Plan Review Details - Permit 04121920
Plan Review Stops For Permit 04121920
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-10-03 Cont ID  
Sent By jgomez Date 2005-10-03 Time 10:58 Rev Time 0.50
Received By jgomez Date 2005-10-03 Time 10:58 Sent To PC
Notes
2005-10-03 00:00:00REVISION CHECKLIST:
 1- PROVIDE FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL FOR
 STORM SHUTTERS AS REQUIRED BY RULE 9B-72
 OF DCA. DADE COUNTY NOA ALONE IS NOT
 AUTOMATICALLY AN STATEWIDE PRODUCT
 APPROVAL. MANUFACTURER MAY APPLY FOR
 LOCAL PRODUCT APPROVAL USING THE DADE
 COUNTY NOA AND COMPLETING THE LOCAL
 PRODUCT APPROVAL FORM DOWNLOADED FROM
 DCA WEBSITE WWW.FLORIDABUILDING.ORG.
  
 2- KEY PLAN SHOWS THAT ENTRY DOOR WILL
 HAVE SHUTTERS. CONTRACTOR SPECIFIED THAT
 ENTRY DOOR WILL BE USED AS THE EMERGENCY
 EGRESS AND IS IMPACT RESISTANT. REVISE
 KEY PLAN AND INSTALLATION SCHEDULE
 SHOWING ENTRY DOOR AS EMERGENCY EGRESS
 WITH NO SHUTTERS.
  
 3- PROVIDE A COMPLETE INSTALLATION
 SCHEDULE WITH THE MINIMUM REQUIRED
 INFORMATION. SEE ATTACHED SAMPLE AND
 FILL COMPLETELY.
  
 4- PANELS FOR OPENING #14 EXCEED THE
 MAX. PANEL SPAN SHOWN ON DRAWING 4 OF 7.
 REVISE AS REQUIRED.
  
 5- THERE ARE TWO DIFFERENT SHUTTER TYPES
 SUBMITTED (DIFFERENT GAUGE). CLARIFY
 WHICH ONE IS GOING TO BE USED.
  
 6- INDICATE IN THE INSTALLATION SCHEDULE
 PAGE 5 OF 7 SPECIFIC ANCHOR TYPE AND
 SPACING TO BE USED. INFORMATION
 SUBMITTED SHOW THE ALL COLUMN BEING
 HIGHLIGHTED. INDICATE SPECIFIC ANCHOR
 THAT WILL BE USED IN THIS PROJECT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-28 Cont ID  
Sent By jgomez Date 2005-04-28 Time 10:43 Rev Time 0.50
Received By jgomez Date 2005-04-28 Time 10:43 Sent To E
Notes
2005-04-28 00:00:00BUILDING SUBMITTAL RESPONDING TO PROVISO
 DATED 3-2-05. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-03-02 Cont ID  
Sent By jgomez Date 2005-03-02 Time 15:42 Rev Time 3.00
Received By jgomez Date 2005-03-02 Time 15:42 Sent To PC
Notes
2005-03-02 00:00:00BUILDING REVIEW PROVISO:
 **NOTE: PROVIDE THE FOLLOWING
 INFORMATION PRIOR TO CONSTRUCTION OR
 INSTALLATION TO AVOID DELAYS/CONFLICTS:
 1- IF USING ENTRY DOOR FOR EGRESS AS
 REQUIRED BY SEC. 1005.4.5 FBC 2001 AND
 DOOR HAS GLAZING, THEN, GLAZING MUST BE
 IMPACT PROTECTED OR SOLID DOOR.
  
 2- UPDATE/REVISE TRUSS ANCHOR SCHEDULE
 AND CALCULATIONS IF CONNECTOR'S CAPACITY
 AND NUMBER OF NAILS DIFFER FROM THAT
 TESTED AND PUBLISHED BY MANUFACTURER.
 **NOTE: CALCULATIONS SHALL COMPLY WITH
 SECTION 1609.4.3 FBC 2001.
  
 3- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR USP CONNECTORS SPECIFIED ON
 TRUSS ANCHOR SCHEDULE. PAGE A-6.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-24 Cont ID  
Sent By jgomez Date 2005-01-24 Time 15:33 Rev Time 2.00
Received By jgomez Date 2005-01-24 Time 15:33 Sent To PC
Notes
2005-01-24 00:00:00BUILDING REVIEW CHECKLIST:
 1-PROVIDE COMPLETE BATHROOM WITH A DOOR
 THAT ALLOWS 29" MIN. CLEAR OPENING.
 SECTION 11-11 FBC 2001.
  
 2-SPECIFY ROOF TILE FASTENING. SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 3-UPDATE TRUSS ANCHOR SCHEDULE. PROVIDE
 COMPLETE ENGINEERING CALCULATIONS FOR
 TYPE AND NUMBER OF FASTENERS THAT
 DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER TO COMPLY WITH SEC.
 1609.4.3 FBC 2001.
  
 4- A)TITLE BLOCK NEEDS NAME OF
 ARCHITECT
 SEALING THE PLANS. SEE CHAPTER
 61G1-16004 FLORIDA ADMINISTRATIVE CODE.
 B) STATE REGISTRATION NUMBER IS
 INCORRECT. REVISE AS REQUIRED.
  
 5- PROVIDE COMPLETE DETAIL / SPECS FOR
 INSTALLATION OF CEILING AT ENTRY AND
 REAR PORCH. SPECIFY ALL FASTENERS AND
 SPACING. SEE ASTM C926 AND ASTM C1063.
 SEC. 2504.2 FBC 2001.
  
 6-ENERGY CALCULATIONS: OWNER/AGENT TO
 SIGN AND DATE BOTTOM OF FORM.
  
 7-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR: A) ENTRY DOORS.
 B) FRENCH DOORS. SEE SIZES ON PLANS.
 C) CONCRETE LINTELS: NEED DADE COUNTY
 NOA THAT MATCHES ONE SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
 D) FIXED WINDOWS THAT MEET THE DESIGN
 PRESSURES CALCULATED ON PLANS. SEE
 PLANS
 FOR SIZES AND DESIGN PRESSURES.
 E) ARABESQUE WINDOW AS SHOWN ON PLANS.
  
 8-A) PROVIDE COMPLETE UL LISTING AND
 SPECS FOR FIREPLACE.
 B) PROVIDE APPROVED BBQ SPECS.
  
 9- STORM SHUTTERS: A) KEY PLAN DOESN'T
 MATCH PLANS.
 B) REVISE MIN. PANEL SIZE. SEE
 ENGINEERED DRAWINGS.
 C) REVISE INTERIOR AND END ZONES. SEE
 PLANS FOR LOCATION.
 D) REVISE DESIGN PRESSURES. SEE PLANS.
  
 10-PROVIDE COMPLETE FRAMING DETAILS FOR
 ARABESQUE WINDOW. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 11-OWES $866.23 FOR UPDATED VALUATION.
  
 12-REVISE FOUNDATION NOTE #2 ON SHEET
 A-2: SEE CHAPTER 19 FBC 2001 FOR PROPER
 ACI REFERENCE.
  
 13-REVISE DETAIL CONNECTORS SHOWN ON
 DETAIL 2/A-9. "SEMCO" IS OUT OF
 BUSINESS
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-09-21 Cont ID  
Sent By dpalmer Date 2005-09-21 Time 16:30 Rev Time 1.25
Received By dpalmer Date 2005-09-21 Time 16:30 Sent To  
Notes
2005-09-21 00:00:00REV'S FOR FINAL.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-09-09 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 21:01 Rev Time 0.30
Received By dpalmer Date 2005-09-09 Time 20:58 Sent To  
Notes
2005-09-09 00:00:00RELDINED
  
 CORRELATE OCP, AWG AND KW RATING FOR
 AHU#2, 5KW ON 60A OCP , W/ #6 AWG?
  
 PLEASE SEE 2/0'S SHOWN FOR 150A PANELS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-05-18 Cont ID  
Sent By dpalmer Date 2005-05-18 Time 07:28 Rev Time 0.20
Received By dpalmer Date 2005-05-18 Time 07:28 Sent To  
Notes
2005-05-18 00:00:00************ UNSAT ************
  
 **PLEASE SEE PLANS AND RISER DIAGRAM
 HAVE COMPLETELY CHANGED FROM ORIG PLANS.
  
 1)NOTE: PLEASE SEE NEW RISER NOW
 INDICATES THREE ELECTRICAL PANELS,
 HOWEVER NO OCP IS SHOWN ON RISER FOR NEW
 PANELS.
 IS THERE NOW A PANEL SCHEDULE FOR NEW
 METER/MAIN COMBO.
 215.5,240.4, 310.16 ETC.
  
 2)NOTE: PLEASE SEE ONLY ONE PANEL IS
 SHOWN ON ELECTRICAL PLANS AND RISER
 SHOWS 3.
 215.5
  
 3)NOTE: PLEASE SEE NUMEROUS ITEMS ON
 PANEL SCHEDULE INDICATE 20A OCP ON #14
 AWG. PLEASE SEE 310.16,240.4.
  
 4)NOTE:
  
 5)NOTE: PLEASE SEE A JACUZZI/WHIRLPOOL
 TUB IS NOW ADDED TO PANEL SCHEDULE,
 HOWEVER NO ELECTRICAL IS SHOWN ON PLANS.
 PLEASE ALSO SEE 680.71 FOR REQUIRED
 INDICATION OF GFI PROTECTION.
  
 6)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THE # OF
 RECESSED LTS INDICATED ON PANEL
 SCHEDULE/LOAD CALCULATIONS.
 PLEASE SEE SOME MODELS SHOW THESE AS
 "OPT". EACH PLAN MUST REFLECT THE ACTUAL
 INSTALLATION PER WHICH ARE INSTALLED OR
 NOT INSTALLED.
 215.5
  
 7)NOTE:
  
 8)NOTE:
  
 PLEASE SEE MANY OF THESE ITEMS HAVE BEEN
 REDLINED AT LOCATIONS ON PLANS AT
 LOCATIONS OF NOTES.
  
 *** PLEASE BE SURE ALL PLANS ARE SIGNED
 BY THE ARCHITECT OF RECORD.
 FS 481.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-05-06 Cont ID  
Sent By btrobaug Date 2005-05-06 Time 12:07 Rev Time 0.50
Received By btrobaug Date 2005-05-06 Time 12:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-17 Cont ID  
Sent By btrobaug Date 2005-02-17 Time 09:02 Rev Time 0.50
Received By btrobaug Date 2005-02-17 Time 08:41 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By btrobaug Date 2005-01-07 Time 10:57 Rev Time 0.50
Received By btrobaug Date 2005-01-07 Time 10:46 Sent To M
Notes
2005-01-07 00:00:00 
  
 .PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE OVERCURRENT PROTECTION FOR AHU
 #2 AT 60 AMPS IS TOO LARGE TO PROTECT A
 5KW UNIT.(5000X125%/240=26 AMPS, MAX 30
 AMP OCP). ALSO 60 AMP OCP SHOWN INTHE
 MAIN PANEL SEEM TOOLARGE FOR THE
 CONDENSING UNIT. SEE ARTICLE 440.22
 NEC.
  
 2} THERE ARE NO PROVISIONS IN THE
 CALCULATIONS FOR POOL EQUIPMENT, BUT
 THERE IS EQUIPMENT SHOWN ON THE PLAN.
  
 3} IF NOTE #15 IS ADHERED TO, THOSE
 CIRCUITS WOULD HAVE TO BE PROTECTED BY
 AN AFCI BECAUSE THE DETECTORS ARE
 LOCATED IN BEDROOMS. 210.12.
  
 4} THE GFI'S SHOWN IN THE DINING ROOM
 AND BREAKFAST NOOK, WHILE NOT REQUIRED
 ALTHOUGH PERMISSIBLE, MUST BE INSTALLED
 IF LEFT ON THE PLAN.
  
 5} A RECEPTACLE NEEDS TO BE ADDED TO THE
 MASTER BEDROOM TO COMPLY WITH
 210.52(A).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-09-27 Cont ID  
Sent By adarroug Date 2005-09-27 Time 10:59 Rev Time 0.00
Received By adarroug Date 2005-09-27 Time 10:59 Sent To B
Notes
2005-09-27 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-04-18 Cont ID  
Sent By adarroug Date 2005-04-18 Time 09:48 Rev Time 0.00
Received By adarroug Date 2005-04-18 Time 09:48 Sent To B
Notes
2005-04-18 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-15 Cont ID  
Sent By adarroug Date 2005-04-15 Time 16:44 Rev Time 0.00
Received By adarroug Date 2005-04-15 Time 16:44 Sent To E
Notes
2005-04-15 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-14 Cont ID  
Sent By adarroug Date 2005-02-14 Time 16:06 Rev Time 0.00
Received By adarroug Date 2005-02-14 Time 16:06 Sent To E
Notes
2005-02-14 00:00:00TO BTROBAUG DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 08:24 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 08:24 Sent To E
Notes
2005-01-06 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 11:38 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 11:37 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By prafter Date 2005-01-11 Time 15:37 Rev Time 0.45
Received By prafter Date 2005-01-11 Time 15:37 Sent To B
Notes
2005-01-11 00:00:00NO A/C PLANS.
 PAT RAFTER 561/805/6725 OR 8056719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-10 Cont ID  
Sent By jleech Date 2005-01-10 Time 16:47 Rev Time 0.33
Received By jleech Date 2005-01-10 Time 16:47 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-05 Cont ID  
Sent By mmclean Date 2005-01-05 Time 18:40 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 18:40 Sent To I
Notes
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK