| Plan Review Stops For Permit 04121980 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2005-12-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-12-29 |
Time |
18:49 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2005-12-29 |
Time |
18:49 |
Sent To |
PC |
|
| Notes |
| 2005-12-29 00:00:00 | BUILDING REVISION CHECKLIST: | | | 1- KEY PLAN STILL DOESN'T MATCH FLOOR | | | PLAN. REVISE AS REQUIRED. SEE FLOOR | | | PLAN. | | | | | | 2- PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE ATTACHED INSTALLATION | | | SCHEDULE SAMPLE THAT SUMMARIZES | | | INFORMATION REQUIRED FOR PLAN REVIEW. | | | PROVIDE ALL INFORMATION TO EXPEDITE | | | REVIEW. IT ALSO FACILITATES INSPECTIONS. | | | | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2005-11-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-11-14 |
Time |
17:39 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2005-11-14 |
Time |
17:56 |
Sent To |
PC |
|
| Notes |
| 2005-11-14 00:00:00 | BUILDING SUBMITTAL CHECKLIST: | | | 1- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR WINDOW MULLIONS THAT MEET | | | THE DESIGN PRESSURES CALCULATED BY THE | | | ARCHITECT. WINDOW MULLION PRODUCT | | | APPROVAL SUBMITTED DON'T RESIST THE | | | DESIGN PRESSURES CALCULATED IN PLANS. | | | | | | 2- STORM SHUTTERS INFORMATION WAS | | | SUBMITTED ON 8-12-05. IT WAS REJECTED | | | BECAUSE IT WAS A REVISION AND | | | INFORMATION WAS NOT COMPLETE. SEE COPY | | | OF COMMENTS DATED 9-20-05. RESUBMIT AND | | | PAY REVISION FEES AS REQUIRED. | | | | | | NOTE: | | | REVISED SHEET A-6 AND STEEL HEADER | | | DETAIL ARE APPROVED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2005-09-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-09-20 |
Time |
16:52 |
Rev Time |
0.33 |
| Received By |
jgomez |
Date |
2005-09-20 |
Time |
16:52 |
Sent To |
PC |
|
| Notes |
| 2005-09-20 00:00:00 | SUBMITTAL BUILDING REVIEW CHECKLIST: | | | 1- SHUTTERS INFORMATION SUBMITTED IS | | | DIFFERENT FROM INFORMATION SUBMITTED AT | | | TIME OF PRINTING PERMIT. THIS IS A | | | REVISION AND REVISION FEES APPLY. | | | | | | 2- PROVIDE COMPLETE INFORMATION FOR | | | STORM SHUTTERS INCLUDING INSTALLATION | | | SCHEDULE (SEE ATTACHED SAMPLE FOR REQ'D | | | MIN. INFORMATION).ALSO, INDICATE ON | | | DRAWINGS SPECIFIC MOUNTING CONDITIONS | | | AND ANCHOR TYPE AND SPACING TO BE USED | | | ACCORDING TO THE DESIGN PRESSURES, EDGE | | | DISTANCE, PANEL SPAN, CONNECTION TYPE | | | AND STRUCTURE TO BE ATTACHED TO | | | (CONCRETE OR CONCRETE BLOCK). | | | | | | 3- PROVIDE INFORMATION REQUESTED ON | | | PROVISO DATED 8-2-05. SEE ATTACHED COPY. | | | | | | JULIO GOMEZ | | | PLANS EXAMINER | | | (561)805-6712. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-08-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-08-02 |
Time |
13:50 |
Rev Time |
2.50 |
| Received By |
jgomez |
Date |
2005-08-02 |
Time |
13:50 |
Sent To |
PC |
|
| Notes |
| 2005-08-02 00:00:00 | BUILDING REVIEW PROVISO: | | | 1- DESIGNER OF RECORD TO SPECIFY ON | | | PLANS ROOF TILE FASTENING AS REQUIRED BY | | | SEC. 104.2.1.1 CITY AMENDMENTS TO FBC. | | | 2- ANCHOR SCHEDULE: A)REVISE FASTENERS | | | FOR THD210 CONNECTOR. SEE TECHNICAL | | | BULLETIN. | | | B) CONNECTOR G: PROVIDE TESTING AND | | | ENGINEERING CALCS FOR NUMBER/TYPE OF | | | NAILS THAT DIFFER TO THOSE TESTED AND | | | PUBLISHED BY THE MANUFACTURER. SEC. | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | **NAIL CALCS SHOWN ON SHEET A-6 ARE FOR | | | 10D NAILS ONLY. THEY DON'T APPLY TO 16D. | | | WHAT CRITERIA IS USED WHEN REDUCING THE | | | NUMBER OF NAILS. EG: SEE PAGE 17 OF USP | | | BOOK FOR LOADS REDUCTION (SIMPSON HAS AN | | | EQUATION ON PAGE 137 OF 2005 CATALOGUE). | | | 3- SPECIFY SIZE AND ANCHORS FOR WINDOW | | | MULLIONS AT LIVING ROOM FIXED WINDOWS TO | | | VERIFY DESIGN PRESSURES COMPLIANCE. SEE | | | PRODUCT APPROVAL FOR SIZE LIMITATIONS. | | | 4-STORM SHUTTERS: REVISE KEY PLAN AND | | | INSTALLATION SCHEDULE TO MATCH FLOOR | | | PLAN AND RE-SUBMIT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-05-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-05-12 |
Time |
13:36 |
Rev Time |
2.00 |
| Received By |
jgomez |
Date |
2005-05-12 |
Time |
12:23 |
Sent To |
Z |
|
| Notes |
| 2005-05-12 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- DESIGNER OF RECORD TO SPECIFY ROOF | | | TILE FASTENING AS REQUIRED BY SECTION | | | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. | | | | | | 2-UPDATE TRUSS ANCHOR SCHEDULE. SEE | | | LATEST CATALOGUE THAT WAS REVISED TO | | | COMPLY WITH SECTION 1609.4.3 FBC 2001. | | | OTHERWISE, PROVIDE COMPLETE ENGINEERING | | | CALCS FOR FASTENER TYPE AND NUMBER THAT | | | DIFFER FROM THOSE TESTED AND PUBLISHED | | | BY THE MANUFACTURER. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | | | | 3- ELEVATIONS CALL FOR FLAT TILE. | | | PRODUCT APPROVAL SUBMITTED WAS FOR "S" | | | TILE. REVISE AS REQUIRED. | | | | | | 4- INSURANCE WILL EXPIRE ON 5-27-05. | | | PLEASE, UPDATE INFORMATION AT TIME OF | | | SUBMITTAL TO AVOID ANY DELAYS. | | | | | | 5- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR FRENCH DOORS WITH | | | SIDELITES. PRODUCT SUBMITTED ARE FOR | | | 6'-8" DOORS. NEED 8'-0" HEIGHT DOORS. | | | | | | 6- OWES $949.68 FOR UPDATE VALUE AND | | | RADON FEES. AND, FOR ADDED A/C AREA. | | | | | | 7- DETAIL 2/A-9:PROVIDE SPECS FOR "U" | | | STRAP TO BE USED. SEC. 104.2.1 CITY | | | AMENDMENTS TO FBC 2001. | | | | | | 8- DESIGN PARAMETERS ON SHEET A-3: | | | SPECIFY/CLARIFY WHERE IS THE BASIC | | | VELOCITY PRESSURE TAKEN FROM?. THERE ARE | | | NOT TABLES ON CHAPTER 16 FBC 2001 | | | SHOWING THIS VALUES. | | | | | | 9- LEFT SIDE ELEVATION DON'T MATCH FLOOR | | | PLAN. NEED TO SHOW MASTER BEDROOM | | | SITTING AREA. REVISE AS REQUIRED. | | | | | | 10- REVISE FRONT ELEVATION TO SHOW STEEL | | | DOOR AS PER PRODUCT APPROVAL SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-01-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-01-27 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2005-05-12 |
Time |
11:27 |
Sent To |
PC |
|
| Notes |
| 2005-01-27 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- PROVIDE COMPLETE BATHROOM WITH DOOR | | | THAT ALLOWS 29" MIN. CLEAR OPENING. | | | SECTION 11-11 FBC 2001. | | | | | | 2- SPECIFY ROOF TILE FASTENING. SECTION | | | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. | | | | | | 3- UPDATE TRUSS ANCHOR SCHEDULE. PROVIDE | | | COMPLETE ENGINEERING CALCULATIONS FOR | | | TYPE AND NUMBER OF FASTENERS THAT DIFFER | | | FROM THOSE TESTED AND PUBLISHED BY THE | | | MANUFACTURER TO COMPLY WITH SECTION | | | 1609.4.3 FBC 2001. | | | | | | 4- A) TITLE BLOCK NEEDS NAME OF | | | ARCHITECT SEALING THE PLANS. CHAPTER | | | 61G1-16004 F.A.C. | | | B) STATE REGISTRATION NUMBER IS | | | INCORRECT. REVISE AS REQUIRED. | | | | | | 5- PROVIDE COMPLETE DETAIL/SPECS FOR | | | CEILING INSTALLATION AT ENTRY AND REAR | | | PORCHES. SEE ASTM C926 AND ASTM C1063. | | | SECTION 2504.2 FBC 2001. | | | | | | 6- ENERGY CALCS NEED TO BE SIGNED AND | | | DATED BY THE OWNER/AGENT. | | | | | | 7- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR: | | | A) ENTRY DOORS. | | | B) FRENCH DOORS. SEE SIZES ON PLANS. | | | C) CONCRETE LINTELS: NEED DADE COUNTY | | | NOA THAT MATCHES ONE SUBMITTED FOR | | | FLORIDA PRODUCT APPROVAL. | | | D) FIXED WINDOWS THAT MEET THE DESIGN | | | PRESSURES CALCULATED ON PLANS. SEE PLANS | | | FOR SIZES AND DESIGN PRESSURES. | | | E) ARABESQUE WINDOW. SEE PLANS. | | | | | | 8- A) PROVIDE COMPLETE UL LISTING AND | | | SPECS FOR FIREPLACE. SEC. 2806 FBC | | | 2001. | | | B) PROVIDE APPROVED BBQ SPECS AS REQ'D | | | BY SECTION 2808 FBC 2001. | | | | | | 9- STORM SHUTTERS: A) KEY PLAN DOESN'T | | | MATCH PLANS. | | | B) REVISE MIN. PANEL SIZE. SEE | | | ENGINEERED DRAWINGS FOR LIMITATIONS. | | | C) REVISE INTERIOR AND END ZONES. SEE | | | PLANS FOR LOCATION OF OPENINGS. | | | D) REVISE DESIGN PRESSURES. SEE PLANS. | | | | | | 10- PROVIDE COMPLETE FRAMING DETAILS FOR | | | ARABESQUE WINDOW. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | | | | 11- OWES $866.23 FOR UPDATED VALUATION. | | | | | | 12- REVISE FOUNDATION NOTE #2 ON SHEET | | | A-2. SEE CHAPTER 19 FBC 2001 FOR PROEPR | | | ACI REFERENCE TO BE USED. | | | | | | 13- REVISE CONNECTORS SHOWN ON DETAIL | | | 2/A-9. "SEMCO" IS OUT OF BUSINESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2006-03-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-03-20 |
Time |
07:03 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-03-20 |
Time |
06:31 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2005-12-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-12-22 |
Time |
14:10 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-12-22 |
Time |
13:33 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-07-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-07-11 |
Time |
10:16 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-07-11 |
Time |
07:25 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-04-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-04-26 |
Time |
12:05 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-04-26 |
Time |
10:43 |
Sent To |
P |
|
| Notes |
| 2005-04-26 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} INDICATE THE LOCATION OF PANEL "B". | | | | | | 2} INDICATE LOCATION OF OVERCURRENT | | | PROTECTION FOR PANELS "A" & "B". | | | | | | 3} THE OCP FOR CIRCUITS 12,13 PANEL "A", | | | 12,13,14,15 PANEL "B" IS TOO LARGE FOR | | | THE CONDUCTORS PER 210.16. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-01-07 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-01-07 |
Time |
13:54 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-01-07 |
Time |
13:53 |
Sent To |
M |
|
| Notes |
| 2005-01-07 00:00:00 | | | | | | | .PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE OVERCURRENT PROTECTION FOR AHU | | | #2 AT 60 AMPS IS TOO LARGE TO PROTECT A | | | 5KW UNIT.(5000X125%/240=26 AMPS, MAX 30 | | | AMP OCP). ALSO 60 AMP OCP SHOWN INTHE | | | MAIN PANEL SEEM TOOLARGE FOR THE | | | CONDENSING UNIT. SEE ARTICLE 440.22 | | | NEC. | | | | | | 2} THERE ARE NO PROVISIONS IN THE | | | CALCULATIONS FOR POOL EQUIPMENT, BUT | | | THERE IS EQUIPMENT SHOWN ON THE PLAN. | | | | | | 3} IF NOTE #15 IS ADHERED TO, THOSE | | | CIRCUITS WOULD HAVE TO BE PROTECTED BY | | | AN AFCI BECAUSE THE DETECTORS ARE | | | LOCATED IN BEDROOMS. 210.12. | | | | | | 4} THE GFI'S SHOWN IN THE DINING ROOM | | | AND BREAKFAST NOOK, WHILE NOT REQUIRED | | | ALTHOUGH PERMISSIBLE, MUST BE INSTALLED | | | IF LEFT ON THE PLAN. | | | | | | 5} A RECEPTACLE NEEDS TO BE ADDED TO | | | THE MASTER BEDROOM TO COMPLY WITH | | | 210.52(A). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-03-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-17 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-17 |
Time |
14:59 |
Sent To |
E |
|
| Notes |
| 2006-03-17 00:00:00 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-12-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-16 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-16 |
Time |
16:43 |
Sent To |
E |
|
| Notes |
| 2005-12-16 00:00:00 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-10-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-07 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-07 |
Time |
16:34 |
Sent To |
B |
|
| Notes |
| 2005-10-07 00:00:00 | TO "JGOMEZ" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-08-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-16 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-16 |
Time |
08:23 |
Sent To |
B |
|
| Notes |
| 2005-08-16 00:00:00 | TO "JGOMEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-07-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-08 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-08 |
Time |
16:23 |
Sent To |
E |
|
| Notes |
| 2005-07-08 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-04-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-25 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-25 |
Time |
10:32 |
Sent To |
B |
|
| Notes |
| 2005-04-25 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-01-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-06 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-06 |
Time |
07:38 |
Sent To |
E |
|
| Notes |
| 2005-01-06 00:00:00 | TO "SFD" RACK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-01-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-03 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-03 |
Time |
12:08 |
Sent To |
Z |
|
| Notes |
| 2005-01-03 00:00:00 | TO "Z" BOX. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-01-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-01-07 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
prafter |
Date |
2005-01-11 |
Time |
13:36 |
Sent To |
B |
|
| Notes |
| 2005-01-11 00:00:00 | NO A/C PLANS. | | | PAT RAFTER 561/805/6725 OR 8056719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2005-08-01 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-08-01 |
Time |
07:23 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2005-08-01 |
Time |
07:22 |
Sent To |
B1 |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-05-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-05-09 |
Time |
06:41 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-05-09 |
Time |
06:41 |
Sent To |
B |
|
| Notes |
| 2005-05-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT A-7 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS: | | | A. THE FUTURE SINK ON THE PATIO DOES | | | NOT SHOW THE STUB OUT ABOVE THE SLAB, | | | SHOULD SHOW A RISER. ALSO THE SINK DOES | | | NOT SHOW A VENT. SECTIONS 104.2.1. & | | | 901.2.1. | | | B. DOUBLE SANITARY TEE PATTERNS SHALL | | | NOT RECIEVE THE DISCHARGE OF APPLIANCES | | | WITH PUMPING ACTION DISCHARGE. THE WASH | | | MACHINE SHALL CONNECT DOWNSTREAM OF THE | | | LAUNDRY SINK. SECTION 706.3 | | | C. THE CLEANOUT ON THE WASH MACHINE | | | STACK SHALL BE A MINIMUM OF 4' ABOVE THE | | | FLOOR FOR ACCESS. SECTION 708.10. | | | D. SEE RED LINE EXAMPLES OF CORRECT | | | PIPING/VENT/CLEANOUT ON A-7 SHEET. | | | 2) AS REQUIRED BY 104.3.1.1 OF THE CODE, | | | TWO OR MORE COPIES OF DRAWINGS ARE | | | REQUIRED. LOOSE SHEETS ARE NOT APPROVED, | | | PLEASE STAPLE SETS OF PLANS TOGETHER. | | | SECTIONS 104.2.1 & 104.2.1.3. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2005-01-10 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-01-10 |
Time |
18:58 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2005-01-10 |
Time |
18:58 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-05-13 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-05-13 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-05-13 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2005-05-13 00:00:00 | APPROVED RE-SUB. MUST PULL SEPERATE | | | PERMIT FOR POOL/SPA/DECK/SCREEN | | | ENCLOSURE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-01-05 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-01-05 |
Time |
17:45 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-01-05 |
Time |
17:45 |
Sent To |
I |
|
| Notes |
| 2005-01-05 00:00:00 | MUST PULL SEPERATE PERMIT FOR POOL/DECK |
|
|