Plan Review Details - Permit 05010891
Plan Review Stops For Permit 05010891
Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-09-25 Cont ID  
Sent By pschmitz Date 2005-09-25 Time 09:37 Rev Time 0.00
Received By pschmitz Date 2005-09-25 Time 09:36 Sent To PC
Notes
2005-09-25 00:00:00GAS PLAN REVIEW: DENIED FBC 2001
 1)SEC 104 SEPERATE PERMIT REQUIRED.
 2)SEC 104.2 DRAWINGS SHALL BEAR THE NAME
 AND SIGNATURE OF THE DESIGN PERSON
 RESPONSIBLE.
 3)SHOW TOTAL BTU ON EX GAS SYSTEM.
 4)TYPE OF PIPING MATERIAL
 5) SHOW NATURAL GAS OR L P?
 6)GAS PSI
 7) TOTAL DEVELOPED LGTH.
 END OF COMMENTS, QUESTIONS
 CONTACT PAUL SCHMITZ 561-805-6692