Plan Review Details - Permit 05010233
Plan Review Stops For Permit 05010233
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-01-24 Cont ID  
Sent By lsmith Date 2005-01-24 Time 09:05 Rev Time 0.75
Received By lsmith Date 2005-01-24 Time 09:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-01-18 Cont ID  
Sent By dpalmer Date 2005-01-18 Time 14:11 Rev Time 0.20
Received By dpalmer Date 2005-01-18 Time 14:11 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-28 Cont ID  
Sent By mjacobs Date 2005-01-28 Time 11:46 Rev Time 0.00
Received By mjacobs Date 2005-01-28 Time 11:46 Sent To P
Notes
2005-01-28 00:00:00TO "P" BOX/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-13 Cont ID  
Sent By mjacobs Date 2005-01-13 Time 16:12 Rev Time 0.00
Received By mjacobs Date 2005-01-13 Time 16:12 Sent To E
Notes
2005-01-13 00:00:00TO 'E" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 16:10 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 16:10 Sent To Z
Notes
2005-01-06 00:00:00TO "Z" BOX.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-02-14 Cont ID  
Sent By kstevens Date 2005-02-14 Time 09:10 Rev Time 0.50
Received By kstevens Date 2005-02-14 Time 09:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-21 Cont ID  
Sent By kstevens Date 2005-01-21 Time 05:04 Rev Time 0.50
Received By kstevens Date 2005-01-20 Time 18:54 Sent To B1
Notes
2005-01-21 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING
 POOLS
  
 A) THE FOLLOWING INFORMATION IS REQUIRED
 TO BE ON THE PLANS FOR REVIEW:
 1) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 2) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 3) FBC-2001 424.2.13.2 JOINTS AND
 CONNECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING AND
 FITTINGS. (ADD TO NOTES)
 4) FBC-2001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-13 Cont ID  
Sent By mmclean Date 2005-01-13 Time 15:58 Rev Time 0.00
Received By mmclean Date 2005-01-13 Time 15:58 Sent To I
Notes
***NONE***