Plan Review Details - Permit 04121974
Plan Review Stops For Permit 04121974
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-27 Cont ID  
Sent By alange Date 2005-09-27 Time 13:26 Rev Time 1.66
Received By alange Date 2005-09-27 Time 11:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-08 Cont ID  
Sent By alange Date 2005-08-08 Time 11:18 Rev Time 0.75
Received By alange Date 2005-08-08 Time 10:55 Sent To Z
Notes
2005-08-08 00:00:00DENIED
  
 1.BASED ON SBCCI BUILDING VALUATION
 DATA THE VALUE HAS BEEN CHANGED TO
 $344,615.ADDITIONAL PERMIT FEES OF
 $1046.13 ARE DUE PRIOR TO RESUBMITTING
 PLANS.
 SEE APPLICATION FOR COST BREAKDOWN.
  
 3.PLEASE SUBMIT 2 COPIES OF PRODUCT
 APPROVALS STRAPS AND TIE-DOWNS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-18 Cont ID  
Sent By alange Date 2005-01-18 Time 16:22 Rev Time 1.50
Received By alange Date 2005-01-18 Time 14:43 Sent To  
Notes
2005-01-18 00:00:00DENIED
  
 1.BASED ON SBCCI BUILDING VALUATION
 DATA THE VALUE HAS BEEN CHANGED TO
 $335,607.ADDITIONAL PERMIT FEES OF
 $955.15 ARE DUE.
 SEE APPLICATION FOR COST BREAKDOWN.
  
 2.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 3.PLEASE SUBMIT 2 COPIES OF PRODUCT
 APPROVALS FOR GOLF CART GARAGE DOOR AND
 STRAPS AND TIE-DOWNS.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.FOOTING DETAILS:THESE DETAILS
 SHOW A 12" DEEP FOOTING WITH A GRADE OF
 "APPROXIMATLY" 4".THESE ARE BOTH OK,
 THEY ARE BOTH MINIMUMS AND THIS LEAVES
 NO ROOM FOR ERROR OF GRADE.
 PLEASE REMOVE "APPROXIMATE" FROM PLANS
 AND SHOW AS "MINIMUM" GRADE 4" FROM
 FINISH FLOOR.WPB AMMENDMENT TO THE
 FBC
 1804.1.7
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-05 Cont ID  
Sent By dpalmer Date 2006-07-05 Time 09:31 Rev Time 0.00
Received By dpalmer Date 2006-07-05 Time 09:31 Sent To PC
Notes
2006-07-05 00:00:00REVISED RISER , PANELS, AND PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-14 Cont ID  
Sent By dpalmer Date 2005-07-14 Time 19:49 Rev Time 0.30
Received By dpalmer Date 2005-07-14 Time 19:49 Sent To P
Notes
2005-07-14 00:00:00REDLINED:
 POSSIBLE RECEPT FOR BEDRM #2, 210.52
 CONTINUOUS LOAD (125%) FOR POOL PUMP.
 REDLINED GROUNDING ELECTRODE CONDUCTOR
 TO BE A MIN OF 1/0. 250.66,310.15B6
  
 NO NEED FOR CORRECTIONS, OR REVISIONS,
 HOWEVER IF PLANS COME BACK IN WITH ANY
 OTHER REVISIONS, PLEASE ADJUST AT THAT
 TIME.
  
  
  
 **PLANS ROUTED TO PLUMB, AS NEW PLUMBING
 SHEETS WERE IN SETS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By dpalmer Date 2005-01-07 Time 14:13 Rev Time 0.30
Received By dpalmer Date 2005-01-07 Time 14:13 Sent To M
Notes
2005-01-07 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN
 COUNTERSPACE GFI RECEPTS.
  
 2)NOTE: PLEASE SEE HI-HAT LOAD SHOWN AT
 48.0KW. PLEASE SEE 64@75W EACH.
 PLEASE SEE THIS MAY AFFECT SIZE OF
 SERVICE.
  
 3)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR PER 310.15B6,
 250.66
 #2 MIN. (IFF 300A SERVICE REMAINS. )
  
 4)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATESBRKFST NOOK AS GFI. THIS IS
 NOT REQUIRED,, YET PERMITTED. IF SHOWN
 ON PLANS THEN THIS IS REQUIRED TO BE
 DONE.
  
 5)NOTE: PLEASE CORRELATE RISER WITH
 PLANS. PLANS INDICATE METER/MAIN ON
 OUTSIDE OF HOUSE, PANEL IN GARAGE AND
 PANEL IN LAUNDRY RM?
 215.5
  
  
 6)NOTE: PLEASE SEE OCP IS NOT CLEAR ON
 PANEL SCHEDULE/LOAD CALCS FOR AHU 5KE
 HEAT. APPEARS TO BE 50A?
 PLEASE SEE 424.3B 125% MIN AND 150%
 USUALLY MAX. IS THIS 30A OCP?
 PLEASE ALSO SEE RISER SHOWS 60A OCP FOR
 COND UNITS. PLEASE VERIFY THE OCP WITH
 MECH PLANS FOR SIZE OF CU.
  
 7)NOTE: PLEASE SEE 210.52 FOR RECEPT
 LOCATIONS MISSING ON PLANS. BEDRM #2,
 #3, AND DEN.
  
 8)NOTE: PLEASE SEE PLANS INDICATE POOL
 EQUIPMENT, YET THIS IS NOT ON PANEL
 SCHEDULE. IF "FUTURE" PLEASE JUST PLACE
 NOTE ON PLANS FOR "FUTURE".
  
 PLEASE SEE ALL OF THESE ABOVE ITEMS HAVE
 BEEN REDLINED ON ONE SET OF PLANS FOR
 AREAS OF CONCERN.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD SET MAY BE SUBMITTED FOR
 REFERENCE ONLY.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-03 Cont ID  
Sent By adarroug Date 2006-07-03 Time 15:42 Rev Time 0.00
Received By adarroug Date 2006-07-03 Time 15:42 Sent To E
Notes
2006-07-03 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-16 Cont ID  
Sent By adarroug Date 2005-09-16 Time 16:45 Rev Time 0.00
Received By adarroug Date 2005-09-16 Time 16:45 Sent To B
Notes
2005-09-16 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-12 Cont ID  
Sent By adarroug Date 2005-07-12 Time 16:02 Rev Time 0.00
Received By adarroug Date 2005-07-12 Time 16:02 Sent To E
Notes
2005-07-12 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 07:48 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 07:48 Sent To E
Notes
2005-01-06 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 11:53 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 11:53 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-10 Cont ID  
Sent By prafter Date 2005-01-10 Time 15:19 Rev Time 0.45
Received By prafter Date 2005-01-10 Time 15:19 Sent To P
Notes
2005-01-10 00:00:00NO A/C PLANS
 PAT RAFTER 561/805/6725 OR 805/6719 .

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-07-30 Cont ID  
Sent By jleech Date 2005-07-30 Time 07:49 Rev Time 0.25
Received By jleech Date 2005-07-30 Time 07:49 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-11 Cont ID  
Sent By jleech Date 2005-01-11 Time 14:09 Rev Time 0.33
Received By jleech Date 2005-01-11 Time 14:09 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-10 Cont ID  
Sent By mmclean Date 2005-08-10 Time 16:38 Rev Time 0.00
Received By mmclean Date 2005-08-10 Time 16:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-05 Cont ID  
Sent By mmclean Date 2005-01-05 Time 14:21 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 14:21 Sent To I
Notes
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK