Plan Review Details - Permit 04121944
Plan Review Stops For Permit 04121944
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2005-11-10 Cont ID  
Sent By jgomez Date 2005-11-10 Time 18:43 Rev Time 0.50
Received By jgomez Date 2005-11-10 Time 18:43 Sent To PC
Notes
2005-11-10 00:00:00BUILDING REVISION CHECKLIST:
 1- CONTRACTOR NEEDS TO APPLY FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT AS
 AGREED ON PROVISO DATED 4-29-05. SEE
 ATTACHED COPY, ALONG WITH REMAINDERS TO
 APPLY FOR SEPARATE PERMIT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-09-23 Cont ID  
Sent By jgomez Date 2005-09-23 Time 17:05 Rev Time 0.50
Received By jgomez Date 2005-09-23 Time 17:05 Sent To P
Notes
2005-09-23 00:00:00SUBMITTAL BUILDING REVIEW CHECKLIST:
 1- NEED TO APPLY FOR SEPARATE PERMIT FOR
 STORM SHUTTERS. SYSTEM DOESN'T SHOW ANY
 APPLICATION FOR SHUTTERS. SEE ATTACHED
 COPY OF PERMITS APPLIED FOR THIS
 ADDRESS.
  
 ***NOTE: DRAWINGS SUBMITTED ARE OK.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-08-25 Cont ID  
Sent By jgomez Date 2005-08-25 Time 08:34 Rev Time 0.50
Received By jgomez Date 2005-08-25 Time 08:34 Sent To PC
Notes
2005-08-25 00:00:00SUBMITTAL BUILDING REVIEW CHECKLIST:
 1- PERMIT APPLICATION FOR STORM SHUTTERS
 HAS NOT BEING SUBMITTED YET. APPLY FOR
 PERMIT AS SOON AS POSSIBLE TO AVOID
 DELAYS.
  
 2- DESIGNER OF RECORD TO SPECIFY IN
 PLANS ROOF TILE FASTENING AS REQUIRED BY
 SEC. 104.2.1.1 CITY AMENDMENTS TO FBC
 2001.
  
 3- TRUSS ANCHOR SCHEDULE: REVISE
 FASTENERS FOR THD210. SEE TECHNICAL
 BULLETIN FOR TESTED FASTENERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-07-06 Cont ID  
Sent By rmcdouga Date 2005-07-06 Time 09:01 Rev Time 0.00
Received By rmcdouga Date 2005-07-06 Time 07:31 Sent To  
Notes
2005-07-06 00:00:00PROVISO ITEMS RECIEVED AND APPROVED ARE:
  
 1- ITEM #3 THE TECHNICAL BULLETINS FOR
 USP THD210 AND THD210-2 CONNECTORS ARE
 OK.
  
 2- ITEM #5 REVISED SHEET A-3 TO ASCE7-98
 IS OK.
  
 ITEM #1 REQUIRES A SEPARATE PERMIT FOR
 STORMPANELS.
  
 ITEMS #2 AND #4 HAVE NOT BEEN PROPERLY
 ADDRESSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-29 Cont ID  
Sent By jgomez Date 2005-04-29 Time 14:08 Rev Time 2.00
Received By jgomez Date 2005-04-29 Time 14:08 Sent To E
Notes
2005-04-29 00:00:00BUILDING REVIEW PROVISO:
 PROVIDE INFORMATION PRIOR TO
 CONSTRUCTION OR INSTALLATION TO AVOID
 DELAYS OR CONFLICTS.
  
 1- PROVIDE COMPLETE STORM SHUTTERS
 INFORMATION UNDER ANOTHER PERMIT AS
 AGREED UPON WITH CONTRACTOR.
  
 2- DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 3- UPDATE/REVISE TRUSS ANCHOR SCHEDULE.
 PROVIDE COMPLETE ENGINEERING CALCS FOR
 TYPE AND NUMBER OF FASTENERS THAT DIFFER
 FROM MANUFACTURER'SCATALOGUE. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 4- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR FRENCH DOORS WITH SIDELITES
 AS SHOWN ON PLANS.
  
 5- DESIGN PARAMETERS CRITERIA: CLARIFY
 WHERE IS THE BASIC VELOCITY PRESSURE
 TAKEN FROM. IT'S NOT SHOWN ON CHAPTER 16
 FBC 2001. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-28 Cont ID  
Sent By jgomez Date 2005-03-28 Time 16:32 Rev Time 2.00
Received By jgomez Date 2005-03-28 Time 16:32 Sent To  
Notes
2005-03-28 00:00:00CHECKLIST:
 1- SPECIFY ROOF TILE FASTENING. THIS IS
 THE DESIGNER OF RECORD RESPONSIBILITY,
 NOT THE BUILDER. SEE SEC. 104.2.1.1.
 CITY AMENDMENTS TO FBC 2001.
  
 2- UPDATE TRUSS ANCHOR SCHEDULE. SEE
 LATEST CATALOGUE. PROVIDE COMPLETE
 ENGINEERING CALCS FOR TYPE AND NUMBER OF
 FASTENERS THAT DIFFER FROM THOSE TESTED
 AND PUBLISHED BY MANUFACTURER.
 **NOTE: CALCULATIONS TO COMPLY WITH SEC.
 1609.4.3 FBC 2001.
  
 3- STORM SHUTTERS INFORMATION WAS NOT
 CHANGED FROM PREVIOUS CHECKLIST:
 A) NEED ENGINEER'S ORIGINAL SEAL,
 SIGNATURE AND DATE AS REQUIRED BY
 GENERAL NOTE #6.
 B) KEY PLAN DOESN'T MATCH PLANS.
 C) CLEARLY INDICATE ON DWGS INSTALLATION
 SCHEDULESPECIFIC MOUNTING CONDITIONS
 AND ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURES, EDGE
 DISTANCE, PANEL SPAN, CONNECTION TYPE
 AND STRUCTURE TO BE ATTACHED TO (MASONRY
 OR CONCRETE).
  
 4- ENERGY CALCULATIONS: A) A/C AREA
 DOESN'T MATCH PLANS. THESE PLANS INCLUDE
 ADDITIONAL SITTING AREA.
 B) COMPLETE ALL INFORMATION ON TOP OF
 FORM. INCLUDING PROJECT ADDRESS, ETC.
  
 5- CLARIFY IF USING FLUSH STEEL DOOR AT
 ENTRY. ARCHITECT'S ELEVATION SHOW GLASS
 DOORS. PROVIDE PRODUCT APPROVAL THAT
 MATCHES DOOR.
  
 6- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS. NEED RE-RECORDED N.O.C.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-04 Cont ID  
Sent By jleech Date 2005-02-04 Time 16:32 Rev Time 0.00
Received By jgomez Date 2005-02-04 Time 14:52 Sent To PC
Notes
2005-02-04 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE COMPLETE BATHROOM WITH DOOR
 THAT ALLOWS 29" MIN. CLEAR OPENING.
 SECTION 11-11 FBC 2001.
  
 2- A) SPECIFY ROOF TILE FASTENING REQ'D
 BY SEC. 104.2.1.1 CITY AMENDMENTS TO
 FBC
 B) PLANS CALL FOR FLAT ROOF. PRODUCT
 APPROVAL SUBMITTED IS FOR "S" TILE.
 CLARIFY AS REQUIRED.
  
 3- UPDATE TRUSS ANCHOR SCHEDULE.
 PROVIDE
 COMPLETE ENGINEERING CALCULATIONS FOR
 TYPE AND NUMBER OF FASTENERS THAT
 DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER TO COMPLY WITH SECTION
 1609.4.3 FBC 2001.
  
 4- PROVIDE COMPLETE DETAIL/SPECS FOR
 INSTALLATION OF CEILING AT ENTRY AND
 REAR PORCHES. SPECIFY FASTENER &
 SPACING
 AS REQ'D BY ASTM C926 AND ASTM C1063.
 SECTION 2504.2 FBC 2001.
  
 5- NEED TO SUBMIT ENERGY CALCULATIONS
 AND MAKE SURE THEY ARE SIGNED/DATED BY
 OWNER/AGENT PRIOR TO SUBMITTAL.
  
 6- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) CONCRETE LINTELS: NEED SAME DADE
 COUNTY NOA THAT WAS SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
 B) ARABESQUE WINDOW AS SHOWN ON PLANS.
  
 7- PROVIDEAPPROVED SPECS FOR BBQ.
 SECTION 2808 FBC 2001.
 **NOTE: CHECK THAT SPECS ALLOW BBQ TO
 BE
 INSTALLED IN PORCHES.
  
 8- STORM SHUTTERS: A) NEED ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED
 BY NOTE #6 ON FIRST PAGE GENERAL NOTES.
 B) KEY PLAN DOESN'T MATCH PLANS.
 C) REVISE MIN. AND MAX. PANEL SIZE
 ALLOWED. SEE ENGINEERED DRAWINGS.
 D) SEE PLANS FOR INTERIOR AND END ZONES
 AND REVISE SCHEDULEAS REQUIRED.
 E) SEE PLANS FOR DESIGN PRESSURES AND
 REVISE SCHEDULE AS REQUIRED.
 F) CLEARLY INDICATE ON ENGINEERED
 DRAWINGS ANCHOR AND SPACING USED
 ACCORDING TO STRUCTURE TO BE ATTACHED
 TO
 MASONRY OR CONCRETE.
  
 9- PROVIDE COMPLETE FRAMING DETAILS FOR
 ARABESQUE WINDOW. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 10- OWES $250.39 FOR UPDATED VALUATION.
  
 11- REVISE FOUNDATION NOTE ON SHEET
 A-2.
 SEE CHAPTER 19 FBC 2001 FOR PROPER ACI
 REFERENCE.
  
 12- REVISE CONNECTORS SPECIFIED ON
 DEATIL 2/A-9. "SEMCO" IS OUT OF
 BUSINESS.
  
 13- SHEET A-3: CLARIFY SIZE OF WINDOWS
 AT BEDROOM #3. ARE BOTH 25SH OR NOT.
 REVISESPECS WRITTEN ON PLAN AS REQ'D.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-11-07 Cont ID  
Sent By dpalmer Date 2005-11-07 Time 17:18 Rev Time 0.30
Received By dpalmer Date 2005-11-07 Time 17:13 Sent To  
Notes
2005-11-07 00:00:00REDLINED GROUNDING ELECTRODE CONDUCTOR,
 MIN #2, 250.66,31.15B6, SHOWS #1

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-05-02 Cont ID  
Sent By btrobaug Date 2005-05-02 Time 12:26 Rev Time 0.50
Received By btrobaug Date 2005-05-02 Time 12:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-03-15 Cont ID  
Sent By btrobaug Date 2005-03-15 Time 09:02 Rev Time 0.50
Received By btrobaug Date 2005-03-15 Time 08:41 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By btrobaug Date 2005-01-07 Time 12:14 Rev Time 0.50
Received By btrobaug Date 2005-01-07 Time 12:12 Sent To M
Notes
2005-01-07 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE OVERCURRENT PROTECTION FOR AHU
 #2 AT 60 AMPS IS TOO LARGE TO PROTECT A
 5KW UNIT.(5000X125%/240=26 AMPS, MAX 30
 AMP OCP). ALSO 60 AMP OCP SHOWN IN THE
 MAIN PANEL SEEM TOOLARGE FOR THE
 CONDENSING UNIT. SEE ARTICLE 440.22
 NEC.
  
 2} THERE ARE NO PROVISIONS IN THE
 CALCULATIONS FOR POOL EQUIPMENT, BUT
 THERE IS EQUIPMENT SHOWN ON THE PLAN.
  
 3} IF NOTE #15 IS ADHERED TO, THOSE
 CIRCUITS WOULD HAVE TO BE PROTECTED BY
 AN AFCI BECAUSE THE DETECTORS ARE
 LOCATED IN BEDROOMS. 210.12.
  
 4} THE GFI'S SHOWN IN THE DINING ROOM
 AND BREAKFAST NOOK, WHILE NOT REQUIRED
 ALTHOUGH PERMISSIBLE, MUST BE INSTALLED
 IF LEFT ON THE PLAN.
  
 5} A RECEPTACLE NEEDS TO BE ADDED TO
 THE MASTER BEDROOM TO COMPLY WITH
 210.52(A).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-10-21 Cont ID  
Sent By adarroug Date 2005-10-21 Time 16:21 Rev Time 0.00
Received By adarroug Date 2005-10-21 Time 16:21 Sent To B
Notes
2005-10-21 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-10-17 Cont ID  
Sent By adarroug Date 2005-10-17 Time 16:40 Rev Time 0.00
Received By adarroug Date 2005-10-17 Time 16:40 Sent To E
Notes
2005-10-17 00:00:00TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-06 Cont ID  
Sent By adarroug Date 2005-09-06 Time 15:24 Rev Time 0.00
Received By adarroug Date 2005-09-06 Time 15:24 Sent To B
Notes
2005-09-06 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-12 Cont ID  
Sent By adarroug Date 2005-07-12 Time 15:53 Rev Time 0.00
Received By adarroug Date 2005-07-12 Time 15:53 Sent To  
Notes
2005-07-12 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 14:33 Rev Time 0.00
Received By shill Date 2005-06-20 Time 14:33 Sent To B
Notes
2005-06-20 00:00:00TO JG DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-18 Cont ID  
Sent By adarroug Date 2005-04-18 Time 14:34 Rev Time 0.00
Received By adarroug Date 2005-04-18 Time 14:34 Sent To B
Notes
2005-04-18 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-07 Cont ID  
Sent By adarroug Date 2005-03-07 Time 15:52 Rev Time 0.00
Received By adarroug Date 2005-03-07 Time 15:52 Sent To E
Notes
2005-03-07 00:00:00TO BTROBAUG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 07:41 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 07:41 Sent To E
Notes
2005-01-06 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 12:09 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 12:09 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By jleech Date 2005-01-10 Time 11:10 Rev Time 0.00
Received By prafter Date 2005-01-10 Time 14:00 Sent To P
Notes
2005-01-10 00:00:00ON ENERGY MANUAL J OR A/C PLANS.
 PAT RAFTER 561/805/6725 OR 8056719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-26 Cont ID  
Sent By jleech Date 2005-09-26 Time 07:22 Rev Time 0.33
Received By jleech Date 2005-09-26 Time 07:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-10 Cont ID  
Sent By prafter Date 2005-01-11 Time 11:11 Rev Time 0.50
Received By jleech Date 2005-01-10 Time 13:33 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-05 Cont ID  
Sent By mmclean Date 2005-01-05 Time 18:25 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 18:25 Sent To I
Notes
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK


Account Summary | Usage Policy | Privacy Policy