| 2005-01-11 00:00:00 | ********** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE MISSING CA # |
| | REQUIRED |
| | TO BE PRINTED ON TITLE BLOCK PER FAC |
| | 61G15-23.002, FS 471.023 |
| | PLEASE SEE THIS WAS HANDWRITTEN ON |
| | TITLE |
| | BLOCKS, HOWEVER, DUE TO PLANS COMING |
| | BACK FOR CODE REVIEW COMMENTS, PLEASE |
| | ADD THIS IN CAD AT THIS TIME. |
| | |
| | 2)NOTE: PLEASE VERIFY NEUTRAL CONDUCTOR |
| | REQUIRED TO THE FIRST MEANS OF DISC. |
| | PLEASE SEE REQUIREMENTS FOR METER. |
| | PLEASE SEE NEUTRAL IS ONLY REQUIRED TO |
| | FIRST MEANS OF DISC AND NOT TO |
| | TRANSFORMER AS IT THEN BECOMES A |
| | SEPARATELY DERIVED SYSTEM. |
| | 20.6,250.24 ETC. |
| | |
| | 3)NOTE: PLEASE SHOW ATTACHMENT FOR |
| | GROUNDING OF TRANSFORMER PER 250.30 |
| | SHOWS , GRND BUT NOT ATTACHMENT.(MAY BE |
| | NOTE). |
| | |
| | 4)NOTE: PLEASE SUBMIT LOAD CALCS FOR |
| | ADDITON OF NEW LOAD TO AN EXISTING |
| | SYSTEM. PER 215.5,220 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIE WAND STAMPING. |
| | PLEASE SUBMIT ONLY ONE COPY OF OLD |
| | SHEETS FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |