Plan Review Details - Permit 05010600
Plan Review Stops For Permit 05010600
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-02-01 Cont ID  
Sent By alange Date 2005-02-01 Time 11:19 Rev Time 0.50
Received By alange Date 2005-02-01 Time 11:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-03-02 Cont ID  
Sent By btrobaug Date 2005-03-02 Time 11:51 Rev Time 0.50
Received By btrobaug Date 2005-03-02 Time 11:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-24 Cont ID  
Sent By btrobaug Date 2005-01-24 Time 10:43 Rev Time 0.75
Received By btrobaug Date 2005-01-24 Time 09:48 Sent To M
Notes
2005-01-24 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE LOAD CALCULATIONS,
 RISER DIAGRAM AND PANEL(S) SCHEDULE.
 INDICATE IF SERVICE IS NEW OR EXISTING.
 215.5
  
 2} PROVIDE A FLOOR PLAN THAT INDICATES
 LOCATION OF KITCHEN COUNTERTOPS AND
 APPLIANCES SO THAT COMPLIANCE WITH
 210.52 CAN BE DETERMINED. ALSO SEE THE
 ELECTRICAL FLOOR PLANS DIFFER FROM
 ARCHITECTURALS. PLEASE CORRELATE.
  
 3} PLEASE INDICATE LOCATIONS OF A/C
 EQUIPMENT ON PLAN, VERIFY COMPLIANCE
 WITH 210.63 & 210.70(A)(3).
  
 4} LOCATE FRONT AND REAR RECEPTACLES PER
 210.52(E).
  
 5} INDICATE THE FUNCTION OF THE DEVICES
 THAT APPEAR TO BE LOCATED IN A CLOSET IN
 THE KITCHEN.
  
 6} PER 104.2.1 FBC THE DESIGNER OF
 RECORD MUST PRINT NAMEAND SIGN THE
 PLAN(S) THEY ARE RESPONSIBLE FOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-25 Cont ID  
Sent By adarroug Date 2005-02-25 Time 14:50 Rev Time 0.00
Received By adarroug Date 2005-02-25 Time 14:50 Sent To E
Notes
2005-02-25 00:00:00TO "BT" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-13 Cont ID  
Sent By mjacobs Date 2005-01-13 Time 14:31 Rev Time 0.00
Received By mjacobs Date 2005-01-13 Time 14:31 Sent To E
Notes
2005-01-13 00:00:00TO "E" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-01-25 Cont ID  
Sent By prafter Date 2005-01-25 Time 10:01 Rev Time 1.00
Received By prafter Date 2005-01-25 Time 10:21 Sent To B
Notes
***NONE***