Plan Review Details - Permit 04121908
Plan Review Stops For Permit 04121908
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-02-14 Cont ID  
Sent By alange Date 2005-02-14 Time 14:21 Rev Time 1.00
Received By alange Date 2005-02-14 Time 14:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-20 Cont ID  
Sent By alange Date 2005-01-20 Time 11:25 Rev Time 0.00
Received By adarroug Date 2005-01-20 Time 16:01 Sent To  
Notes
2005-01-20 00:00:00DENIED
  
 1.BASED ON SBCCI BUILDING VALUATION
 DATA THE VALUE HAS BEEN CHANGED TO
 $335,607.ADDITIONAL PERMIT FEES OF
 $955.15 ARE DUE.
 SEE APPLICATION FOR COST BREAKDOWN.
  
 2.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 3.FOOTING DETAILS:THESE DETAILS
 SHOW A 12" DEEP FOOTING WITH A GRADE OF
 "APPROXIMATLY" 4".THESE ARE BOTH OK,
 THEY ARE BOTH MINIMUMS AND THIS LEAVES
 NO ROOM FOR ERROR OF GRADE.
 PLEASE REMOVE "APPROXIMATE" FROM PLANS
 AND SHOW AS "MINIMUM" GRADE 4" FROM
 FINISH FLOOR.WPB AMMENDMENT TO THE
 FBC
 1804.1.7
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-12-14 Cont ID  
Sent By btrobaug Date 2005-12-14 Time 09:20 Rev Time 0.50
Received By btrobaug Date 2005-12-14 Time 09:20 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-05-18 Cont ID  
Sent By dpalmer Date 2005-05-18 Time 06:28 Rev Time 0.20
Received By dpalmer Date 2005-05-18 Time 06:28 Sent To  
Notes
2005-05-18 00:00:00************ UNSAT ************
  
 **PLEASE SEE PLANS AND RISER DIAGRAM
 HAVE COMPLETELY CHANGED FROM ORIG PLANS.
  
 1)NOTE: PLEASE SEE NEW RISER NOW
 INDICATES THREE ELECTRICAL PANELS,
 HOWEVER NO OCP IS SHOWN ON RISER FOR NEW
 PANELS.
 IS THERE NOW A PANEL SCHEDULE FOR NEW
 METER/MAIN COMBO.
 215.5,240.4, 310.16 ETC.
  
 2)NOTE: PLEASE SEE ONLY ONE PANEL IS
 SHOWN ON ELECTRICAL PLANS AND RISER
 SHOWS 3.
 215.5
  
 3)NOTE: PLEASE SEE NUMEROUS ITEMS ON
 PANEL SCHEDULE INDICATE 20A OCP ON #14
 AWG. PLEASE SEE 310.16,240.4.
  
 4)NOTE:
  
 5)NOTE: PLEASE SEE A JACUZZI/WHIRLPOOL
 TUB IS NOW ADDED TO PANEL SCHEDULE,
 HOWEVER NO ELECTRICAL IS SHOWN ON PLANS.
 PLEASE ALSO SEE 680.71 FOR REQUIRED
 INDICATION OF GFI PROTECTION.
  
 6)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THE # OF
 RECESSED LTS INDICATED ON PANEL
 SCHEDULE/LOAD CALCULATIONS.
 PLEASE SEE SOME MODELS SHOW THESE AS
 "OPT". EACH PLAN MUST REFLECT THE ACTUAL
 INSTALLATION PER WHICH ARE INSTALLED OR
 NOT INSTALLED.
 215.5
  
 7)NOTE:
  
 8)NOTE:
  
 PLEASE SEE MANY OF THESE ITEMS HAVE BEEN
 REDLINED AT LOCATIONS ON PLANS AT
 LOCATIONS OF NOTES.
  
 *** PLEASE BE SURE ALL PLANS ARE SIGNED
 BY THE ARCHITECT OF RECORD.
 FS 481.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-07 Cont ID  
Sent By dpalmer Date 2005-02-07 Time 09:49 Rev Time 0.50
Received By dpalmer Date 2005-02-07 Time 09:15 Sent To B
Notes
2005-02-07 00:00:00REDLINED LOAD CALCULATIONS.
  
  
 TOTAL LOAD STILL SHOWN AT 101KW AND
 AFTER DERATING AND A/C, LOAD STILL SHOWN
 AT 247A'S.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By dpalmer Date 2005-01-07 Time 13:37 Rev Time 0.50
Received By dpalmer Date 2005-01-07 Time 13:37 Sent To M
Notes
2005-01-07 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN
 COUNTERSPACE GFI RECEPTS.
  
 2)NOTE: PLEASE SEE HI-HAT LOAD SHOWN AT
 48.0KW. PLEASE SEE 64@75W EACH.
 PLEASE SEE THIS MAY AFFECT SIZE OF
 SERVICE.
  
 3)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR PER 310.15B6,
 250.66
 #2 MIN. (IFF 300A SERVICE REMAINS. )
  
 4)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATESBRKFST NOOK AS GFI. THIS IS
 NOT REQUIRED,, YET PERMITTED. IF SHOWN
 ON PLANS THEN THIS IS REQUIRED TO BE
 DONE.
  
 5)NOTE: PLEASE CORRELATE RISER WITH
 PLANS. PLANS INDICATE METER/MAIN ON
 OUTSIDE OF HOUSE, PANEL IN GARAGE AND
 PANEL IN LAUNDRY RM?
 215.5
  
  
 6)NOTE: PLEASE SEE OCP IS NOT CLEAR ON
 PANEL SCHEDULE/LOAD CALCS FOR AHU 5KE
 HEAT. APPEARS TO BE 50A?
 PLEASE SEE 424.3B 125% MIN AND 150%
 USUALLY MAX. IS THIS 30A OCP?
 PLEASE ALSO SEE RISER SHOWS 60A OCP FOR
 COND UNITS. PLEASE VERIFY THE OCP WITH
 MECH PLANS FOR SIZE OF CU.
  
 7)NOTE: PLEASE SEE 210.52 FOR RECEPT
 LOCATIONS MISSING ON PLANS. BEDRM #2,
 #3, AND DEN.
  
 8)NOTE: PLEASE SEE PLANS INDICATE POOL
 EQUIPMENT, YET THIS IS NOT ON PANEL
 SCHEDULE. IF "FUTURE" PLEASE JUST PLACE
 NOTE ON PLANS FOR "FUTURE".
  
 PLEASE SEE ALL OF THESE ABOVE ITEMS HAVE
 BEEN REDLINED ON ONE SET OF PLANS FOR
 AREAS OF CONCERN.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD SET MAY BE SUBMITTED FOR
 REFERENCE ONLY.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-12-20 Cont ID  
Sent By adarroug Date 2005-12-20 Time 09:33 Rev Time 0.00
Received By adarroug Date 2005-12-20 Time 09:33 Sent To P
Notes
2005-12-20 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-08 Cont ID  
Sent By adarroug Date 2005-07-08 Time 16:04 Rev Time 0.00
Received By adarroug Date 2005-07-08 Time 16:04 Sent To P
Notes
2005-07-08 00:00:00TO "KSTEVENS" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-15 Cont ID  
Sent By adarroug Date 2005-04-15 Time 16:48 Rev Time 0.00
Received By adarroug Date 2005-04-15 Time 16:48 Sent To E
Notes
2005-04-15 00:00:00TO "BTROBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-01 Cont ID  
Sent By adarroug Date 2005-02-01 Time 16:09 Rev Time 0.00
Received By adarroug Date 2005-02-01 Time 16:09 Sent To E
Notes
2005-02-01 00:00:00TO "DP" DESK/RESUBMITT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 08:16 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 08:16 Sent To E
Notes
2005-01-06 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 11:04 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 11:04 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By prafter Date 2005-01-11 Time 12:36 Rev Time 0.45
Received By prafter Date 2005-01-11 Time 12:36 Sent To B
Notes
2005-01-11 00:00:00NO A/C PLANS.
 PAT RAFTER 561/805/6725 OR 805/6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-12-21 Cont ID  
Sent By jleech Date 2005-12-21 Time 13:47 Rev Time 0.50
Received By jleech Date 2005-12-21 Time 13:47 Sent To  
Notes
2005-12-21 00:00:00REVISED SANITARY RISER DIAGRAM OK

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-11 Cont ID  
Sent By jleech Date 2005-01-11 Time 10:36 Rev Time 0.33
Received By jleech Date 2005-01-11 Time 10:36 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-05 Cont ID  
Sent By mmclean Date 2005-01-05 Time 18:58 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 18:58 Sent To I
Notes
2005-01-20 00:00:00DENIED
  
 1.BASED ON SBCCI BUILDING VALUATION
 DATA THE VALUE HAS BEEN CHANGED TO
 $335,607.ADDITIONAL PERMIT FEES OF
 $955.15 ARE DUE.
 SEE APPLICATION FOR COST BREAKDOWN.
  
 2.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 3.FOOTING DETAILS:THESE DETAILS
 SHOW A 12" DEEP FOOTING WITH A GRADE OF
 "APPROXIMATLY" 4".THESE ARE BOTH OK,
 THEY ARE BOTH MINIMUMS AND THIS LEAVES
 NO ROOM FOR ERROR OF GRADE.
 PLEASE REMOVE "APPROXIMATE" FROM PLANS
 AND SHOW AS "MINIMUM" GRADE 4" FROM
 FINISH FLOOR.WPB AMMENDMENT TO THE
 FBC
 1804.1.7
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK