Plan Review Details - Permit 05010679
Plan Review Stops For Permit 05010679
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-01-27 Cont ID  
Sent By jwitmer Date 2005-01-27 Time 12:42 Rev Time 0.55
Received By jwitmer Date 2005-01-27 Time 12:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2005-10-14 Cont ID  
Sent By btrobaug Date 2005-05-06 Time 13:28 Rev Time 0.50
Received By btrobaug Date 2005-05-06 Time 12:17 Sent To PC
Notes
2005-10-14 00:00:00 
 NEED 2ND SET OF SPECS./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-01-24 Cont ID  
Sent By btrobaug Date 2005-01-24 Time 16:15 Rev Time 0.50
Received By btrobaug Date 2005-01-24 Time 16:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-04-18 Cont ID  
Sent By mwennerg Date 2005-04-18 Time 13:52 Rev Time 0.00
Received By mwennerg Date 2005-04-18 Time 13:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-02-08 Cont ID  
Sent By mcarsill Date 2005-02-08 Time 15:55 Rev Time 0.00
Received By mcarsill Date 2005-02-08 Time 15:55 Sent To  
Notes
2005-02-08 00:00:001. PLEASE PROVIDE DETAILS FOR
 GENERATOR.
  
 2. PLEASE PROVIDE CLEARANCES FROM
 THE GENERATOR EXHAUST TO ANY
 DOORS, WINDOWS, INTAKES, EXHAUSTS, ETC.
  
 3. NO FUMES CAN RE-ENTER THE
 BUILDING.
  
 4. PLEASE ILLUSTRATE ALL PROPERTY
 LINES, ETC.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 15:56 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 15:56 Sent To E
Notes
2005-07-07 00:00:00TO "BTROBAUG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-11 Cont ID  
Sent By ebowers Date 2005-05-19 Time 12:34 Rev Time 0.00
Received By adarroug Date 2005-04-11 Time 16:12 Sent To  
Notes
2005-04-11 00:00:00TO "COMM" BD#49

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-21 Cont ID  
Sent By mjacobs Date 2005-01-21 Time 08:45 Rev Time 0.00
Received By mjacobs Date 2005-01-21 Time 08:45 Sent To  
Notes
2005-01-21 00:00:00TO "COMM BD#9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-14 Cont ID  
Sent By mjacobs Date 2005-01-14 Time 13:32 Rev Time 0.00
Received By mjacobs Date 2005-01-14 Time 13:32 Sent To Z
Notes
2005-01-14 00:00:00TO " Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-05-05 Cont ID  
Sent By pkrauss Date 2005-05-05 Time 06:47 Rev Time 0.40
Received By pkrauss Date 2005-05-05 Time 06:46 Sent To  
Notes
2005-05-05 00:00:00NEW OFIC 100KW 120/208V 3P, 4W GENERATOR
 (OFIC) WITH 240 GALLON DOUBLE WALL
 SUBBASE UL LISTED DIESEL FUEL TANK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-28 Cont ID  
Sent By pkrauss Date 2005-01-28 Time 07:07 Rev Time 0.50
Received By pkrauss Date 2005-01-28 Time 06:39 Sent To  
Notes
2005-01-28 00:00:00DENIED:
 1.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE GENERATOR.
  
 2.PLAN INDICATES GENERATOR ON THE
 SOUTH SIDE OF THE BUILDING.PLEASE
 PROVIDE INFORMATION ON CLEARANCE TO
 OPENINGS (DOORS, WINDOWS, FRESH AIR
 INTAKES, ETC).PER NFPA 110, 7.10.2,
 EXHAUST SHALL TERMINATE IN SUCH A MANNER
 THAT TOXIC FUMES CANNOT REENTER A
 BUILDING STRUCTURE.
  
 3.PLEASE INDICATE WHAT WILL BE TIED
 INTO THE EMERGENCY POWER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-05-19 Cont ID  
Sent By ebowers Date 2005-05-19 Time 09:50 Rev Time 0.00
Received By ebowers Date 2005-05-19 Time 12:31 Sent To I
Notes
2005-05-19 00:00:00--PROVISO--
 LANDSCAPING SHALL BE ADDED TO REFLECT
 RESUBMITTED DRAWINGS OF 5/19/05
  
2005-04-18 00:00:00MINOR PD AMENDMENT AND LANDSCAPING PLAN
 REQUIRED; NEEDS TO ADD LANDSCAPING
 AROUND ENCLOSURE

Review Stop Z ZONING
Rev No 1 Status F Date 2005-01-20 Cont ID  
Sent By mmclean Date 2005-01-20 Time 16:59 Rev Time 0.00
Received By mmclean Date 2005-01-20 Time 16:59 Sent To I
Notes
2005-01-20 00:00:00DENIED, NEED TO PROVIDE TWO COPY OF
 SURVEY SHOWING THE LOCATION OF THE
 GENERATOR WITH SETBACKS
 (SIDE/REAR/FRONT).