Plan Review Details - Permit 05010487
Plan Review Stops For Permit 05010487
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-05-26 Cont ID  
Sent By alange Date 2005-05-26 Time 13:05 Rev Time 0.50
Received By alange Date 2005-05-26 Time 12:53 Sent To  
Notes
2005-05-26 00:00:00DECK REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-16 Cont ID  
Sent By alange Date 2005-03-16 Time 11:48 Rev Time 0.66
Received By alange Date 2005-03-16 Time 11:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-25 Cont ID  
Sent By alange Date 2005-02-25 Time 08:50 Rev Time 0.50
Received By alange Date 2005-02-25 Time 08:50 Sent To  
Notes
2005-02-25 00:00:00DENIED
  
 1.PRODUCT APPROVALS SUBMITTED ARE
 INCOMPLETE.PLEASE SUBMIT TWO SETS OF
 PRODUCT APPROVALS WITH QUALITY
 ASSURANCE (MIAMI-DADE) FOR EXAMPLE.
 PGT DOORS DO NOT HAVE QUALITY ASSURANCE
 SUBMITTED.SUBMIT 2 COPIES FOR EACH
 WINDOW TYPE.
 ALL OF THE ABOVE REQUIRE THE FOLLOWING
 TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.SEE NOTES FROM ELECTRICAL REVIEW
 THAT MAY EFFECT ISSUING OF PERMIT.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-28 Cont ID  
Sent By alange Date 2005-01-28 Time 08:38 Rev Time 1.00
Received By alange Date 2005-01-28 Time 08:38 Sent To  
Notes
2005-01-28 00:00:00DENIED
  
 1.PRODUCT APPROVALS SUBMITTED ARE
 INCOMPLETE.PLEASE SUBMIT TWO SETS OF
 PRODUCT APPROVALS WITH QUALITY
 ASSURANCE (MIAMI-DADE) FOR EXAMPLE.
 ALL OF THE ABOVE REQUIRE THE FOLLOWING
 TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2.SHOW ON FLOOR PLAN NEW AND EXISTING
 WALLS.
  
 3.SHOW LOCATION OF NEW STAIR CASE.
 SHOW STRUCTURAL DETAIL OF FRAMING FOR
 STAIRS, RAILINGS AND GUARDRAILS.
  
 4.SEE NOTES FROM ELECTRICAL REVIEW
 THAT MAY EFFECT ISSUING OF PERMIT.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT.
 THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-03-14 Cont ID  
Sent By dpalmer Date 2005-03-14 Time 13:18 Rev Time 0.30
Received By dpalmer Date 2005-03-14 Time 13:18 Sent To B
Notes
2005-03-14 00:00:00REDLINED:
  
 110.26 ELECTRICAL PANEL
 210.52 RAIL/WALL SPACE
 210.8A6 KITCHEN RECEPT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-02-23 Cont ID  
Sent By dpalmer Date 2005-02-23 Time 15:07 Rev Time 0.25
Received By dpalmer Date 2005-02-23 Time 15:07 Sent To B
Notes
2005-02-23 00:00:00********* UNSAT 2ND REVIEW *********
  
 1)NOTE: PLEASE SEE COMMENTS FROM
 PREVIOUS REVIEW.
 PLEASE SEE RESPONSE LETTER MENTIONS WORK
 ONLY TO BE DONE IN KITCHEN AND NEW
 STAIR.
 PLEASE SUBMIT ELECTRICAL PLANS WHICH
 ONLY INDICATE WORK TO BE DONE.
 ELECTRICAL NOTES MENTIONS MORE WORK THAN
 WHAT IS MENTIONED IN RESPONSE LTR.
 PLEASE SEE ELECTRICAL PLAN SHOWS MANY
 OTHER ELECTRICAL ITEMS TO BE DONE??
 IF HOUSE IS BEING REMODELED/ REWIRED,
 PLEASE SHOW ALL REQUIRED PER 2002 NEC
 AND NFPA-72.
  
 2)NOTE: PLEASE SEE PLANS WHICH ARE
 SIGNED AND SEALED BY AN ARCH/ ENGINEER
 ARE NOT PERMITTED TO HAND-DRAWN CHANGES
 AND "WHITE-OUT" ON PLANS. PLEASE SEE
 HAND DRAWN CHANGES REQUIRED EACH CHANGE
 TO BE SIGNED, DATED.
 PLEASE SUBMIT NEW REPRINTED SIGNED,
 DATED AND SEALED PLANS.
 FS 481.221
  
 3)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN
 COUNTERSPACE RECEPT SPACING.
 PLEASE ALSO SEE 210.8A6 FOR REQUIRED GFI
 PROTECTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
 NOTE ADDED:
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-19 Cont ID  
Sent By dpalmer Date 2005-01-19 Time 11:46 Rev Time 0.30
Received By dpalmer Date 2005-01-19 Time 11:46 Sent To B
Notes
2005-01-19 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SEE PER PERMIT
 APPLICATION MENTIONS NEW AREAS WHICH
 WOULD REQUIRE ELECTRICAL WORK. PLEASE
 SEE A4X FEE PER INSPECTOR WAS ALSO
 ISSUED FOR THIS SMAE SCOPE OF WORK FOR
 ELECTRICAL. ??
 PLANS SUBMITTED ARE NOTED AS ALL
 ELECTRICAL EXISTING??
 PLEASE SUBMIT COMPLETED PLANS FOR 2002
 CODE COMPLIANCE FOR NEW WORK BEING
 PERFORMED.
  
 2)NOTE: PLEASE SEE FS 481.221, PLANS ARE
 REQUIRED TO BE SIGNED, SEALED AND DATED
 BY ARCH.
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2005-01-11 Cont ID  
Sent By spalmer Date 2005-01-11 Time 15:41 Rev Time 0.15
Received By spalmer Date 2005-01-11 Time 15:41 Sent To  
Notes
2005-01-11 00:00:00OKAY PER EMILY STILLINGS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-23 Cont ID  
Sent By adarroug Date 2005-05-23 Time 16:16 Rev Time 0.00
Received By adarroug Date 2005-05-23 Time 16:16 Sent To B
Notes
2005-05-23 00:00:00TO "ALANGE" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-10 Cont ID  
Sent By adarroug Date 2005-03-10 Time 13:35 Rev Time 0.00
Received By adarroug Date 2005-03-10 Time 13:35 Sent To E
Notes
2005-03-10 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-11 Cont ID  
Sent By mjacobs Date 2005-01-11 Time 16:00 Rev Time 0.00
Received By mjacobs Date 2005-01-11 Time 16:00 Sent To E
Notes
2005-01-11 00:00:00TO "E" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-14 Cont ID  
Sent By mjacobs Date 2005-02-14 Time 15:35 Rev Time 0.00
Received By mjacobs Date 2005-02-14 Time 15:35 Sent To E
Notes
2005-02-17 00:00:00TO "DP" DESK/RESUB.