Plan Review Details - Permit 05010748
Plan Review Stops For Permit 05010748
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-04-04 Cont ID  
Sent By nmccray Date 2005-03-29 Time 08:39 Rev Time 0.00
Received By nmccray Date 2005-03-29 Time 08:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-01-27 Cont ID  
Sent By nmccray Date 2005-01-27 Time 15:33 Rev Time 0.00
Received By nmccray Date 2005-01-27 Time 15:25 Sent To  
Notes
2005-01-27 00:00:00DENIED:
 1) PLEASE PROVIDE SHOP DRAWING OF THE
 FLOOR PLAN ON THE LOCATION OF THE
 DEVICES.
  
 2) NEW FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 3) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENTS
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 FINAL APPROVAL OF THE FIRE ALARM
 SYSTEM.
  
 4) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-09 Cont ID  
Sent By adarroug Date 2005-03-09 Time 10:05 Rev Time 0.00
Received By adarroug Date 2005-03-09 Time 10:05 Sent To FIRE
Notes
2005-03-09 00:00:00TO "F" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-18 Cont ID  
Sent By mjacobs Date 2005-01-18 Time 13:45 Rev Time 0.00
Received By mjacobs Date 2005-01-18 Time 13:45 Sent To FIRE
Notes
2005-01-18 00:00:00TO "FIRE" BOX.