| Plan Review Stops For Permit 05010891 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2005-09-25 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-09-25 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-09-25 |
Time |
09:36 |
Sent To |
PC |
|
| Notes |
| 2005-09-25 00:00:00 | GAS PLAN REVIEW: DENIED FBC 2001 | | | 1)SEC 104 SEPERATE PERMIT REQUIRED. | | | 2)SEC 104.2 DRAWINGS SHALL BEAR THE NAME | | | AND SIGNATURE OF THE DESIGN PERSON | | | RESPONSIBLE. | | | 3)SHOW TOTAL BTU ON EX GAS SYSTEM. | | | 4)TYPE OF PIPING MATERIAL | | | 5) SHOW NATURAL GAS OR L P? | | | 6)GAS PSI | | | 7) TOTAL DEVELOPED LGTH. | | | END OF COMMENTS, QUESTIONS | | | CONTACT PAUL SCHMITZ 561-805-6692 |
|
|