| Plan Review Stops For Permit 04121962 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
N |
Date |
2005-09-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-09-02 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-09-02 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2005-09-02 00:00:00 | STORM PANEL REVISION DENIED | | | | | | 1) SPECIFY THE ANCHOR TYPE, CONNECTION | | | TYPE AND EDGE DISTANCE AS REQUIRED BY | | | THE PRODUCT APPROVAL ANCHOR SCHEDULE TO | | | DETERMINE ANCHOR SPACING. | | | | | | 2) ON SHEET 4 OF THE PRODUCT APPROVAL, | | | THE MAXIMUM DESIGN PRESSURE FOR A PANEL | | | SPAN OF 129" IS 39.10 PSF AND ON THE | | | INSTALLATION SCHEDULE SUBMITTED, THE | | | PRESSURE AT OPENING #6 FOR THE 129" | | | SHUTTER SPAN IS 43 PSF. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-03-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-03-22 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-03-22 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2005-03-22 00:00:00 | REVISION TO ENTRY DOOR IS OK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-03-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-03-02 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-03-02 |
Time |
10:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-01-19 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-01-19 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2005-01-19 00:00:00 | DENIED | | | | | | 1) NO OPENINGS ARE ALLOWED IN THE WALL | | | ON THE ZERO LOT LINE PER FBC TABLE 600. | | | REMOVE THE GARAGE VENT ON THE ZERO LOT | | | LINE. | | | | | | 2) SPECIFY ONE HOUR FIRE RATED GLASS | | | BLOCK AT THE ZERO LOT LINE ON THE FLOOR | | | PLAN. | | | | | | 3) THE GLASS BLOCK DETAIL ON A9 | | | INCORRECTLY REFERENCES ASCE 7-88. THE | | | CORRECT REFERENCE IS ASCE 7-98. | | | | | | 4)CHPTER 11 OF THE 2001 FBC REQUIRES AT | | | LEAST ONE FULL BATHROOM WITH A DOOR THAT | | | HAS A 29" CLEAR OPENING. | | | | | | 5) DETAIL 2 ON A9 SPECIFIES "SEMCO" | | | CONNECTORS. SEMCO IS NO LONGER IN | | | BUSNIESS AND DOES NOT HAVE STATE PRODUCT | | | APPROVAL. | | | | | | 6) SPECIFY THE POSITIVE AND NEGATIVE | | | WINDLOAD PRESSURES FOR THE 8' WIDE | | | SLIDING GLASS DOOR. | | | | | | 7) THE OWNER/AGENT IS REQUIRED TO SIGN | | | THE ENERGY CALC. FORM PER FBC CHAPTER | | | 13. | | | | | | 8) SUBMIT MANUFACTURER'S SPECIFICATIONS | | | AND AND LISTING INFORMATION FOR THE BBQ | | | AND PREFAB FIREPLACE. | | | | | | 9) THE KEY PLAN AND INSTALLATION | | | SCHEDULE FOR THE STORM PANELS HAS AN | | | EXTRA WINDOW THAT IS NOT SHOWN ON THE | | | PLANS. THE SINGLE FRENCH DOOR IS SHOWN | | | AS A DOUBLE DOOR ON THE KEY PLAN. | | | | | | 10) SUBMIT STATE/LOCAL PRODUCT APPROVAL | | | FOR THE SINGLE OUTSWING GLAZED FRENCH | | | DOOR AND THE DOUBLE OUTSWING WOOD ENTRY | | | DOORS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2005-08-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-26 |
Time |
18:42 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2005-08-26 |
Time |
18:42 |
Sent To |
|
|
| Notes |
| 2005-08-26 00:00:00 | ELEC OK,STAMPED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2005-07-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-15 |
Time |
21:00 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-07-15 |
Time |
21:00 |
Sent To |
|
|
| Notes |
| 2005-07-15 00:00:00 | STAMPED REV'S. OK |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-05-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-05-18 |
Time |
07:36 |
Rev Time |
0.20 |
| Received By |
dpalmer |
Date |
2005-05-18 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2005-05-18 00:00:00 | ************ UNSAT ************ | | | | | | **PLEASE SEE PLANS AND RISER DIAGRAM | | | HAVE COMPLETELY CHANGED FROM ORIG PLANS. | | | | | | 1)NOTE: PLEASE SEE NEW RISER NOW | | | INDICATES THREE ELECTRICAL PANELS, | | | HOWEVER NO OCP IS SHOWN ON RISER FOR NEW | | | PANELS. | | | IS THERE NOW A PANEL SCHEDULE FOR NEW | | | METER/MAIN COMBO. | | | 215.5,240.4, 310.16 ETC. | | | | | | 2)NOTE: PLEASE SEE ONLY ONE PANEL IS | | | SHOWN ON ELECTRICAL PLANS AND RISER | | | SHOWS 3. | | | 215.5 | | | | | | 3)NOTE: PLEASE SEE NUMEROUS ITEMS ON | | | PANEL SCHEDULE INDICATE 20A OCP ON #14 | | | AWG. PLEASE SEE 310.16,240.4. | | | | | | 4)NOTE: | | | | | | 5)NOTE: PLEASE SEE A JACUZZI/WHIRLPOOL | | | TUB IS NOW ADDED TO PANEL SCHEDULE, | | | HOWEVER NO ELECTRICAL IS SHOWN ON PLANS. | | | PLEASE ALSO SEE 680.71 FOR REQUIRED | | | INDICATION OF GFI PROTECTION. | | | | | | 6)NOTE: PLEASE CORRELATE THE NUMBER OF | | | RECESSED LTS ON PLANS WITH THE # OF | | | RECESSED LTS INDICATED ON PANEL | | | SCHEDULE/LOAD CALCULATIONS. | | | PLEASE SEE SOME MODELS SHOW THESE AS | | | "OPT". EACH PLAN MUST REFLECT THE ACTUAL | | | INSTALLATION PER WHICH ARE INSTALLED OR | | | NOT INSTALLED. | | | 215.5 | | | | | | 7)NOTE: PLEASE SEE MISSING RECEPT | | | REQUIRED IN BATHRM 210.52D. | | | | | | 8)NOTE: PLEASE SEE MISSING GFI ALONG | | | KITCHEN COUNTERSPACE. | | | | | | PLEASE SEE MANY OF THESE ITEMS HAVE BEEN | | | REDLINED AT LOCATIONS ON PLANS AT | | | LOCATIONS OF NOTES. | | | | | | *** PLEASE BE SURE ALL PLANS ARE SIGNED | | | BY THE ARCHITECT OF RECORD. | | | FS 481.025 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-02-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-02-17 |
Time |
08:39 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-02-17 |
Time |
08:10 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-01-07 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-01-07 |
Time |
16:00 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-01-07 |
Time |
16:00 |
Sent To |
M |
|
| Notes |
| 2005-01-07 00:00:00 | | | | | | | | | | .PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE OVERCURRENT PROTECTION FOR AHU | | | #2 AT 60 AMPS IS TOO LARGE TO PROTECT A | | | 5KW UNIT.(5000X125%/240=26 AMPS, MAX 30 | | | AMP OCP). ALSO 60 AMP OCP SHOWN INTHE | | | MAIN PANEL SEEM TOOLARGE FOR THE | | | CONDENSING UNIT. SEE ARTICLE 440.22 | | | NEC. | | | | | | 2} THERE ARE NO PROVISIONS IN THE | | | CALCULATIONS FOR POOL EQUIPMENT, BUT | | | THERE IS EQUIPMENT SHOWN ON THE PLAN. | | | | | | 3} IF NOTE #14 IS ADHERED TO, THOSE | | | CIRCUITS WOULD HAVE TO BE PROTECTED BY | | | AN AFCI BECAUSE THE DETECTORS ARE | | | LOCATED IN BEDROOMS. 210.12. | | | | | | 4} THE GFI'S SHOWN IN THE DINING ROOM | | | AND BREAKFAST NOOK, WHILE NOT REQUIRED | | | ALTHOUGH PERMISSIBLE, MUST BE INSTALLED | | | IF LEFT ON THE PLAN. | | | | | | 5} A RECEPTACLE NEEDS TO BE ADDED TO | | | THE MASTER BEDROOM TO COMPLY WITH | | | 210.52(A). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2005-08-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-24 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-24 |
Time |
17:49 |
Sent To |
E |
|
| Notes |
| 2005-08-24 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-08-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-24 |
Time |
17:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-24 |
Time |
17:47 |
Sent To |
B |
|
| Notes |
| 2005-08-24 00:00:00 | TO "RMCDOUGAL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-07-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-15 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-15 |
Time |
16:34 |
Sent To |
E |
|
| Notes |
| 2005-07-15 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-04-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-15 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-15 |
Time |
16:45 |
Sent To |
E |
|
| Notes |
| 2005-04-15 00:00:00 | TO "BTROBAUG" DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-03-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-18 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-18 |
Time |
13:27 |
Sent To |
B |
|
| Notes |
| 2005-03-18 00:00:00 | TO "RMCDOUGAL" DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-02-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-15 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-15 |
Time |
08:40 |
Sent To |
E |
|
| Notes |
| 2005-02-15 00:00:00 | TO BTROBAUG DESK/RESUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-01-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-06 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-06 |
Time |
08:36 |
Sent To |
E |
|
| Notes |
| 2005-01-06 00:00:00 | TO "SFD" RACK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-01-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-03 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-03 |
Time |
10:58 |
Sent To |
Z |
|
| Notes |
| 2005-01-03 00:00:00 | TO "Z" BOX. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-01-11 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-01-11 |
Time |
14:30 |
Rev Time |
0.45 |
| Received By |
prafter |
Date |
2005-01-11 |
Time |
14:30 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2005-02-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-02-26 |
Time |
08:23 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-02-26 |
Time |
08:23 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-01-11 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-01-11 |
Time |
11:28 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-01-11 |
Time |
11:28 |
Sent To |
M |
|
| Notes |
| 2005-01-11 00:00:00 | DENIED; | | | 1.TUB IN BATH 3 IS NOT VENTED. WET VENT | | | SHALL BE UPSTREAM OF THE WATER CLOSET. | | | 2.PLEASE CHANGE PLUMBING NOTE 3 TO | | | COMPLY WITH FBC PLUMBING TABLE 704.1. | | | 3.PLEASE DELETE PLUMBING NOTE 6. A/C | | | CONDENSATE IS NOT PERMITED TO DRAIN INTO | | | THE SEWER SYSTEM. THIS WATER DOESNOT | | | NEED TO BE TREATED. | | | 4.LAUNDRY TUB TO DRAIN ABOVE CLOTHES | | | WASHER AND C.O. SHOULD BE 48" OFF FINISH | | | FLOOR. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-01-05 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-01-05 |
Time |
18:32 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-01-05 |
Time |
18:32 |
Sent To |
I |
|
| Notes |
| 2005-01-05 00:00:00 | MUST PULL SEPERATE PERMIT FOR POOL/DECK |
|
|