Plan Review Details - Permit 04121950
Plan Review Stops For Permit 04121950
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-11-10 Cont ID  
Sent By jgomez Date 2005-11-10 Time 18:16 Rev Time 0.50
Received By jgomez Date 2005-11-10 Time 18:16 Sent To PC
Notes
2005-11-10 00:00:00SHUTTERS REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-28 Cont ID  
Sent By jgomez Date 2005-04-28 Time 10:11 Rev Time 0.50
Received By jgomez Date 2005-04-28 Time 10:11 Sent To PC
Notes
2005-04-28 00:00:00SUBMITTAL RESPONDING TO PROVISO DATED
 3-29-05. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-03-29 Cont ID  
Sent By jgomez Date 2005-03-29 Time 16:41 Rev Time 2.00
Received By jgomez Date 2005-03-29 Time 16:41 Sent To  
Notes
2005-03-29 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 PROVIDE THE FOLLOWING INFORMATION PRIOR
 TO INSTALLATION OR CONSTRUCTION TO AVOID
 CONFLICTS OR DELAYS.
 1- DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 2- UPDATE TRUSS ANCHOR SCHEDULE. SEE
 LATEST CATALOGUE OR PROVIDE COMPLETE
 ENGINEERING CALCS THAT COMPLY WITH SEC.
 1609.4.3 FBC 2001.
  
 3- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR: A) FRENCH DOORS WITH
 OUTSWING AND SIZE AS SHOWN ON PLANS.
 B) USP OR SIMPSON TRUSS CONNECTORS.
  
 4- PLANS CALL FOR FLAT ROOF SYSTEM.
 PRODUCT APPROVAL SUBMITTED IS FOR "S".
 TILE. REVISE AS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-01 Cont ID  
Sent By jgomez Date 2005-02-01 Time 08:55 Rev Time 2.00
Received By jgomez Date 2005-02-01 Time 08:55 Sent To PC
Notes
2005-01-31 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE COMPLETE BATHROOM WITH DOOR
 THAT ALLOWS 29" MIN. CLEAR OPENING.
 SECTION 11-11 FBC 2001.
  
 2- SPECIFY ROOF TILE FASTENING. SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 3- UPDATE TRUSS ANCHOR SCHEDULE. PROVIDE
 COMPLETE ENGINEERING CALCULATIONS FOR
 TYPE AND NUMBER OF FASTENERS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER TO COMPLY WITH SECTION
 1609.4.3 FBC 2001.
  
 4- A) NEED NAME OF ARCHITECT SEALING THE
 PLANS. CHAPTER 61G1-16004 FAC.
 B) STATE REGISTRATION NUMBER IS
 INCORRECT. REVISE AS REQUIRED.
  
 5- PROVIDE COMPLETE DETAIL/SPECS FOR
 CEILING INSTALLATION AT ENTRY AND REAR
 PORCHES. SPECIFY FASTENER SIZE AND
 SPACING. SEE ASTM C926 AND ASTM C1063.
 SECTION 2504.2 FBC 2001.
  
 6- OWNER/AGENT TO SIGN AND DATE THE
 ENERGY CALCULATIONS.
  
 7- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) ENTRY DOORS. SEE SIZES ON PLANS.
 B) FRENCH DOORS. SEE SIZES ON PLANS.
 C) CONCRETE LINTELS: NEED SAME DADE
 COUNTY NOA THAT WAS SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
 D) FIXED WINDOWS THAT MEET THE DESIGN
 PRESSURES AND SIZES AS SHOWN ON PLANS.
 E) ARABESQUE WINDOW. SEE PLANS.
  
 8- A) PROVIDE COMPLETE UL LISTING AND
 SPECS FOR FIREPLACE. SEC. 2806 FBC
 2001.
 B) PROVIDE COMPLETE APPROVED BBQ SPECS.
 SECTION 2808 FBC 2001.
  
 9- STORM SHUTTERS: A) KEY PLAN DOESN'T
 MATCH PLANS.
 B) REVISE MIN. PANEL SIZE. SEE
 ENGINEERED DRAWINGS.
 C) REVISE INTERIOR AND END ZONES. SEE
 PLANS FOR LOCATION.
 D) REVISE DESIGN PRESSURES. SEE PLANS.
  
 10- PROVIDE COMPLETE FRAMING DETAILS FOR
 ARABESQUE WINDOW. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
  
 11- OWES $866.23 FOR UPDATED VALUATION.
  
 12- REVISE FOUNDATIOON NOTE #2 ON SHEET
 A-2. SEE CHAPTER 19 FBC 2001 FOR PROPER
 ACI REFERENCE.
  
 13- REVISE CONNECTORS SPECIFIED ON
 DETAIL 2/A-9. "SEMCO" IS OUT OF
 BUSINESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-11-12 Cont ID  
Sent By jleahy Date 2005-11-12 Time 21:15 Rev Time 0.30
Received By jleahy Date 2005-11-12 Time 21:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-10-14 Cont ID  
Sent By btrobaug Date 2005-10-14 Time 12:47 Rev Time 0.50
Received By btrobaug Date 2005-10-14 Time 12:04 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-22 Cont ID  
Sent By dpalmer Date 2005-09-22 Time 19:55 Rev Time 0.00
Received By dpalmer Date 2005-09-22 Time 19:55 Sent To  
Notes
2005-09-22 00:00:00********** PROVISO ************
  
 1)NOTE: PLEASE SEE AHU'S AND CU'S ON
 PANEL SCHEDULES AND LOAD CALCULATIONS.
 PLEASE CORRELATE OCP, AWG AND KW LOADS
 FOR EACH.
 PLEASE ADJUST LOAD CALCULATIONS AS
 NEEDED.
  
 2)NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARENCE REQUIRED FOR POOL PANEL.
  
 3)NOTE: PLEASE SEE DISH/DISP IS SHOWN AS
 2-P, HOWEVER ONLY INDICATES ONE CIRCUIT
 SPACE ON PANEL SCHEDULE.
  
 4)NOTE: PLEASE SEE RISER INDICATES 2/0'S
 FOR 150A MAINS, THIS IS OK, HOWEVER IF
 2/0'S ARE SHOWN THEN THIS IS WHAT WILL
 BE REQUIRED TO BE INSTALLED.
 ***THIS IS ONLY A NOTE***
  
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW ALONG
 WITH ANY OTHER REVISIONS BEFORE FINAL
 ELECTRICAL INSPECTION IS CALLED IN.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-03-22 Cont ID  
Sent By btrobaug Date 2005-03-22 Time 11:01 Rev Time 0.50
Received By btrobaug Date 2005-03-22 Time 10:48 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By btrobaug Date 2005-01-07 Time 12:26 Rev Time 0.50
Received By btrobaug Date 2005-01-07 Time 12:17 Sent To M
Notes
2005-01-07 00:00:00 
  
 .PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE OVERCURRENT PROTECTION FOR AHU
 #2 AT 60 AMPS IS TOO LARGE TO PROTECT A
 5KW UNIT.(5000X125%/240=26 AMPS, MAX 30
 AMP OCP). ALSO 60 AMP OCP SHOWN INTHE
 MAIN PANEL SEEM TOOLARGE FOR THE
 CONDENSING UNIT. SEE ARTICLE 440.22
 NEC.
  
 2} THERE ARE NO PROVISIONS IN THE
 CALCULATIONS FOR POOL EQUIPMENT, BUT
 THERE IS EQUIPMENT SHOWN ON THE PLAN.
  
 3} IF NOTE #15 IS ADHERED TO, THOSE
 CIRCUITS WOULD HAVE TO BE PROTECTED BY
 AN AFCI BECAUSE THE DETECTORS ARE
 LOCATED IN BEDROOMS. 210.12.
  
 4} THE GFI'S SHOWN IN THE DINING ROOM
 AND BREAKFAST NOOK, WHILE NOT REQUIRED
 ALTHOUGH PERMISSIBLE, MUST BE INSTALLED
 IF LEFT ON THE PLAN.
  
 5} A RECEPTACLE NEEDS TO BE ADDED TO
 THE MASTER BEDROOM TO COMPLY WITH
 210.52(A).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-10-22 Cont ID  
Sent By adarroug Date 2005-10-22 Time 10:32 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 10:32 Sent To B
Notes
2005-10-22 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-10-14 Cont ID  
Sent By adarroug Date 2005-10-14 Time 10:19 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 10:19 Sent To E
Notes
2005-10-14 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-22 Cont ID  
Sent By adarroug Date 2005-09-22 Time 15:18 Rev Time 0.00
Received By adarroug Date 2005-09-22 Time 15:18 Sent To E
Notes
2005-09-22 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-18 Cont ID  
Sent By adarroug Date 2005-04-18 Time 09:50 Rev Time 0.00
Received By adarroug Date 2005-04-18 Time 09:50 Sent To B
Notes
2005-04-18 00:00:00TO "JGOMEZ" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-15 Cont ID  
Sent By adarroug Date 2005-03-15 Time 11:19 Rev Time 0.00
Received By adarroug Date 2005-03-15 Time 11:19 Sent To E
Notes
2005-03-15 00:00:00TO "BT" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 07:45 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 07:45 Sent To E
Notes
2005-01-06 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 11:02 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 11:02 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By prafter Date 2005-01-11 Time 16:11 Rev Time 0.45
Received By prafter Date 2005-01-11 Time 16:11 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-10 Cont ID  
Sent By jleech Date 2005-01-10 Time 17:37 Rev Time 0.33
Received By jleech Date 2005-01-10 Time 17:37 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-05 Cont ID  
Sent By mmclean Date 2005-01-05 Time 18:11 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 18:11 Sent To I
Notes
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK