Plan Review Details - Permit 05010074
Plan Review Stops For Permit 05010074
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-05-25 Cont ID  
Sent By shill Date 2005-05-25 Time 15:12 Rev Time 0.50
Received By shill Date 2005-05-25 Time 15:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-05-20 Cont ID  
Sent By shill Date 2005-05-20 Time 09:28 Rev Time 0.50
Received By shill Date 2005-05-20 Time 09:28 Sent To  
Notes
2005-05-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
 FAX 561-653-2962
  
 1.)SEE PREVIOUS LIST, ITEMS 1 - 4.
 NOT ENOUGH INFORMATION TO DETERMINE CODE
 COMPLIANCE IN REGARDS TO OCCUPANCY,
 OCCUPANCY SEPARATIONS AND EGRESS.
  
 PLEASE INCLUDE THE FOLLOWING INFORMATION
 ON THE PLAN:
  
 OCCUPANCY TYPE FOR NEW AND EXISTING
 AREAS FBC CHAPTER 3
  
 SHOW COMPLIANCE WITH FBC704, OCCUPANCY
 SEPARATION, IF REQUIRED.INCLUDE
 INFORMATION FOR THE DOORS (FIRE RATING)
 AS REQUIRED
  
 2.)ONLY ONE MEANS OF EGRESS FROM
 "EXISTING BUILDING" AREA IS SHOWN.
 ADDRESS; TWO REQUIRED, FBC1004.2.
  
 3.)SEE ATTACHED FS553.80(2)(B).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-24 Cont ID  
Sent By shill Date 2005-01-24 Time 13:12 Rev Time 2.00
Received By shill Date 2005-01-24 Time 13:03 Sent To  
Notes
2005-01-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)DECLARE AN OCCUPANCY TYPE FOR NEW
 AND EXISTING AREAS FBC CHAPTER 3.
  
 2.)SHOW COMPLIANCE WITH FBC 704,
 OCCUPANCY SEPARATIONS.INCLUDE
 INFORMATION FOR THE DOORS (FIRE RATING)
 AS REQUIRED.
  
 3.)PROVIDE INFORMATION IN REGARDS TO
 CHEMICALS TO BE USED IN THE MIXING ROOM
 AND SPRAY BOOTHS; MSDS IF NECESSARY.
 WHERE WILL PAINT BE STORED?
 (INFORMATION
 PERTINENT TO OCCUPANCY, STORAGE OF
 COMBUSTIBLE MATERIALS).ALSO SEE FBC
 TABLE 308.2; SHOW COMPLIANCE ON THE
 PLAN.
  
 4.)PROVIDE STRUCTURAL DETAILS FOR THE
 MIXING ROOM AND SPRAY BOOTH.THE FLOOR
 PLAN DOES NOT SHOW DOORS FOR THE MIXING
 ROOM, WALL SECTIONS ARE NOT ON THE
 PLAN.
  
 5.)SHEET 1, CODE INFORMATION, LISTS
 THREE DIFFERENT BUILDING CODES (FBC,
 UBC
 AND IBC).PLEASE REFER TO THE CORRECT
 BUILDING CODE ONLY, FBC 2001 WITH
 AMENDMENTS.
  
 6.)THE SEAL IS TO BE DATED AND THE CA
 NUMBER FOR MOLVET ENGINEERING LLC IS TO
 BE ON THE TITLE BLOCK, FAC61G15-23.002.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-05-18 Cont ID  
Sent By dpalmer Date 2005-05-18 Time 18:59 Rev Time 0.25
Received By dpalmer Date 2005-05-18 Time 18:52 Sent To  
Notes
2005-05-18 00:00:00****** PLANS REDLINED *******
  
 ELECTRICAL PLANS DID NOT INDICATE
 RESTRICATIONS PER NFPA-33, NEC 516 ,
 HOWEVER, PLEASE SEE "SPRAY BOOTHPLANS"
  
 **ALL ELECTRICAL WIRING TO MEET THE
 ABOVE AS NOTED.
  
  
  
 ATTACHED ELECTRICAL SHEETS TO SPRAY
 BOOTH PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-04-12 Cont ID  
Sent By dpalmer Date 2005-04-12 Time 19:16 Rev Time 0.20
Received By dpalmer Date 2005-04-12 Time 19:16 Sent To FIRE
Notes
2005-04-12 00:00:00********* UNSAT ********
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEW.
  
 1)NOTE: PLEASE SEE ONLY SHEET 1 WAS
 REVISED. PLEASE SEE ALL OTHER SHEETS DID
 NOT HAVE CORRECTIONS MADE TO TITLE
 BLOCKS AS REQUIRED PER FAC 61G15-23.002,
 FS 471.023
 PLEASE SEE NO NEW SHEETS CONTAINING
 HAZARDOUS LAYOUT AS REQUIRED FOR PAINT
 BOOTH(S).
  
 2)NOTE: PLEASE SEE NEW SHEET 1 DOES NOT
 CONTAIN ANY ELECTRICAL INFORMATION FOR
 REVIEW.??
 PLEASE SUBMIT ELECTRICAL INFORMATION ON
 HOW THIS BOOTH WILL BE CONNECTED, FROM
 WHERE ETC. 215.5
 PLEASE INCLUDE ANY ELECTRICAL WHICH MAY
 BE PART OF THIS SCOPE.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-13 Cont ID  
Sent By dpalmer Date 2005-01-13 Time 14:09 Rev Time 0.25
Received By dpalmer Date 2005-01-13 Time 14:09 Sent To  
Notes
2005-01-13 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SEE THERE IS NOT ENOUGH
 ELECTRICAL INFORMATION SUBMITTED FOR
 REVIEW.
  
 2)NOTE: PLEASE CLARIFY "MIXING RM".
  
 3)NOTE: PLEASE PROVIDE ALL INFORMATION
 ON WHAT IS GOING TO BE PAINTED, USE
 ETC.
 PLEASE SEE REVIEW COMMENTS FROM OTHER
 REVIEWER(S).
  
 4)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK FOR ENG FIRM.
 FAC 61G15-23.002, FS 471.023
  
 5)NOTE: PLEASE SEE PLANS REFERENCE A
 2003 NEC. PLEASE SEE THERE IS NO 2003
 NEC. THE 2002 IS NOW IN AFFECT AND THEN
 WILL GO TO 2005.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-04-12 Cont ID  
Sent By pkrauss Date 2005-04-12 Time 13:25 Rev Time 0.10
Received By pkrauss Date 2005-04-12 Time 13:25 Sent To  
Notes
2005-04-12 00:00:00PROVISO:
 ADDITIONAL FIRE SUPPRESSION PERMIT
 REQUIRED.PROVIDE PLANS WITH PERMIT
 APPLICATION.
  
 SPRAY BOOTH PLANS APPROVED PER NATE
 MCCRAY 4-12-05

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-01-25 Cont ID  
Sent By nmccray Date 2005-01-25 Time 11:13 Rev Time 0.00
Received By nmccray Date 2005-01-25 Time 11:01 Sent To  
Notes
2005-01-25 00:00:00DENIED:
 1) HOW MUCH FLAMMABLE AND COMBUSTIBLE
 LIQUIDS OR MATERIALS WILL BE STORED ON
 SITE?
  
 2) A FLAMMABLE AND COMBUSTIBLE MATERIALS
 CABINET WILL BE REQUIRED FOR STORAGE.
  
 3) PLEASE PROVIDE INFORMATION AS TO WHAT
 WILL THIS SPRAY PAINT BOOTH BE USED
 FOR.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-18 Time 09:08 Rev Time 0.00
Received By adarroug Date 2005-05-04 Time 16:32 Sent To  
Notes
2005-05-18 00:00:00TO "COMM" BD#46
2005-05-04 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-12 Cont ID  
Sent By adarroug Date 2005-04-12 Time 17:08 Rev Time 0.00
Received By adarroug Date 2005-04-12 Time 17:08 Sent To E
Notes
2005-04-12 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-04 Cont ID  
Sent By mjacobs Date 2005-01-04 Time 15:40 Rev Time 0.00
Received By mjacobs Date 2005-01-04 Time 15:35 Sent To M
Notes
2005-01-04 00:00:00TO "COMM BD#26"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-05-04 Cont ID  
Sent By pkrauss Date 2005-05-04 Time 13:40 Rev Time 0.55
Received By pkrauss Date 2005-05-04 Time 13:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-04-13 Cont ID  
Sent By pkrauss Date 2005-04-13 Time 15:19 Rev Time 0.45
Received By pkrauss Date 2005-04-13 Time 15:09 Sent To  
Notes
2005-04-13 00:00:00DENIED:
 PLANS ORIGINALLY SUBMITTED INDICATE "OLD
 PLANS".THE NEW PLANS DO NOT GIVE THE
 REQUIRED DISTANCES AROUND THE SPRAY &
 MIXING BOOTHS.
  
 PLEASE PROVIDE DISTANCE BETWEEN THE
 TERMINATION OF EXHAUST AND PROPERTY
 LINES, ADJACENT OR CONTIGUOUS BUILDINGS.
  
 ADDITIONAL PERMIT REQUIRED FOR FIRE
 SUPPRESSION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-12 Cont ID  
Sent By pkrauss Date 2005-01-12 Time 16:05 Rev Time 0.55
Received By pkrauss Date 2005-01-12 Time 12:19 Sent To  
Notes
2005-01-12 00:00:00DENIED:
 PROVIDE INFORMATION AS TO WHAT WILL BE
 THE SPRAY PAINT BOOTH BE USED FOR
 (FURNITURE, CARS?)
  
 PROVIDE MSDS SUBMITTALS FOR CHEMICALS
 THAT MAY BE USED IN THIS PROCESS.
  
 PROVIDE SUBMITTAL FOR STORAGE OF
 CHEMICALS OR HAZARDOUS LIQUIDS TO BE AT
 THIS LOCATION.
  
 PLEASE NOTE, ZONING APPROVAL REQUIRED
 FOR THIS APPLICATION AT THIS SITE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-13 Cont ID  
Sent By mmclean Date 2005-01-13 Time 14:52 Rev Time 0.00
Received By mmclean Date 2005-01-13 Time 14:51 Sent To  
Notes
2005-01-13 00:00:00APPROVED BY JOSH LONG, PLANNER RECEIVED
 A CLASS B SPECIAL USE PERMIT.