Plan Review Details - Permit 04121932
Plan Review Stops For Permit 04121932
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-12-01 Cont ID  
Sent By amorse Date 2005-12-01 Time 11:28 Rev Time 0.00
Received By amorse Date 2005-12-01 Time 11:27 Sent To PC
Notes
2005-12-01 00:00:00 
  
 REVISED PRODUCT APPROVALS FOR STORM
 SHUTTERS ACCEPTED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 (561)805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2005-09-02 Cont ID  
Sent By rmcdouga Date 2005-09-02 Time 09:15 Rev Time 0.00
Received By rmcdouga Date 2005-08-30 Time 16:49 Sent To  
Notes
2005-08-30 00:00:00STORM PANEL RVISION IS DENIED.
  
 1) SPECIFY THE ANCHOR TYPE, CONNECTION
 TYPE AND EDGE DISTANCE AS REQUIRED BY
 THE PRODUCT APPROVAL ANCHOR SCHEDULE TO
 DETERMINE ANCHOR SPACING.
  
 2) ON SHEET 4 OF THE PRODUCT APPROVAL
 THE MAXIMUM DESIGN PRESSURE FOR A PANEL
 SPAN OF 129" IS 39.10 PSF AND ON THE
 INSTALLATION SCHEDULE SUBMITTED THE
 PRESSURE AT OPENING #10 FOR THE 129"
 SHUTTER SPAN IS 43 PSF. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-07-11 Cont ID  
Sent By rmcdouga Date 2005-07-11 Time 15:48 Rev Time 0.00
Received By rmcdouga Date 2005-07-11 Time 15:48 Sent To  
Notes
2005-07-11 00:00:00RESTAMP OF COPIED FILE SET OF PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-17 Cont ID  
Sent By rmcdouga Date 2005-03-17 Time 07:10 Rev Time 0.00
Received By rmcdouga Date 2005-03-17 Time 07:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-22 Cont ID  
Sent By rmcdouga Date 2005-02-22 Time 14:52 Rev Time 0.00
Received By rmcdouga Date 2005-02-22 Time 14:52 Sent To  
Notes
2005-02-22 00:00:00DENIED
  
 1) FBC 11-4.23.2 REQUIRES AT LEAST ONE
 FULL BATHROOM WITH A DOOR THAT HAS A 29"
 CLEAR OPENING. THE 2-6 DOOR ON THE PLAN
 WILL NOT PROVIDE THE REQUIRED CLEAR
 OPENING WIDTH WHICH IS MEASURED BETWEEN
 THE FACE OF THE DOOR AND THE OPPOSITE
 STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 2) SPECIFY THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURES FOR THE SMALL GOLF
 CART GARAGE DOOR.
  
 3) SUBMIT THE STATE/LOCAL PRODUCT
 APPROVAL FOR THE SINGLE OUTSWING GLAZED
 DOOR. THE ONE SUBMITTED IS FOR DOUBLE
 OUTSWING DOORS.
  
 4) SUBMIT THE STATE/LOCAL PRODUCT
 APPROVAL FOR THE DOUBLE OUTSWING GLAZED
 WOOD FRONT DOORS AS SPECIFIED ON THE
 PLANS. THESE DOORS ARE NOT SHOWN ON THE
 STORM PANEL SCHEDULE AS BEING SHUTTERED.
 THEREFORE, THE PRODUCT APPROVAL FOR
 IMPACT RESISTANT DOORS IS REQUIRED. IF
 THE DOORS ARE NOT WOOD, THEY SHOULD NOT
 BE SPECIFIED AS SUCH ON SHEET A3.
  
 5)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-18 Cont ID  
Sent By rmcdouga Date 2005-01-18 Time 15:47 Rev Time 0.00
Received By rmcdouga Date 2005-01-18 Time 15:47 Sent To  
Notes
2005-01-18 00:00:00DENIED
  
 1) NO OPENINGS ARE ALLOWED IN THE WALL
 ON THE ZERO LOT LINE PER FBC TABLE 600.
 REMOVE THE GARAGE VENT ON THE ZERO LOT
 LINE.
  
 2) SPECIFY ONE HOUR FIRE RATED GLASS
 BLOCK AT THE ZERO LOT LINE ON THE FLOOR
 PLAN.
  
 3) THE GLASS BLOCK DETAIL ON A9
 INCORRECTLY REFERENCES ASCE 7-88. THE
 CORRECT REFERENCE IS ASCE 7-98.
  
 4) CHAPTER 11 OF THE 2001 FBC REQUIRES
 AT LEAST ONE FULL BATHROOM WITH A DOOR
 THAT HAS A 29" CLEAR OPENING.
  
 5) THE DETAIL 2 ON A9 SPECIFIES
 "SEMCO"CONNECTORS. SEMCO IS NO LONGER IN
 BUSINESS AND DOES NOT HAVE STATE PRODUCT
 APPROVAL.
  
 6) SPECIFY THE POSITIVE AND NEGATIVE
 DESIGN PRESSURES FOR THE SMALL GARAGE
 DOOR AND THE 8' WIDE SLIDING GLASS DOOR.
  
  
 7) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALCULATION FORM PER FBC
 CHAPTER 13.
  
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND LISTING INFORMATION FOR THE BBQ AND
 PREFAB FIREPLACE.
  
 9) THE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS HAS AN
 EXTRA WINDOW THAT IS NOT SHOWN ON THE
 PLANS. THE SINGLE FRENCH DOOR IS SHOWN
 AS A DOUBLE DOOR ON THE KEY PLAN.
  
 10) SUBMIT STATE/LOCAL PRODUCT APPROVAL
 FOR THE SINGLE OUTSWING GLAZED FRENCH
 DOOR AND THE DOUBLE OUTSWING WOOD ENTRY
 DOORS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-11-07 Cont ID  
Sent By dpalmer Date 2005-11-07 Time 17:32 Rev Time 0.33
Received By dpalmer Date 2005-11-07 Time 17:32 Sent To  
Notes
2005-11-07 00:00:00REDLINED GROUNDING ELECTRODE CONDUCTOR,
 MIN #2, 250.66,31.15B6, SHOWS #1

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-09-22 Cont ID  
Sent By dpalmer Date 2005-09-22 Time 19:54 Rev Time 0.00
Received By dpalmer Date 2005-09-22 Time 19:54 Sent To  
Notes
2005-09-22 00:00:00REV'S FOR FINAL.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-07-11 Cont ID  
Sent By rmcdouga Date 2005-07-11 Time 15:47 Rev Time 0.00
Received By rmcdouga Date 2005-07-11 Time 15:47 Sent To  
Notes
2005-07-11 00:00:00RESTAMP OF COPIED FILE SET OF PLANS

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-05-18 Cont ID  
Sent By dpalmer Date 2005-05-18 Time 06:10 Rev Time 0.25
Received By dpalmer Date 2005-05-18 Time 06:10 Sent To  
Notes
2005-05-18 00:00:00************ UNSAT ************
  
 **PLEASE SEE PLANS AND RISER DIAGRAM
 HAVE COMPLETELY CHANGED FROM ORIG PLANS.
  
 1)NOTE: PLEASE SEE NEW RISER NOW
 INDICATES THREE ELECTRICAL PANELS,
 HOWEVER NO OCP IS SHOWN ON RISER FOR NEW
 PANELS.
 IS THERE NOW A PANEL SCHEDULE FOR NEW
 METER/MAIN COMBO.
 215.5,240.4, 310.16 ETC.
  
 2)NOTE: PLEASE SEE ONLY ONE PANEL IS
 SHOWN ON ELECTRICAL PLANS AND RISER
 SHOWS 3.
 215.5
  
 3)NOTE: PLEASE SEE NUMEROUS ITEMS ON
 PANEL SCHEDULE INDICATE 20A OCP ON #14
 AWG. PLEASE SEE 310.16,240.4.
  
 4)NOTE:
  
 5)NOTE: PLEASE SEE A JACUZZI/WHIRLPOOL
 TUB IS NOW ADDED TO PANEL SCHEDULE,
 HOWEVER NO ELECTRICAL IS SHOWN ON PLANS.
 PLEASE ALSO SEE 680.71 FOR REQUIRED
 INDICATION OF GFI PROTECTION.
  
 6)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THE # OF
 RECESSED LTS INDICATED ON PANEL
 SCHEDULE/LOAD CALCULATIONS.
 PLEASE SEE SOME MODELS SHOW THESE AS
 "OPT". EACH PLAN MUST REFLECT THE ACTUAL
 INSTALLATION PER WHICH ARE INSTALLED OR
 NOT INSTALLED.
 215.5
  
 7)NOTE: PLEASE SEE MISSING RECEPT
 REQUIRED IN BATHRM 210.52D.
  
 8)NOTE: PLEASE SEE MISSING GFI ALONG
 KITCHEN COUNTERSPACE.
  
 PLEASE SEE MANY OF THESE ITEMS HAVE BEEN
 REDLINED AT LOCATIONS ON PLANS AT
 LOCATIONS OF NOTES.
  
 *** PLEASE BE SURE ALL PLANS ARE SIGNED
 BY THE ARCHITECT OF RECORD.
 FS 481.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-10 Cont ID  
Sent By btrobaug Date 2005-02-10 Time 13:08 Rev Time 0.50
Received By btrobaug Date 2005-02-10 Time 07:51 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By btrobaug Date 2005-01-07 Time 15:57 Rev Time 0.50
Received By btrobaug Date 2005-01-07 Time 15:57 Sent To M
Notes
2005-01-07 00:00:00 
  
  
 .PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE OVERCURRENT PROTECTION FOR AHU
 #2 AT 60 AMPS IS TOO LARGE TO PROTECT A
 5KW UNIT.(5000X125%/240=26 AMPS, MAX 30
 AMP OCP). ALSO 60 AMP OCP SHOWN INTHE
 MAIN PANEL SEEM TOOLARGE FOR THE
 CONDENSING UNIT. SEE ARTICLE 440.22
 NEC.
  
 2} THERE ARE NO PROVISIONS IN THE
 CALCULATIONS FOR POOL EQUIPMENT, BUT
 THERE IS EQUIPMENT SHOWN ON THE PLAN.
  
 3} IF NOTE #14 IS ADHERED TO, THOSE
 CIRCUITS WOULD HAVE TO BE PROTECTED BY
 AN AFCI BECAUSE THE DETECTORS ARE
 LOCATED IN BEDROOMS. 210.12.
  
 4} THE GFI'S SHOWN IN THE DINING ROOM
 AND BREAKFAST NOOK, WHILE NOT REQUIRED
 ALTHOUGH PERMISSIBLE, MUST BE INSTALLED
 IF LEFT ON THE PLAN.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-11-29 Cont ID  
Sent By adarroug Date 2005-11-29 Time 10:40 Rev Time 0.00
Received By adarroug Date 2005-11-29 Time 10:40 Sent To B
Notes
2005-11-29 00:00:00TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-10-17 Cont ID  
Sent By adarroug Date 2005-10-17 Time 16:41 Rev Time 0.00
Received By adarroug Date 2005-10-17 Time 16:41 Sent To E
Notes
2005-10-17 00:00:00TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-09-22 Cont ID  
Sent By adarroug Date 2005-09-22 Time 15:17 Rev Time 0.00
Received By adarroug Date 2005-09-22 Time 15:17 Sent To E
Notes
2005-09-22 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-08-24 Cont ID  
Sent By adarroug Date 2005-08-24 Time 17:44 Rev Time 0.00
Received By adarroug Date 2005-08-24 Time 17:44 Sent To B
Notes
2005-08-24 00:00:00TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-08 Cont ID  
Sent By adarroug Date 2005-07-08 Time 16:31 Rev Time 0.00
Received By adarroug Date 2005-07-08 Time 16:31 Sent To B
Notes
2005-07-08 00:00:00TO "RMCDOUGAL" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-04-15 Cont ID  
Sent By adarroug Date 2005-04-15 Time 16:43 Rev Time 0.00
Received By adarroug Date 2005-04-15 Time 16:42 Sent To E
Notes
2005-04-15 00:00:00TO "BTROBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-15 Cont ID  
Sent By adarroug Date 2005-03-15 Time 11:16 Rev Time 0.00
Received By adarroug Date 2005-03-15 Time 11:16 Sent To B
Notes
2005-03-15 00:00:00TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-01 Cont ID  
Sent By adarroug Date 2005-02-01 Time 16:26 Rev Time 0.00
Received By adarroug Date 2005-02-01 Time 16:26 Sent To E
Notes
2005-02-01 00:00:00TO "BTROBAUG"DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 07:52 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 07:52 Sent To E
Notes
2005-01-06 00:00:00TO SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 12:12 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 12:12 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By prafter Date 2005-01-11 Time 14:18 Rev Time 0.45
Received By prafter Date 2005-01-11 Time 14:18 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-02-14 Cont ID  
Sent By kstevens Date 2005-02-14 Time 18:33 Rev Time 0.34
Received By kstevens Date 2005-02-14 Time 18:33 Sent To B1
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-11 Cont ID  
Sent By jleech Date 2005-01-11 Time 11:52 Rev Time 0.33
Received By jleech Date 2005-01-11 Time 11:52 Sent To M
Notes
2005-01-11 00:00:00DENIED;
 1.TUB IN BATH 3 IS NOT VENTED. WET VENT
 SHALL BE UPSTREAM OF THE WATER CLOSET.
 2.PLEASE CHANGE NOTE 3 TO COMPLY WITH
 FBC PLUMBING TABLE 704.1.
 3.PLEASE DELETE NOTE 6 A/C CONDENSATE IS
 NOT PERMITED TO DRAIN TO SANITARY.
 4.LAUNDRY TUB TO DRAIN ABOVE CLOTHES
 WASHER AND C.O> SHOULD BE 48" OF FINISH
 FLOOR
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-05 Cont ID  
Sent By mmclean Date 2005-01-05 Time 17:01 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 17:00 Sent To I
Notes
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK