Plan Review Details - Permit 05010076
Plan Review Stops For Permit 05010076
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-05-20 Cont ID  
Sent By jwitmer Date 2005-05-20 Time 14:42 Rev Time 1.66
Received By jwitmer Date 2005-05-20 Time 14:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-05-20 Cont ID  
Sent By jwitmer Date 2005-05-20 Time 14:42 Rev Time 1.66
Received By jwitmer Date 2005-05-20 Time 14:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-12 Cont ID  
Sent By jwitmer Date 2005-03-12 Time 09:22 Rev Time 0.55
Received By jwitmer Date 2005-03-12 Time 09:22 Sent To  
Notes
2005-03-12 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010076
 ADD: 1400 NORTHPOINT PARKWAY# 10
 CONT:BRICAR ENTERPRISES INC
 TEL: (561)675-1976
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)COMMENT # 1B FROM THE PREVIOUS REVIEW:
 RESPONSE FROM KAMM, THIS COMMENT TO BE
 SUPPLIED BY OWNER. NO INFORMATION WAS
 SUPPLIED. NUMBER OF TANKS AND SIZE OF
 TANKS FOR EACH OF THE GASSES?
  
 COMMENT #3 WAS ANSWERED BY THE FIRE
 REVIEW COMMENT #4 ABOUT RATING OF THE
 ENCLOSURE WAS PARTIALLY ANSWERED BUT NO
 MENTION OF AIR CIRCULATION?
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-21 Cont ID  
Sent By jwitmer Date 2005-01-21 Time 13:43 Rev Time 1.55
Received By jwitmer Date 2005-01-21 Time 13:43 Sent To  
Notes
2005-01-21 00:00:00BUILDING PLAN REVIEW
 PERMIT:05010076
 ADD: 1400 NORTHPOINT PKWY# 10
 CONT: BRICAR ENTERPRISES
 TEL: (954)675-1976
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE NEW LAB DOESN'T INDICATE IF THERE
 WILL BE FUME HOODS? WHAT QUANITIES OF
 GASSES WILL BE STORED?
  
 2) ALSO THE PLUMBING PAGES INDICATE THE
 USE OF HYDROGEN TANKS IN A INCLOSURE
 BUT THERE IS NO MENTION OF PIPING OF
 HYDROGEN?
  
 3)THE ENCLOSURE HOLDING THE HYDROGEN
 TANK WHAT IS IT RATED FOR?
  
 4) 1511.7 ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-01-12 Cont ID  
Sent By dpalmer Date 2005-01-12 Time 08:53 Rev Time 0.60
Received By dpalmer Date 2005-01-12 Time 08:53 Sent To  
Notes
2005-01-12 00:00:00REDLINED 250.24,250.6

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-05-25 Cont ID  
Sent By mwennerg Date 2005-05-25 Time 15:11 Rev Time 0.00
Received By mwennerg Date 2005-05-25 Time 15:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-03-30 Cont ID  
Sent By mwennerg Date 2005-03-30 Time 11:10 Rev Time 0.00
Received By mwennerg Date 2005-03-30 Time 11:10 Sent To  
Notes
2005-03-30 00:00:001) IN REGARDS TO THE FIRE SEPARATION FOR
 THE CYLINDER STORAGE AREA, ALTHOUGH IT'S
 EXISTING, WHAT IS THE FIRE SEPARATION?
  
 2) IN REGARDS TO YOUR RESPONSE AS TO
 WHAT SPECIAL PRECAUTIONS WILL BE TAKEN
 WITH THE ACETYLENE AND ARGON, NO ANSWER
 HAS BEEN PROVIDED BY THE OWNER.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-01-25 Cont ID  
Sent By mcarsill Date 2005-01-25 Time 15:40 Rev Time 0.00
Received By mcarsill Date 2005-01-25 Time 15:39 Sent To  
Notes
2005-01-25 00:00:001. THE ARGON, HELIUM, AND ACETYLENE
 SHALL BE USED, STORED, AND HANDLED
 IN ACCORDANCE WITH ALL APPLICABLE
 CODES AND STANDARDS.
  
 2. WHAT IS THE FIRE SEPARATION FOR
 THE CYLINDER STORAGE AREA.
  
 3. PLEASE INDICATE WHAT SPECIAL
 PRECAUTIONS WILL BE TAKEN WITH
 THE ACETYLENE AND ARGON.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-25 Cont ID  
Sent By adarroug Date 2005-04-25 Time 14:44 Rev Time 0.00
Received By adarroug Date 2005-04-25 Time 14:44 Sent To  
Notes
2005-04-25 00:00:00TO "COMM" BD#43

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-02 Cont ID  
Sent By adarroug Date 2005-03-02 Time 13:48 Rev Time 0.00
Received By adarroug Date 2005-03-02 Time 13:48 Sent To  
Notes
2005-03-02 00:00:00TO "COMM" BD#37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-05 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 08:47 Rev Time 0.00
Received By pkrauss Date 2005-01-05 Time 10:07 Sent To  
Notes
2005-01-05 00:00:00TO "COMM BD#14

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-06-13 Cont ID  
Sent By pkrauss Date 2005-06-13 Time 06:52 Rev Time 0.15
Received By pkrauss Date 2005-06-13 Time 06:45 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-06-07 Cont ID  
Sent By pkrauss Date 2005-06-07 Time 06:41 Rev Time 0.55
Received By pkrauss Date 2005-06-06 Time 16:52 Sent To  
Notes
2005-06-07 00:00:00CALLED CONTRACTOR TO CORRELATE PLANS.
 PLANS ARE CODE COMPLIANT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-05-26 Cont ID  
Sent By hmoser Date 2005-05-26 Time 18:33 Rev Time 0.00
Received By hmoser Date 2005-05-26 Time 18:33 Sent To  
Notes
2005-05-26 00:00:00PLAN DENIED
 COMMENTS1 THROUGH 6 FROM LAST REVIEW
 WERE NOT ADDRESSED.PLEASE INLARGE
 MECHANICAL PLANS SO ALL DUCT SIZES,CFM,
 AND CAN SIZES CAN BE SEEN BY PLAN
 REVIEWER AND INSPECTIOR.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-03-31 Cont ID  
Sent By pkrauss Date 2005-03-31 Time 10:22 Rev Time 0.45
Received By pkrauss Date 2005-03-31 Time 08:28 Sent To  
Notes
2005-03-31 00:00:00DENIED:
 COMMENTS 1 THORUGH 3, 5 & 6 FROM REVIEW
 DATED 1-24-05 WERE NOT ADDRESSED.
 RESPONSE LETTER FROM KAMM INDICATES THE
 OWNER WILL ADDRESS.OWNERS COMMENTS
 WERE NOT INCLUDED.
  
 PROVIDE THE AMOUNT OR QUANTITIES FOR ALL
 OF THE PRODUCTS LISTED AND SUBMITTED ON
 THE MATERIAL SAFETY DATA SHEETS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-25 Cont ID  
Sent By pkrauss Date 2005-01-24 Time 16:50 Rev Time 1.00
Received By pkrauss Date 2005-01-24 Time 16:25 Sent To  
Notes
2005-01-24 00:00:00DENIED:
 1. PLEASE INDICATE ON THE PLAN WHAT
 TYPE
 OF PROCESSES WILL TAKE PLACE IN THE
 LAB.
  
 2. PLEASE INDICATE WHAT APPLICATION THE
 ARGON AND NITROGEN GASES WILL BE USED
 FOR.
  
 3. INDICATE CAPACITY OF THE BOTTLES OR
 OR TANKS FOR THE GASES.
  
 4. INDICATE VENTILATION FOR THE STORAGE
 ROOM WHERE THE GASES WILL BE STORED (NEW
 OR EXISTING).
  
 5.WILL ANY OTHER TOXIC OR HAZARDOUS
 CHEMICALS BE USED OR STORED IN THE LAB?
 PROVIDE DETAILS ON STORAGE.
  
 6.PROVIDE MSDS INFORMATION FOR ANY
 HAZARDOUS OR TOXIC CHEMICALS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-06-16 Cont ID  
Sent By kstevens Date 2005-06-16 Time 17:28 Rev Time 1.10
Received By kstevens Date 2005-06-16 Time 17:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-06-06 Cont ID  
Sent By kstevens Date 2005-06-06 Time 06:53 Rev Time 1.57
Received By kstevens Date 2005-06-04 Time 11:28 Sent To  
Notes
2005-06-06 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
  
 INITIALS ARE NOT ACCEPTABLE PER RULEING
 BY FBPE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-03-18 Cont ID  
Sent By kstevens Date 2005-03-18 Time 13:49 Rev Time 3.84
Received By kstevens Date 2005-03-18 Time 13:49 Sent To  
Notes
2005-03-18 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 A) FROM PREVIOUS REVIEW:
 1) MORE INFORMATION IS REQUIRED.
 INDICATE THE USE OF THE GASES. SECTION
 104.2.1. RESPONSE NOTED, BUT NO
 INFORMATION FROM THE OWNER HAS BEEN
 SUBMITTED.
 4) INDIACTE THE AMOUNT AND TYPE OF GAS
 STORED ON THE JOBSITE. SECTION 104.2.1.
 RESPONSE NOTED, BUT NO INFORMATION FROM
 OWNER HAS BEEN SUBMITTED.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-25 Cont ID  
Sent By kstevens Date 2005-01-25 Time 16:18 Rev Time 1.25
Received By kstevens Date 2005-01-25 Time 16:18 Sent To  
Notes
2005-01-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 NFPA 99
 NFPA 54
  
 1) MORE INFORMATION IS REQUIRED.
 INDICATE THE USE OF THE GASES. SECTION
 104.2.1.
 2) SHT PO.1 GENERAL GAS NOTES INDICATES
 THAT ALL GAS LINES SHALL BE 1/8" BUT
 THE
 FITTINGS SHALL BE 7/8" SWEAGLOCK.
 PLEASE
 CLARIFY. SECTION 104.2.1. (ALSO SEE SHT
 P5.1 RISER DIAGRAM SHOWS 1/2" PIPE).
 3) SHT P0.1 GENERAL GAS NOTES REFERENCES
 NFPA 54 WHICH IS FOR NATURAL GAS. PLEASE
 INDICATE WHERE THE NATURAL GAS SYSTEM IS
 LOCATED AND SHOW PIPING DIAGRAM FOR THIS
 SYSTEM. MORE COMMENTS MAY FOLLOW WITH
 THE RESPONSE FROM THIS COMMENT.
 4) INDICATE THE AMOUNT AND TYPE OF GAS
 STORED ON THE JOBSITE. SECTION 104.2.1.
 5) SHT P2.1 NOTES INDICATE (3) LINES
 FROM HELIUM, NITROGEN, AND ACETLYENE
 TANKS, - (2) LINES FROM ARGON AND
 NITROGEN TANKS, - (4) LINES FROM ARGON,
 BUT SHT P5.1 SHOWS 4 LINES, 1EA FROM
 ARGON, HELIUM, ACETYLENE, & NITROGEN TO
 EACH VALVE BOX. PLEASE CLARIFY.
 6) PLEASE INDICATE WHERE THE AIR AND
 CH4
 GAS IS PIPED TO. THIS IS NOT INDICATED
 ON THE PLANS. SECTION 104.2.1.
 7) SUBMIT MSDS SHEETS FOR ALL HAZARDOUS
 MATERIALS STORED AND/OR USED ON THE JOB
 SITE. SECTION 104.2.1.
 8) STH P5.1 SUBMIT A DETAIL FOR THE
 VENTING FOR THE GAS TANK STORAGE ROOM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy