Plan Review Details - Permit 04121926
Plan Review Stops For Permit 04121926
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-09-21 Cont ID  
Sent By jgomez Date 2005-09-21 Time 08:48 Rev Time 0.50
Received By jgomez Date 2005-09-21 Time 08:48 Sent To PC
Notes
2005-09-21 00:00:00BUILDING REVISION CHECKLIST:
 1- STORM SHUTTERS KEY PLAN DOESN'T MATCH
 FLOOR PLANS. REVISE AS REQUIRED.
  
 2- REVISE INSTALLATION SCHEDULE TO
 PROVIDE MINIMUM REQUIRED INFORMATION.
 SEE ATTACHED SAMPLE WHICH IS MORE
 COMPLETE THAN THE ONE SUBMITTED. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 3- CLEARLY MARK ON SHUTTER DRAWINGS
 SPECIFIC MOUNTING CONDITIONS AND ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING TO
 THE DESIGN PRESSURES, EDGE DISTANCE,
 PANEL SPAN, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO (CONCRETE OR
 CONCRETE BLOCK). SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 4- ACCORDING TO MAXIMUM PANEL SPAN CHART
 ON DRAWINGS 4 OF 7 OPENING #12 EXCEEDS
 THE MAXIMUM SPAN. REVISE AS REQUIRED.
 SECTION 104.2.1.2 CITY AMENDMENTS TO FBC
 2001.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-28 Cont ID  
Sent By jgomez Date 2005-04-28 Time 11:39 Rev Time 0.50
Received By jgomez Date 2005-04-28 Time 11:39 Sent To E
Notes
2005-04-28 00:00:00SUBMITTAL TO ADDRESS PROVISO DATED
 3-10-05. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-03-10 Cont ID  
Sent By jgomez Date 2005-03-10 Time 09:09 Rev Time 2.00
Received By jgomez Date 2005-03-10 Time 09:09 Sent To PC
Notes
2005-03-10 00:00:00BUILDING REVIEW PROVISO:
 PROVIDE INFORMATION PRIOR TO
 INSTALLATION OR CONSTRUCTION TO AVOID
 CONFLICTS OR DELAYS:
 1- PRODUCT APPROVAL FOR ENTRY DOORS.
 NOTE: ENTRY DOORS NEEDS TO BE SOLID OR
 TO HAVE IMPACT GLAZING BECAUSE IS USED
 FOR EMERGENCY EGRESS. NO SHUTTERS
 ALLOWED FOR ENTRY DOOR.
  
 2- UPDATE/REVISE TRUSS ANCHOR SCHEDULE
 AND CALCULATIONS IF CONNECTOR'S CAPACITY
 AND NUMBER OF NAILS DIFFER FROM THOSE
 TESTED AND PUBLISHED BY MANUFACTURER.
 **NOTE: CALCULATIONS NEED TO CONSIDER
 SEC. 1609.4.3 FBC 2001.
  
 3- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) USP CONNECTORS SPECIFIED ON PLANS AND
 TRUSS ANCHOR SCHEDULE.
  
 B) CASEMENT WINDOW ASSEMBLIES AS SHOWN
 ON PLANS (SEE BEDROOM #2).
  
 C) FRENCH DOORS WITH SIZE AND SWING
 DIRECTION AS SHOWN ON PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-21 Cont ID  
Sent By jgomez Date 2005-01-21 Time 16:44 Rev Time 3.00
Received By jgomez Date 2005-01-21 Time 16:43 Sent To B
Notes
2005-01-21 00:00:00BUILDING REVIEW CHECKLIST:
 1-PROVIDE COMPLETE BATHROOM WITH A DOOR
 THAT ALLOWS 29" MIN. CLEAR OPENING AS
 REQUIRED BY SEC. 11-11 OF FBC 2001.
  
 2-SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 104.2.1.1 OF CITY
 AMENDMENTS TO FBC 2001.
  
 3-UPDATE TRUSS ANCHOR SCHEDULE. PROVIDE
 COMPLETE ENGINEERING CALCULATIONS FOR
 TYPE AND NUMBER OF FASTENERS THAT
 DIFFER
 FROM THOSE TESTED AND PUBLISHED ON
 MANUFACTURER'S CATALOGUE REFLECTING NO
 STRESS INCREASE AS REQUIRED BY SECTION
 1609.4.3 FBC 2001.
  
 4-TITLE BLOCK TO HAVE ALL INFORMATION
 AS
 REQUIRED BY CHAPTER 481 FLORIDA
 STATUTES
 AND CHAPTER 61G1-16.004 OF
 ADMINISTRATIVE CODE. INCLUDING NAME OF
 ARCHITECT SEALING THE PLANS.
 ***ALSO, STATE REGISTRATION NUMBER IS
 INCORRECT. REVISE AS REQUIRED.
  
 5-PROVIDE COMPLETE
 DETAIL/SPECIFICATIONS
 FOR INSTALLATION OF CEILING AT ENTRY
 AND
 REAR PORCHES. SPECIFY FASTENERS TYPE
 AND
 SPACING AS REQUIRED BY ASTM C926 AND
 ASTM C1063. (SEC. 2504.2 FBC 2001.)
  
 6-ENERGY CALCULATIONS: OWNER/AGENT TO
 SIGN AND DATE BOTTOM OF FORM.
  
 7-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR ENTRY DOORS AND ALL
 EXTERIOR FRENCH DOORS. CHECK SIZES.
  
 8-STORM SHUTTERS: A)KEY PLAN DON'T
 MATCH
 PLANS.
 B)SEE ENGINEERED DRAWINGS FOR MIN.
 PANEL
 SIZE ALLOWED AND REVISEINSTALLATION
 SCHEDULE AS REQUIRED..
 C) INTERIORAND END ZONES SHOWN ON
 INSTALLATION SCHEUDLE ARE INCORRECT.
 SEE
 PLANS AND REVISE AS REQUIRED.
 D) REVISE DESIGN PRESSURES SHOWN ON THE
 INSTALLATION SCHEDULE. SEE PLANS..
  
 9-CONCRETE LINTELS PRODUCT APPROVAL:
 PROVIDE COPIES OF MIAMI-DADE NOA REPORT
 THAT WAS SUBMITTED FOR FLORIDA PRODUCT
 APPROVAL. REPORT SUBMITTED HERE IS NOT
 THE SAME. SEE INFORMATION ON FLORIDA
 WEBSITE WWW.FLORIDABUILDING.ORG.
  
 10-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR FIXED WINDOWS THAT MEET
 THE
 DESIGN PRESSURES CALCULATED ON PLANS.
  
 11-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR ARABESQUE WINDOW SHOWN ON
 FRONT ELEVATION.
  
 12-PROVIDE COMPLETE FRAMING DETAILS FOR
 ARABESQUE WINDOW. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 13-OWES $235.45 FOR UPDATED VALUATION.
  
 14-FOUNDATION NOTES ON SHEET A-2: REVISE
 NOTE #2. SEE CHAPTER 19 FBC 2001 FOR
 PROPER ACI REFERENCE.
  
 15-DETAIL 2/A-9: UPDATE CONNECTORS.
 SEMCO IS OUT OF BUSINESS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2005-09-22 Cont ID  
Sent By dpalmer Date 2005-09-22 Time 19:40 Rev Time 1.50
Received By dpalmer Date 2005-09-22 Time 19:39 Sent To P
Notes
2005-09-22 00:00:00TIME RELITIVE TO PHONE CALLS AND
 MEETINGS.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2005-09-20 Cont ID  
Sent By dpalmer Date 2005-09-20 Time 12:56 Rev Time 0.33
Received By dpalmer Date 2005-09-20 Time 12:56 Sent To P
Notes
2005-09-20 00:00:00******* UNSAT **********
  
 PLEASE SEE REVISIONS WILL BE COMING BACK
 FOR PLUMBING COMMENTS, PLEASE MAKE THE
 BELOW CORRECTIONS AT THIS TIME.
  
 1)NOTE: PLEASE SEE OCP FOR CON/A/C SYS
 #1 WAS INCREASED TO 60A'S, HOWEVER
 CONDUCTOR SIZE HAS NOT BEEN INCREASED.
 PLEASE SEE 310.16,240.4
  
 2)NOTE: PLEASE SEE DISHWASHER /DISPOSAL
 CIRCUIT HAS BEEN UPGRADED TO A 2-POLE
 BRKR, HOWEVER CIRCUITING ON PANEL
 SCHEDULE STILL SHOWS 1-POLE.
  
 3)NOTE;PLEASE SEE ITEMS ON PLANS WHICH
 INDICATE BEING "OPTIONAL". PLEASE REVISE
 TO INCLUDE ACTUAL INSTALLATION OF
 ELECTRICAL. IF AN APPLIANCE, THE
 APPLIANCE DOES NOT HAVE TO BE INSTALLED
 FOR ROUGH OR BEFORE FINAL.
 ONLY THE ELECTRICAL FOR THE EQUIPMENT IS
 TO BE SHOWN.
 PLEASE KNOW, ELECTRICAL FOR WASHER
 CIRCUIT CAN NOT BE OPTIONAL.
 210.52,210.11,220.16
  
 4)NOTE: PLEASE SEE LOCATION FOR POOL SUB
 PANEL SHOULD BE LOCATED TO MEET 110.26
 FOR MIN CLEARNECES.
 PLEASE SEE POOL EQUIPMENT WAS NOTED ON
 PREVIOUS PLANS AS TO BE MOVED TO EXACT
 LOCATION AT LATER DATE, HOWEVER THIS HAS
 NOTBEEN REVISED AS OF YET?
 110.26
  
 PLEASE SEE PLUMB COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-08-26 Cont ID  
Sent By dpalmer Date 2005-08-26 Time 19:09 Rev Time 0.33
Received By dpalmer Date 2005-08-26 Time 19:09 Sent To  
Notes
2005-08-26 00:00:00ELEC OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-07-15 Cont ID  
Sent By dpalmer Date 2005-07-15 Time 21:16 Rev Time 0.33
Received By dpalmer Date 2005-07-15 Time 21:16 Sent To  
Notes
2005-07-15 00:00:00REDLINED,
 NO LTS SHOWN IN MASTER BATH.
 MIN LT REQUIRED 210.70, LS 101 5-8

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-05-17 Cont ID  
Sent By dpalmer Date 2005-05-17 Time 11:59 Rev Time 0.30
Received By dpalmer Date 2005-05-17 Time 11:59 Sent To  
Notes
2005-05-17 00:00:00************ UNSAT ************
  
 **PLEASE SEE PLANS AND RISER DIAGRAM
 HAVE COMPLETELY CHANGED FROM ORIG PLANS.
  
 1)NOTE: PLEASE SEE NEW RISER NOW
 INDICATES THREE ELECTRICAL PANELS,
 HOWEVER NO OCP IS SHOWN ON RISER FOR NEW
 PANELS.
 IS THERE NOW A PANEL SCHEDULE FOR NEW
 METER/MAIN COMBO.
 215.5,240.4, 310.16 ETC.
  
 2)NOTE: PLEASE SEE ONLY ONE PANEL IS
 SHOWN ON ELECTRICAL PLANS AND RISER
 SHOWS 3.
 215.5
  
 3)NOTE: PLEASE SEE NUMEROUS ITEMS ON
 PANEL SCHEDULE INDICATE 20A OCP ON #14
 AWG. PLEASE SEE 310.16,240.4.
  
 4)NOTE: PLEASE CORRELATE AHU#2 HEAT
 STRIP WITH LOAD CALCULATIONS.
 PLEASE SEE PANEL SCHEDULE INDICATES 5KW,
 HOWEVER LOAD CALCS SHOW 10KW?
 215.5
  
 5)NOTE: PLEASE SEE A JACUZZI/WHIRLPOOL
 TUB IS NOW ADDED TO PANEL SCHEDULE,
 HOWEVER NO ELECTRICAL IS SHOWN ON PLANS.
 PLEASE ALSO SEE 680.71 FOR REQUIRED
 INDICATION OF GFI PROTECTION.
  
 6)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THE # OF
 RECESSED LTS INDICATED ON PANEL
 SCHEDULE/LOAD CALCULATIONS.
 215.5
  
 PLEASE SEE MANY OF THESE ITEMS HAVE BEEN
 REDLINED AT LOCATIONS ON PLANS AT
 LOCATIONS OF NOTES.
  
 *** PLEASE BE SURE ALL PLANS ARE SIGNED
 BY THE ARCHITECT OF RECORD.
 FS 481.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-05-05 Cont ID  
Sent By btrobaug Date 2005-05-05 Time 17:04 Rev Time 0.50
Received By btrobaug Date 2005-05-05 Time 12:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-28 Cont ID  
Sent By btrobaug Date 2005-02-28 Time 11:10 Rev Time 0.50
Received By btrobaug Date 2005-02-28 Time 10:54 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By btrobaug Date 2005-01-07 Time 11:49 Rev Time 0.50
Received By btrobaug Date 2005-01-07 Time 11:23 Sent To M
Notes
2005-01-07 00:00:00 
  
 .PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE OVERCURRENT PROTECTION FOR AHU
 #2 AT 60 AMPS IS TOO LARGE TO PROTECT A
 5KW UNIT.(5000X125%/240=26 AMPS, MAX 30
 AMP OCP). ALSO 60 AMP OCP SHOWN INTHE
 MAIN PANEL SEEM TOOLARGE FOR THE
 CONDENSING UNIT. SEE ARTICLE 440.22
 NEC.
  
 2} THERE ARE NO PROVISIONS IN THE
 CALCULATIONS FOR POOL EQUIPMENT, BUT
 THERE IS EQUIPMENT SHOWN ON THE PLAN.
  
 3} IF NOTE #15 IS ADHERED TO, THOSE
 CIRCUITS WOULD HAVE TO BE PROTECTED BY
 AN AFCI BECAUSE THE DETECTORS ARE
 LOCATED IN BEDROOMS. 210.12.
  
 4} THE GFI'S SHOWN IN THE DINING ROOM
 AND BREAKFAST NOOK, WHILE NOT REQUIRED
 ALTHOUGH PERMISSIBLE, MUST BE INSTALLED
 IF LEFT ON THE PLAN.
  
 5} A RECEPTACLE NEEDS TO BE ADDED TO
 THE
 MASTER BEDROOM TO COMPLY WITH
 210.52(A).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 10 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-09-16 Cont ID  
Sent By adarroug Date 2005-09-16 Time 16:59 Rev Time 0.00
Received By adarroug Date 2005-09-16 Time 16:59 Sent To E
Notes
2005-09-16 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-08-24 Cont ID  
Sent By adarroug Date 2005-08-24 Time 19:23 Rev Time 0.00
Received By adarroug Date 2005-08-24 Time 19:23 Sent To E
Notes
2005-08-24 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-08-23 Cont ID  
Sent By adarroug Date 2005-08-23 Time 18:18 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 18:18 Sent To B
Notes
2005-08-23 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-15 Cont ID  
Sent By adarroug Date 2005-07-15 Time 16:34 Rev Time 0.00
Received By adarroug Date 2005-07-15 Time 16:34 Sent To E
Notes
2005-07-15 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-04-18 Cont ID  
Sent By adarroug Date 2005-04-18 Time 09:46 Rev Time 0.00
Received By adarroug Date 2005-04-18 Time 09:46 Sent To B
Notes
2005-04-18 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-15 Cont ID  
Sent By adarroug Date 2005-04-15 Time 16:46 Rev Time 0.00
Received By adarroug Date 2005-04-15 Time 16:46 Sent To E
Notes
2005-04-15 00:00:00TO "BTROBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-15 Cont ID  
Sent By mmclean Date 2005-02-23 Time 11:01 Rev Time 0.00
Received By adarroug Date 2005-02-15 Time 09:25 Sent To E
Notes
2005-02-15 00:00:00TO "BTROBAUG" DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By btrobaug Date 2005-01-07 Time 12:05 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 07:50 Sent To E
Notes
2005-01-06 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 11:49 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 11:49 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By btrobaug Date 2005-01-07 Time 12:06 Rev Time 0.45
Received By prafter Date 2005-01-11 Time 15:47 Sent To B
Notes
2005-01-11 00:00:00ON A/C PLANS.
 PAT RAFTER 561/805/6725 OR 805/6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-24 Cont ID  
Sent By pschmitz Date 2005-09-24 Time 12:12 Rev Time 0.00
Received By pschmitz Date 2005-09-24 Time 12:12 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-10 Cont ID  
Sent By jleech Date 2005-01-10 Time 16:14 Rev Time 0.33
Received By jleech Date 2005-01-10 Time 16:14 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-02-23 Cont ID  
Sent By mmclean Date 2005-01-05 Time 12:08 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 12:08 Sent To I
Notes
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK