Plan Review Details - Permit 05011045
Plan Review Stops For Permit 05011045
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-29 Cont ID  
Sent By alange Date 2005-04-29 Time 09:27 Rev Time 0.50
Received By alange Date 2005-04-29 Time 09:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-04-26 Cont ID  
Sent By alange Date 2005-04-26 Time 09:05 Rev Time 0.66
Received By alange Date 2005-04-26 Time 09:05 Sent To  
Notes
2005-04-26 00:00:00NOTES FROM LAST REVIEW NOT ADDRESSED.
  
  
 DENIED
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS ARE REQUIRED FOR
 ROOFING, WINDOWS, EXTERIOR DOORS,
 IMPACT
 PROTECTION AND STRAPS AND TIE-DOWNS.
 SUBMIT TWO COPIES WITH QUALITY
 ASSURANCE
 WITH THE FOLLOWING ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.DESCRIPTION OF WORK ON APPLICATION
 DOES NOT SHOW A ROOM ADDITION.
 SQUARE FOOTAGE WAS CORRECTED.
 VALUATION HAS BEEN ADJUSTED ACCORDING
 SBCCI BUILDING VALUATION DATA. THE
 REVISED VALUE IS $39,037.44.
 ADDITIONAL
 PERMIT FEES ARE DUE.
  
 5.SAFTEY GLAZING REQUIRED FOR WINDOW
 AT TUB LOCATON.FBC 2405.2.1
  
 6.SUBMIT 2 COPIES OF ENERGY CALCS.
  
 7.WHEN REPAIR AND ALTERATIONS
 AMOUNTING TO MORE THAN 50% OF THE VALUE
 OF THE EXISTING BUILDING ARE MADE
 DURING
 ANDY 12 MONTH PERIOD, THE BUILDING
 SHALL
 BE MADE TO CONFORM TO THE REQUIREMENTS
 FOR A NEW BUILDING.FBC3401.7.2.6
  
 8.BEDROOM WINDOWS ADJACENT TO ROOM
 ADDITION SHALL COMPLY WITH FBC 1005.4.4
 SHOW SIZE AND TYPE OF WINDOW.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-08 Cont ID  
Sent By prafter Date 2005-04-07 Time 10:46 Rev Time 1.66
Received By alange Date 2005-02-08 Time 08:50 Sent To E
Notes
2005-02-08 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF
 COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST
 BE
 RE-RECORDED IF THE DESCRIBED
 IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS ARE REQUIRED FOR
 ROOFING, WINDOWS, EXTERIOR DOORS,
 IMPACT
 PROTECTION AND STRAPS AND TIE-DOWNS.
 SUBMIT TWO COPIES WITH QUALITY
 ASSURANCE
 WITH THE FOLLOWING ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.DESCRIPTION OF WORK ON APPLICATION
 DOES NOT SHOW A ROOM ADDITION.
 SQUARE FOOTAGE WAS CORRECTED.
 VALUATION HAS BEEN ADJUSTED ACCORDING
 SBCCI BUILDING VALUATION DATA. THE
 REVISED VALUE IS $39,037.44.
 ADDITIONAL
 PERMIT FEES ARE DUE.
  
 5.SAFTEY GLAZING REQUIRED FOR WINDOW
 AT TUB LOCATON.FBC 2405.2.1
  
 6.SUBMIT 2 COPIES OF ENERGY CALCS.
  
 7.WHEN REPAIR AND ALTERATIONS
 AMOUNTING TO MORE THAN 50% OF THE VALUE
 OF THE EXISTING BUILDING ARE MADE
 DURING
 ANDY 12 MONTH PERIOD, THE BUILDING
 SHALL
 BE MADE TO CONFORM TO THE REQUIREMENTS
 FOR A NEW BUILDING.FBC3401.7.2.6
  
 8.BEDROOM WINDOWS ADJACENT TO ROOM
 ADDITION SHALL COMPLY WITH FBC 1005.4.4
 SHOW SIZE AND TYPE OF WINDOW.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2005-02-15 Cont ID  
Sent By dpalmer Date 2005-02-15 Time 10:47 Rev Time 0.00
Received By dpalmer Date 2005-02-15 Time 10:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-02-10 Cont ID  
Sent By btrobaug Date 2005-02-10 Time 16:10 Rev Time 0.50
Received By btrobaug Date 2005-02-10 Time 14:15 Sent To P
Notes
2005-02-10 00:00:00 
 SEE #7 ON BUILDING COMMENTS REGARDING
 FBC 3401.7.2.6. SHOW ALL ELECTRICAL
 DEVICES AND EQUIPMENT PER NEC 2002, AND
 RESUBMIT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-30 Cont ID  
Sent By adarroug Date 2005-03-30 Time 11:48 Rev Time 0.00
Received By adarroug Date 2005-03-30 Time 11:48 Sent To M
Notes
2005-03-30 00:00:00TO "PKRAUSS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-26 Cont ID  
Sent By mjacobs Date 2005-01-26 Time 06:59 Rev Time 0.00
Received By mjacobs Date 2005-01-26 Time 06:59 Sent To B
Notes
2005-01-26 00:00:00TO "MISC" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-21 Cont ID  
Sent By mjacobs Date 2005-01-21 Time 09:38 Rev Time 0.00
Received By mjacobs Date 2005-01-21 Time 09:38 Sent To Z
Notes
2005-01-21 00:00:00TO "Z' BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-04-07 Cont ID  
Sent By prafter Date 2005-02-14 Time 10:43 Rev Time 0.45
Received By prafter Date 2005-04-07 Time 10:46 Sent To P
Notes
2005-02-14 00:00:00NO A/C INFORMATION.
  
 A/C CONTRACTOR TO SUBMIT A/C
 PLANS/EQUIPMENT INFORMATION AND ENERGY
 FORMS AT A/C PERMIT TIME.
  
 PAT RAFTER 561/805/6728. IF THEIR ENY
 QUESTION PLEASE CALL.

Review Stop P PLUMBING
Rev No 2 Status N Date 2005-04-12 Cont ID  
Sent By jleech Date 2005-04-12 Time 16:31 Rev Time 0.33
Received By jleech Date 2005-04-12 Time 16:31 Sent To B
Notes
2005-04-12 00:00:00PER PLAN NO PLUMBING WORK IS BING DONE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-02-11 Cont ID  
Sent By kstevens Date 2005-02-11 Time 11:26 Rev Time 0.41
Received By kstevens Date 2005-02-11 Time 11:26 Sent To M
Notes
2005-02-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. THE FLOOR PLAN
 DOES NOT SHOW A WASH MACHINE. ALSO NO
 SINK IS SHOWN ON THE FLOOR PLAN FOR THE
 NEW ADDITION. PLEASE INDICATE WHERE THE
 WASH MACHINE AND THE SINK ARE LOCATED ON
 THE FLOOR PLAN. ONLY SHOW NEW WORK ON
 THE SANT. RISER DIAGRAM. SECTION
 104.2.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status N Date 2005-04-29 Cont ID  
Sent By alange Date 2005-04-29 Time 09:28 Rev Time 0.00
Received By alange Date 2005-04-29 Time 09:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-03-29 Cont ID  
Sent By mmclean Date 2005-03-29 Time 15:39 Rev Time 0.00
Received By mmclean Date 2005-03-29 Time 15:39 Sent To I
Notes
2005-03-29 00:00:00DENIED,
 1. CANNOT HAVE PORCH ENCROACHING IN
 FRONT SETBACK.MUST REMOVE FRONT PORCH
 OFF PLANS AND PERMIT APPLICATION.
 CALLED OWNER.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  

Review Stop Z ZONING
Rev No 1 Status F Date 2005-01-25 Cont ID  
Sent By mmclean Date 2005-01-25 Time 14:52 Rev Time 0.00
Received By mmclean Date 2005-01-25 Time 14:52 Sent To I
Notes
2005-01-25 00:00:00DENIED, NEED TO SHOW WORK ON SURVEY WITH
 SETBACKS.NEED CLARIFICATION FOR THE
 REAR FAMILY ADDITION.NO PERMIT WAS
 FOUND.