06:51 Sent To  
Notes
2005-08-11 00:00:00PROVISO
  
 A SEPARATE PERMIT IS REQUIRED FOR THE
 STORM PANELS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-02-14 Cont ID  
Sent By lsmith Date 2005-02-14 Time 13:41 Rev Time 4.00
Received By lsmith Date 2005-02-14 Time 13:41 Sent To  
Notes
2005-02-14 00:00:00BUILDING PLAN REVIEW:FAILED
  
 1. STORM PANEL PERMIT TO BE APPLIED FOR
 SEPARATELY.
  
 2. TOTAL UNDER AIR 3170: IMPACT FEES
 PAID ON 2900SQ. FT. TAKE PLANS BACK TO
 PBC FOR CORRECT IMPACT FEE & RESTAMPED.
  
 3. FLORIDA ENERGY EFFECIENCY CODE HAS
 2900' CONDITIONED AREA. SHOULD BE 3170.
 CORRECT A/C AREA & UNDER ATTIC AREA ON
 FORM 600A.
  
 4. ADDITIONAL FEES OF $96.42 DUE BEFORE
 PERMIT CAN BE PRINTED.
  
 5. SUBMIT A COPY OF THE RECORDED NOTICE
 OF COMMENCEMENT BEFORE A PERMIT IS
 ISSUED.
  
 6. SUBMIT THE UL LISTING FOR THE WOOD
 BURNING FIREPLACE.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-01-26 Cont ID  
Sent By btrobaug Date 2005-01-26 Time 16:48 Rev Time 0.75
Received By btrobaug Date 2005-01-26 Time 15:57 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2006-02-16 Time 10:36 Sent To  
Notes
2006-02-16 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 10:45 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 10:45 Sent To M
Notes
2005-07-28 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-26 Cont ID  
Sent By mjacobs Date 2005-01-26 Time 10:55 Rev Time 0.00
Received By mjacobs Date 2005-01-26 Time 10:55 Sent To E
Notes
2005-01-26 00:00:00TO "SFR" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-24 Cont ID  
Sent By mjacobs Date 2005-01-24 Time 13:28 Rev Time 0.00
Received By mjacobs Date 2005-01-24 Time 13:28 Sent To Z
Notes
2005-01-24 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-02-16 Cont ID  
Sent By tgordon Date 2006-02-16 Time 14:14 Rev Time 0.25
Received By tgordon Date 2006-02-16 Time 14:14 Sent To  
Notes
2006-02-16 00:00:00REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-03 Cont ID  
Sent By prafter Date 2005-08-02 Time 09:58 Rev Time 0.00
Received By prafter Date 2005-08-03 Time 11:23 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-28 Cont ID  
Sent By pkrauss Date 2005-01-28 Time 13:48 Rev Time 0.35
Received By pkrauss Date 2005-01-28 Time 13:48 Sent To  
Notes
2005-01-28 00:00:00DENIED:
 ENERGY CALCULATIONS INDICATE EQUIPMENT
 AS A 11 SEER AND THE EQUIPMENT SCHEDULE
 ON PLAN SHEET M1 SHOWS SYSTEM 1 AS ONLY
 10.7 SEER.EQUIPMENT SHALL NOT BE LESS
 THAN WHAT THE ENERGY CALCS INDICATE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-02 Cont ID  
Sent By prafter Date 2005-08-03 Time 11:21 Rev Time 0.33
Received By jleech Date 2005-08-02 Time 12:00 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-02-04 Cont ID  
Sent By kstevens Date 2005-02-04 Time 12:54 Rev Time 0.50
Received By kstevens Date 2005-02-04 Time 12:54 Sent To B1
Notes
2005-02-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT 1.1 SANITARY RISER DIAGRAM SHALL
  
 REFLECT THE FLOOR PLAN. ALL OPTIONAL
 FIXTURES SHALL BE SHOWN AS EITHER BEING
 INSTALLED OR NOT. INDICATE ON THE FLOOR
 PLAN AND RISER DIAGRAM EXACTLY HOW THE
 HOUSE IS BEING BUILT, AND HOW THE PIPING
 WILL BE INSTALLED. SECTION 104.2.1.
 2) SHT 1.1 SANITARY RISER DIAGRAM, THE
 LAUNDRY TRAY SHALL NOT DRAIN THROUGH THE
 HORIZONTAL WET-VENT OF THE BATHROOM
 FIXTURES. SECTION 909.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-26 Cont ID  
Sent By mmclean Date 2005-01-26 Time 10:40 Rev Time 0.00
Received By mmclean Date 2005-01-26 Time 10:40 Sent To I
Notes
***NONE***