| 2005-02-09 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) 713.13 F.S.A NOTICE OF |
| | COMMENCEMENT |
| | SHALL BE RECORDED AT PALM BEACH COUNTY |
| | COURTHOUSE AND A COPY SUBMITTED TO THIS |
| | OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| | BLANK FORMS ARE AVAILABLE FROM THIS |
| | OFFICE. |
| | NOTE: THE NOTICE OF COMMENCEMENT MUST |
| | BE |
| | RE-RECORDED IF THE DESCRIBED |
| | IMPROVEMENT |
| | OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| | 90 DAYS OF RECORDING. |
| | |
| | 2) SHEET FBC* 104.2.1SHEET S2.0, THE |
| | FOUNDATION PLAN STATES "F2 NEW FTG", AT |
| | GRID 2A, UNDER EXISTING W10X49 COLUMNS. |
| | HOW IS A NEW FOOTING TO BE CAST UNDER |
| | EXISTING COLUMNS.CROSS-SECTION 2/S3.0 |
| | DOES NOT SHOW HOW THIS IS TO BE |
| | ACHIEVED.ANNOTATE THE PLANS TO |
| | CLARIFY |
| | THE DESIGN INTENTION. |
| | |
| | 3) FBC* F102.2.7ARCHITECTURAL TRIM, |
| | ON |
| | BUILDINGS LOCATED IN THE FIRE DISTRICT, |
| | SHALL BE CONSTRUCTED OF APPROVED |
| | NON-COMBUSTIBLE MATERIALS OR FIRE |
| | RETARDANT TREATED WOOD.SHEET A-2.04 |
| | KEY NOTE 5, SHEET A-2.05 KEY NOTES 2 |
| | AND |
| | 7, SHEET A-5.01 KEY NOTES 2 AND 7, |
| | SHEET |
| | A-7.01 AND SHEET A-8.01 ALL MAKE |
| | REFERENCE TO FOAM MOLDINGS AND/OR EIFS |
| | SYSTEM.THESE ARE COMBUSTIBLE |
| | MATERIALS |
| | NOT PERMITTED IN THE FIRE DISTRICT. |
| | AMEND THE PLANS TO DEMONSTRATE |
| | COMPLIANCE. |
| | |
| | 4)) FBC* F102.2.4ROOF COVERINGS, ON |
| | BUILDINGS LOCATED IN THE FIRE DISTRICT, |
| | SHALL CONFORM TO THE REQUIREMENTS OF |
| | CLASS A OR B ROOF COVERINGS, AS DEFINED |
| | IN FBC 1505.ANNOTATE THE PLANS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 5) FBC 1601.1SHEET A-8.01.SUBMIT |
| | DETAILS TO SHOW THE METHOD OF ATTACHMENT |
| | FOR THE PROPOSED DECORATIVE MOLDINGS |
| | |
| | 6) SHEET S3.0, CROSS-SECTIONS 1 AND 2 |
| | HAVE NOTES STATING THAT THE METAL STUDS |
| | ARE ATTACCHED TO THE STRUCTURAL STEEL |
| | USING 0.145" DIA PDF.SHOULD THIS BE |
| | PAF (POWDER ACTUATED FASTENERS) AS |
| | LISTED ON SHEET S2.0 STRUCTURAL |
| | ABBREVIATIONS?IF NOT, ANNOTATE THE |
| | PLANS TO CLARIFY THE TYPE OF FASTENER TO |
| | BE USED. |
| | |
| | 7) SUBMIT PRODUCT APPROVALS FOR: |
| | - NEW ROOFING SYSTEM |
| | - NEW ALUMINUM STOREFRONT |
| | - NEW STOREFRONT DOORS (INCLUDING |
| | |
| | AUTOMATIC OPENING DOORS, IF |
| | DIFFERENT). |
| | NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| | EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| | SITE-SPECIFIC PRODUCT APPROVAL.THE |
| | SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| | PRODUCT APPROVAL NUMBER (FL###), |
| | AVAILABLE FROM THE DEPT OF COMMUNITY |
| | AFFAIRS PRODUCT APPROVAL WEBSITE |
| | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| | (IF YOU FIND THAT THE QUOTED WEB PAGE |
| | IS |
| | NO LONGER AVAILABLE, PLEASE INFORM THE |
| | PLAN REVIEWER) |
| | THE PRODUCT APPROVAL SHEETS SHALL BE |
| | MARKED, AS APPROPRIATE, TO IDENTIFY |
| | WHICH PRODUCT OPTIONS/MATERIALS/SIZES |
| | ARE TO BE USED. |
| | |
| | 8) FBC 3502SHEET S2.0, CONCRETE AND |
| | REINFORCING NOTE C1 REFERS TO ACI |
| | 318-99.FLORIDA BUILDING CODE CITES ACI |
| | 318-02 AS THE REFERENCED VERSION OF THAT |
| | STANDARD.AMEND THE NOTE. |
| | |
| | 9) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| | WHICH REQUIRES NEW PLANS IN ORDER TO |
| | ADDRESS THE ABOVE COMMENTS, THE OLD |
| | SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| | REMAINING OLD SHEETS, TO FORM A SET OF |
| | 'OLD/VOID SHEETS', FOR COMPARISON OF |
| | REVISIONS WHEN REVIEWING THE RESUBMITTED |
| | PLANS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |