Plan Review Details - Permit 05010768
Plan Review Stops For Permit 05010768
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2005-01-18 Cont ID  
Sent By ptjomsto Date 2005-01-18 Time 14:43 Rev Time 0.00
Received By ptjomsto Date 2005-01-18 Time 14:43 Sent To  
Notes
2005-01-18 00:00:00EXT REQUIRED FOR 2450 PRESIDENTIAL WAY

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-02-02 Cont ID  
Sent By lmartine Date 2005-02-02 Time 16:47 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-25 Cont ID  
Sent By lmartine Date 2005-01-25 Time 14:56 Rev Time  
Received By lmartine Date   Time   Sent To  
Notes
2005-01-25 00:00:00 
  
 BUILDING REVIEW COMMENTS
 -------- ------ --------
  
  
  
 SUBMIT COMPLETE CALCULATIONS
 IN ACCORDANCE WITH ASCE-7 FOR WIND
 PRESSURE DESIGN FOR THE BUILDING.
  
  
 DESIGN PRESSURES SUBMITTED ARE NOT
 CORRECT, PLEASE SEE FBC 1606.1.1,
 EXCEP.#1
  
  
  
  
 L. MARTINEZ
 805-6710
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-18 Cont ID  
Sent By mjacobs Date 2005-01-18 Time 15:42 Rev Time 0.00
Received By mjacobs Date 2005-01-18 Time 15:42 Sent To B
Notes
2005-01-18 00:00:00TO "MISC" BOX.