Plan Review Details - Permit 05010021
Plan Review Stops For Permit 05010021
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2006-02-03 Cont ID  
Sent By jwitmer Date 2006-02-03 Time 15:18 Rev Time 0.77
Received By jwitmer Date 2006-02-03 Time 15:17 Sent To PC
Notes
2006-02-03 00:00:00FRONT DOOR PRODUCT APPROVAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2006-01-17 Cont ID  
Sent By jwitmer Date 2006-01-17 Time 08:23 Rev Time 0.77
Received By jwitmer Date 2006-01-17 Time 08:23 Sent To PC
Notes
2006-01-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010021
 ADD: 201 PALMETTO LN
 CONT: STERLING COMMUNITIES
 TEL: (561)239-9740
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) FROM THE PREVIOUS REVIEW NOTE# 2.
  
 THE PRODUCT APPROVAL SUBMITTED DOES
 NOT HAVE FL APPROVAL. IT STATES IN THE
 REPORT IT IS BASED ON RULE 9B-72.40
 METHOD 1D. THIS IS A REPORT FROM A FL
 REGISTERED ARCHITECT OR A FLORIDA
 PROFESSIONAL ENGINEER WHO DEVELOPED AND
 SIGNED AND SEALED, BASED UPON TESTING OR
 COMPARATIVE ANALYSIS, OR A COMBINATION
 THEREOF WHICH PROVIDES VERIFIABLE
 DOCUMENTATION INDICATING THE PRODUCT WAS
 EVALUATED TO BE IN COMPLIANCE WITH THE
 CODE AND THAT THE PRODUCT IS, FOR THE
 PURPOSE INTENDED, AT LEAST EQUIVLENT TO
 THAT REQUIRED BY THE CODE.
 THE REPORT SUBMITTED IS NOT THE
 ORIGINAL, NOT RAISED SEAL NOR ORIGINAL
 SIGNATURE. RULE 9B-72.040(1)(D).
 THE OTHER ISSUE IS TO PROVIDE STATE
 APPROVED THIRD PARTY QUALITY ASSURANCE
 PROGRAM DOCUMENTATION REQUIRED BY RULE
 9B-72.70.
 THE FLORIDA COVERSHEET SUBMITTED
 IS NOT FOR THE REPORT SUBMITTED. THERE
 IS ONLY ONE SYSTEM THAT HAS BEEN
 APPROVED BY THE STATE THE REST ARE STILL
 ONLY APPLIED FOR OR PENDING. ALL THE
 REPORTS SUBMITTED ARE FOR VARIOUS OTHER
 PRODUCTS MANUFACTURED BY THE SAME
 MANUFACTURER.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2006-01-17 Cont ID  
Sent By jwitmer Date 2006-01-17 Time 07:44 Rev Time 0.55
Received By jwitmer Date 2006-01-17 Time 07:44 Sent To PC
Notes
2006-01-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010021
 ADD: 201 PALMETTO LN
 CONT: STERLING COMMUNITIES
 TEL: (561)239-9740
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW REVISION
 ACTION: DENIED
  
 1)THE ONLY "BUILDING PROVISO" GIVEN AT
 TIME OF ISSUANCE WAS ON 3-14-05 FOR
 1026.5.1 EXTERIOR GUARDRAILS TO BE 42"
 IN HEIGHT. THIS IS A REVISION REQUIRING
 ADDITIONAL FEES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-12-20 Cont ID  
Sent By jwitmer Date 2005-12-20 Time 10:19 Rev Time 0.77
Received By jwitmer Date 2005-12-20 Time 10:19 Sent To PC
Notes
2005-12-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010021
 ADD: 201 PALMETTO LN
 CONT: STERLING COMMUNITIES
 TEL: (561)239-9740
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)THE ONLY "BUILDING PROVISO" GIVEN AT
 TIME OF ISSUANCE WAS ON 3-14-05 FOR
 1026.5.1 EXTERIOR GUARDRAILS TO BE 42"
 IN HEIGHT. THIS IS A REVISION REQUIRING
 ADDITIONAL FEES.
  
 2) THE PRODUCT APPROVAL SUBMITTED DOES
 NOT HAVE FL APPROVAL. IT STATES IN THE
 REPORT IT IS BASED ON RULE 9B-72.40
 METHOD 1D. THIS IS A REPORT FROM A FL
 REGISTERED ARCHITECT OR A FLORIDA
 PROFESSIONAL ENGINEER WHO DEVELOPED AND
 SIGNED AND SEALED, BASED UPON TESTING OR
  
 COMPARATIVE ANALYSIS, OR A COMBINATION
 THEREOF WHICH PROVIDES VERIFIABLE
 DOCUMENTATION INDICATING THE PRODUCT WAS
 EVALUATED TO BE IN COMPLIANCE WITH THE
 CODE AND THAT THE PRODUCT IS, FOR THE
 PURPOSE INTENDED, AT LEAST EQUIVLENT TO
 THAT REQUIRED BY THE CODE.
 THE REPORT SUBMITTED IS NOT THE
 ORIGINAL, NOT RAISED SEAL NOR ORIGINAL
 SIGNATURE. RULE 9B-72.040(1)(D).
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-03-30 Cont ID  
Sent By jwitmer Date 2005-03-30 Time 16:33 Rev Time 1.11
Received By jwitmer Date 2005-03-30 Time 13:15 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-03-20 Cont ID  
Sent By jwitmer Date 2005-03-20 Time 08:22 Rev Time 0.25
Received By jwitmer Date 2005-03-20 Time 08:21 Sent To PC
Notes
2005-03-20 00:00:00SHEET A2- ELEVATION & FOOTER CHANGEJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-14 Cont ID  
Sent By jwitmer Date 2005-03-14 Time 14:54 Rev Time 1.22
Received By jwitmer Date 2005-03-14 Time 14:53 Sent To PC
Notes
2005-03-14 00:00:00BUILDING PROVISO:
 1026.5.1
 EXTERIOR GAURDRAILS 42"

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-12 Cont ID  
Sent By jwitmer Date 2005-03-12 Time 08:02 Rev Time 2.22
Received By jwitmer Date 2005-03-12 Time 07:54 Sent To PC
Notes
2005-03-12 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010021
 ADD: 201 PALMETTO LANE
 CONT:STERLING COMMUNITIES
 TEL: (561)239-9740
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) ONLY (1) SIGNED & SEALED SOILS REPORT
 SUBMITTED
  
 3) EXTERIOR RAILINGS TRUETHERE IS A
 EXCEPTION IN 1026.5.1 FOR 36" HIGH
 GAURDRAILS FOR DWELLING, HOWEVER THE
 EXCEPTION IS FOR "WITHIN" THE DWELLING
 UNITOTHERWISE A 42"HIGH GAURDRAIL IS
 REQUIRED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
 .
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-01 Cont ID  
Sent By jwitmer Date 2005-02-01 Time 13:50 Rev Time 2.22
Received By jwitmer Date 2005-02-01 Time 13:50 Sent To PC
Notes
2005-02-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05010021
 ADD: 201 PALMETTO LANE
 CONT: STERLING COMMUNITIES
 TEL: (561)239-9740
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION:DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN
 QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE
 EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) SHEET A-1 STRUCTURAL NOTES UPDATE
 ACI-99 TO ACI-02, ACI 530/ASCE 5/TMS
 402-99 TO 402-02, ACI 530/ASCE 6/ TMS
 602-99 TO 602-02.
  
 4) SHEET A-3, A-4, FL BLD CODE
 2405.2.1(2) HAZARDOUS LOCATION PROVIDE
 SAFETY GLASS FOR THIS LOCATION:
 A) MASTER BATH TUB
 B) MASTER BATH SHOWER
 C) BATH# 2
 D) BATH# 4
  
 5) SHEET A-6 DETAIL 2, A-7 & A-8 BOTH
 INDICATE THE USE OF A 36" GAURDRAIL,
 1015.2 HEIGHT. GUARDRAILS SHALL FORM A
 VERTICAL PROTECTIVE BARRIER NOT LESS
 THAN 42" HIGH.
  
 6)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) RADIUS HEAD FRONT DOOR
 B) EXTERIOR RAILINGS
 BOTH THE ABOVE MENTIONED SHALL REQUIRE:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7)1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 8) SHEET E-1 MASTER BEDROOM HALL, NO
 SMOKE DETECTOR INDICATED COMPLY WITH :
 905.2.1 APPROVED SINGLE-STATION OR
 MULTIPLE STATION SMOKE DETECTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 CHAPTER 2, WITHIN EVERY DWELLING UNIT
 WITHIN AN APARTMENT HOUSE, CONDOMINIMUM,
 OR TOWNHOUSE AND EVERY GUEST OR SLEEPING
 ROOM IN A MOTEL, HOTEL, OR DORMITORY &
 SLEEPING ROOMS IN RESIDENTIAL CARE/
 ASSISTED LIVING OCCUPANCIES. WHERE MORE
 THAN ONE DETECTOR IS REQUIRED TO BE
 INSTALLED WITHIN INDIVIDUAL DWELLING
 UNIT, THE DETECTOR SHALL BE WIRED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE
 ALARM WILL ACTIVATE ALL THE ALARMS IN
 THE INDIVIDUAL UNIT.
  
 9)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2006-03-07 Cont ID  
Sent By dpalmer Date 2006-03-07 Time 19:24 Rev Time 0.00
Received By dpalmer Date 2006-03-07 Time 18:59 Sent To PC
Notes
2006-03-07 00:00:00REDLINED VA FOR SM APPLIANCE, TO BE
 1.5KW. 220.16

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2006-02-24 Cont ID  
Sent By dpalmer Date 2006-02-24 Time 11:30 Rev Time 0.00
Received By dpalmer Date 2006-02-24 Time 10:45 Sent To PC
Notes
2006-02-24 00:00:00*** UNSAT ***
  
  
 ** PLEASE KNOW, ARCHITECT HAS BEEN
 CONTACTED ON 2/24/06 AND COMMENTS WERE
 GONE OVER IN ORDER TO ALLEAVIATE ANY
 QUESTIONS, OR CONCERNS OVER THE
 CORRECTIONS AND WHAT IS NEEDED.
  
 1)NOTE: PLEASE SEE RISER METER MAIN NOW
 DOES NOT INDICATE ANY OCP FOR EACH OF
 THE TWO PANELS?
 PLEASE SHOW.215.5,240.4,310.16 ETC
  
 2)NOTE: PLEASE SEE MISSING EGRESS LTS,
 LOGGIA, ENTRY, PLEASE KNOW, SOME SORT OF
 FIXTURE IS REQUIRED. LS 101 7.8, NEC
 210.70
  
 3)NOTE: PLEASE SEE THE DEDICATED BATHS
 ARE NOW SHOWN AS 15A, WHERE CODE
 REQUIRES A MIN OF 20A #12. 210.11C3
  
 4)NOTE: PLEASE SEE LAUNDRY CIRCUIT NOW
 INDICATES1200 VA FOR LOAD. PLEASE SEE
 220.16, WHICH REQUIRES A MIN OF 1500VA.
  
 PLEAS ESUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2006-01-30 Cont ID  
Sent By dpalmer Date 2006-01-30 Time 20:18 Rev Time 0.00
Received By dpalmer Date 2006-01-30 Time 19:51 Sent To B
Notes
2006-01-30 00:00:00********** UNSAT ************
  
  
  
 1)NOTE: PLEASE CORRELATE RISER, PLANS
 AND PANEL SCHEDULES SUBMITTED, PLEASE
 SEE THERE ARE NUMEROUS ITEMS WHICH DO
 NOT MATCH.
  
 A) PLEASE SEE RISER SHOWS A PANEL "C",
 HOWEVR NO PANEL SCHEDULE WAS SUBMITTED
 FOR THIS AND THIS IS NOT SHOWN ON PLANS?
  
 B)PLEASE SEE WHAT APPEARS TO INDICATE A
 400A SERVICE NOW WITH METER MAIN, SHOWS
 TWO-200A BRKRS, BUT ALSO SHOWS FEED THRU
 LUGS FOR ONE?? ETC???
  
 C)PLEASE SEE A POOL PANEL IS SHOWN ON
 RISER BUT NOT ON PLANS. PLEASE SEE A
 POOL PUMP IS SHOWN ON PANEL "B"?? VERIFY
 OF POOL PUMP IS NOT FED FROM POOL PANEL.
  
 D)PLEASE SEE NOW SERVICE INDICATES TO
 FPL HAN-HOLE, PLEASE SEE SEC'S SHALL BE
 SIZED PER 310.15B6 (MIN) AND SHALL BE
 SHOWN ON PLANS.
 PLEASE SEE 1-SET OF 2/0'S ARE SHOWN
 WHICH WAS FOR OLD 200A SERVICE. PLEASE
 SEE A MIN OF PARALLEL OR 400MCM IS
 REQUIRED.
  
 E)PLEASE SEE MIN GROUNDING ELECTRODE
 CONDUCTOR SHALL NOW BE SIZED PER 250.66
 AS SEC'S AND SERVICE IS NOW CHANGED TO
 400A'S ETC.
  
 F)PLEASE SUBMIT PANEL SCHEDULES FOR ALL
 MISSING PANELS.
  
 G)PLEASE SEE PANEL "A" IS SHOWN AS MLO,
 WHEN THIS IS ALSO SHOWN AS MCB ON
 RISER??
  
 ABOVE PER 215.5
  
 2)NOTE: PLEASE SEE MISSING SD ON PLANS
 PER NFPA-72 11.5.1.1,OUTSIDE BEDRM 2ND
 FLR.
 PLEASE ALSO SEE SD IN MASTER BEDRM SHALL
 BE LOCATED A MIN OF 3' FROM THE PEAK OF
 A VAULTED CEILING.
 11.8.3.5
  
 3)NOTE: PLEASE SEE MIN CLEARENCE PER
 110.26 FOR CU#1
  
 PLEASE REVISE AND CORRELATE THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-06-27 Cont ID  
Sent By dpalmer Date 2005-06-27 Time 08:01 Rev Time 0.10
Received By dpalmer Date 2005-06-27 Time 08:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status N Date 2005-05-11 Cont ID  
Sent By dpalmer Date 2005-05-11 Time 11:16 Rev Time 0.00
Received By dpalmer Date 2005-05-11 Time 11:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-04-14 Cont ID  
Sent By dpalmer Date 2005-04-14 Time 17:34 Rev Time 0.25
Received By dpalmer Date 2005-04-14 Time 17:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-03-31 Cont ID  
Sent By dpalmer Date 2005-03-31 Time 09:29 Rev Time 0.30
Received By dpalmer Date 2005-03-31 Time 09:29 Sent To M
Notes
2005-03-31 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE "PROVISO/REDLINED"
 FROM PREVOUS REVIEW.
 PLEASE CORRELATE AHU'S FROM MECH PLANS
 WITH ELECTRICAL PANEL SCHEDULE/LOAD
 CALCS.
 PLEASE SEE MECH PLANS SHOWS 1-10KWA,
 2-7.5KW AND ELECTRICAL SHOWS 1-10KW,
 1-5KW AND 1-6KW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-03-01 Cont ID  
Sent By dpalmer Date 2005-03-01 Time 17:53 Rev Time 0.50
Received By dpalmer Date 2005-03-01 Time 17:39 Sent To P
Notes
2005-03-01 00:00:00******** PROVISO/ NOTES REDLINED ****
  
  
 1)NOTE: PLEASE CORRELATE ELECTRICAL
 PLANS WITH MECHANICALFOR AHU HEAT
 STRIPS.
 PLEASE SEE MECHANICAL PLANS INDICATE :
 ONE 10KW AND TWO 7.5KW UNITS.
 ELECTRICAL PLANS INDICATE ONE 10KW , ONE
 5KW AND ONE 6KW.
 PLEASE SEE LOAD CALCULATIONS FOR THIS
 WILL ALSO NEED TO BE ADJUSTED.
 IF LARGER OF THE UNITS ARE INSTALLED, A
 200A SERVICE IS STILL OK.
  
 2)NOTE: PLEASE SEE DISCONNECT'S FOR
 AHU'S AND CU REDLINED PER 110.26. TO BE
 FIELD VERIFIED.
  
 PLEASE SUBMIT REVISED PLANS FOR NOTE #1
 ALONG WITH ANY OTHER POSSIBLE REVISIONS
 BEFORE ELECTRICAL ROUGH INSPECTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-14 Cont ID  
Sent By dpalmer Date 2005-01-14 Time 16:05 Rev Time 1.00
Received By dpalmer Date 2005-01-14 Time 15:01 Sent To M
Notes
2005-01-14 00:00:00************* UNSAT ****************
  
 1)NOTE; PLEASE CLARIFY SERVICE. SHOWN AS
 400A METER MAIN COMBO , YET IT SEEMS
 SERVICE ONLY FEEDS A 200A DISC AND THEN
 PANEL? PLEASE ALSO SEE SEC'S ARE ONLY
 SHOWN AS 2/0'S FOR A 200A RATED
 SERVICE?
 IF INDEED A METER MAIN , PLEASE INCLUDE
 ANY BRKRS AND /OR BRKRS IN MM.
 IF INDEED 400A, PLEASE SEE 310.15B6
 215.5
  
 2)NOTE: PLEASE SEE 210.52 FOR SOME
 MISSING RECEPTS REQUIRED.
  
 3)NOTE: PLEASE SEE GARAGE DOOR OPENERS
 EACH SHOWN ON 2-P 30A BRKRS?
 MISPRINT?
  
 4)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN
 COUNTERSPACE RECEPTS MISSING.
 210.8A6
  
 5)NOTE: PLEASE ADD SD IN HALL OUTSIDE
 BEDRM AS DOOR BETWEEN BEDRM AND OUTER
 HALL BLOCKS PROTECTION.
 NFPA-72
  
 6)NOTE: PLEASE SEE IF 400A SERVICE, THEN
 SIZE GROUNDING ELECTRODE CONDUCTOR PER
 250.66. 1/0 MIN
  
 PLEASE SEE ONE SET OF PLANS HAS MOST OF
 THESE THINGS REDLINED FOR AREAS OF
 CONCERN.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-03-03 Cont ID  
Sent By adarroug Date 2006-03-03 Time 08:53 Rev Time 0.00
Received By adarroug Date 2006-03-03 Time 08:53 Sent To E
Notes
2006-03-03 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-02-21 Cont ID  
Sent By adarroug Date 2006-02-21 Time 09:04 Rev Time 0.00
Received By adarroug Date 2006-02-21 Time 09:04 Sent To E
Notes
2006-02-21 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-01-23 Cont ID  
Sent By adarroug Date 2006-01-23 Time 13:10 Rev Time 0.00
Received By adarroug Date 2006-01-23 Time 13:10 Sent To E
Notes
2006-01-23 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-01-13 Cont ID  
Sent By adarroug Date 2006-01-13 Time 11:06 Rev Time 0.00
Received By adarroug Date 2006-01-13 Time 11:06 Sent To B
Notes
2006-01-13 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-01-12 Cont ID  
Sent By adarroug Date 2006-01-12 Time 15:13 Rev Time 0.00
Received By adarroug Date 2006-01-12 Time 15:13 Sent To B
Notes
2006-01-12 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-12-12 Cont ID  
Sent By adarroug Date 2005-12-12 Time 19:06 Rev Time 0.00
Received By adarroug Date 2005-12-12 Time 19:06 Sent To B
Notes
2005-12-12 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-06-21 Cont ID  
Sent By adarroug Date 2005-06-21 Time 14:48 Rev Time 0.00
Received By adarroug Date 2005-06-21 Time 14:48 Sent To E
Notes
2005-06-21 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-09 Cont ID  
Sent By adarroug Date 2005-05-09 Time 11:24 Rev Time 0.00
Received By adarroug Date 2005-05-09 Time 11:24 Sent To E
Notes
2005-05-09 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-04-11 Cont ID  
Sent By adarroug Date 2005-04-11 Time 11:48 Rev Time 0.00
Received By adarroug Date 2005-04-11 Time 11:48 Sent To E
Notes
2005-04-11 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-03-25 Cont ID  
Sent By adarroug Date 2005-03-25 Time 08:13 Rev Time 0.00
Received By adarroug Date 2005-03-25 Time 08:13 Sent To B
Notes
2005-03-25 00:00:00TO "JWITMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-17 Cont ID  
Sent By adarroug Date 2005-03-17 Time 10:53 Rev Time 0.00
Received By adarroug Date 2005-03-17 Time 10:53 Sent To B
Notes
2005-03-17 00:00:00TO "JWITMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 10:42 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 10:42 Sent To E
Notes
2005-02-28 00:00:00TO "DPALMER"DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-13 Cont ID  
Sent By mjacobs Date 2005-01-13 Time 15:26 Rev Time 0.00
Received By mjacobs Date 2005-01-13 Time 15:26 Sent To E
Notes
2005-01-13 00:00:00TO 'E" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 10:13 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 10:13 Sent To Z
Notes
2005-01-06 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2005-04-07 Cont ID  
Sent By prafter Date 2005-04-07 Time 11:23 Rev Time 0.00
Received By prafter Date 2005-04-07 Time 11:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2005-03-09 Time   Rev Time 0.00
Received By hmoser Date 2005-03-09 Time 18:28 Sent To B
Notes
2005-03-09 00:00:001) MEED RETURN AIR IN DINNING ROOM
 2)REFER TO SECTION 610.1 ABC.3.5.2
 FLORIDA BUILDING CODE CHAPTER 13.NOTICE
 TO HOMEOWNER.REFERRING TO AIRHANDLERS 2
 & 3
 3) REFER TO SECTION 610.1.ABC.3.5.2 #1
 THE SERVICE PANEL OF THE EQUIPMENT IS
 LOCATED WITHIN 6FT.OF AN ATTIC ACCESS
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-20 Cont ID  
Sent By kstevens Date 2005-03-08 Time 08:16 Rev Time 2.00
Received By prafter Date 2005-01-20 Time 11:41 Sent To B
Notes
2005-01-20 00:00:001. RETURN AIR DUCT FOR A.H.U. #1
 SHOULD BE EQUEAL TO SUPPLY AIR DUCT
 CONBINE , 314 SQ. IN. TO RETURN AIR DUCT
 OF 201 SQ. IN. OF AREA.
 RETURN AIR GRILL IS SOME WHAT SMALL
 FOR THE SIZE OF A.H.U. . 2003 FBC/M
 601.4 .
 2. RETURN AIR DUCT OUT OF SECOND FLOOR
 BEDROOMS SHOULD BE ONE AND HALF LARGER
 THAN SUPPLY AIR DUCT.2003 FBC/M
 EXCEPTION #1 .
 3.HALL WAY RETURN AIR GRILL MUST
 COMPLY WITH 2003 FBC/M 601.4 EXCEPTION
 #2 FOR SIZE.
 4. SUPPLY AIR DUCT LEADING TO BEDROOM
 #3 AND #4 SHOULD BE LARGER THAN
 REFLECTED ON PLAN. (4")
 5. CONDENSATE FROM A.H.U. MUST CONFORM
 WITH 2003 FBC/M 307.2.3 .FOR AUX. DRAIN
 PANS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-03-08 Cont ID  
Sent By kstevens Date 2005-03-05 Time 08:16 Rev Time 0.00
Received By kstevens Date 2005-03-05 Time 08:15 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-19 Cont ID  
Sent By jleech Date 2005-01-19 Time 11:15 Rev Time 0.33
Received By jleech Date 2005-01-19 Time 11:15 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-13 Cont ID  
Sent By mmclean Date 2005-01-13 Time 12:40 Rev Time 0.00
Received By mmclean Date 2005-01-13 Time 12:40 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved