Plan Review Details - Permit 04121902
Plan Review Stops For Permit 04121902
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-07-12 Cont ID  
Sent By rmcdouga Date 2005-07-12 Time 09:56 Rev Time 0.00
Received By rmcdouga Date 2005-07-12 Time 07:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-05-18 Cont ID  
Sent By rmcdouga Date 2005-05-18 Time 09:35 Rev Time 0.00
Received By rmcdouga Date 2005-05-18 Time 07:16 Sent To P
Notes
2005-05-18 00:00:00DENIED BY BUILDING
  
 1) NOTICE OF COMMENCEMENT WILL HAVE TO
 BE RE-RECORDED. WORK ON THE PROJECT MUST
 BEGIN WITHIN 90 DAYS OF THE RECORDING
 DATE OR NOTICE BECOMES VOID. FS 713.13
  
 2) THE WRONG NOA REPORT WAS SUBMITTED
 FOR THE CASEMENT WINDOWS WITH FL#2766.
 THE CORRECT NOA IS #03-0612.05.
  
 3) SUBMIT STATE OR LOCAL PRODUCT
 APPROVAL FOR THE SINGLE AND DOUBLE
 OUTSWING GLAZED FRENCH DOORS.
  
 4) THE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS ARE
 INCORRECT. THE KEY PLAN DOES NOT MATCH
 THE FOOTPRINT OF THE STRUCTURE. THE
 SCHEDULE LISTS IMPACT RESISTANT WINDOWS.
 THE PRODUCT APPROVALS ARE FOR NON-IMPACT
 WINDOWS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-24 Cont ID  
Sent By rmcdouga Date 2005-01-24 Time 10:32 Rev Time 0.00
Received By rmcdouga Date 2005-01-24 Time 10:32 Sent To  
Notes
2005-01-24 00:00:00DENIED
  
 1) ONE OF THE WINDOWS IN BEDROOM #3
 SPECIFIED AS AN EGRESS WINDOW IS LABELED
 H33 SH, WHICH DOES NOT MEET EGRESS
 REQUIREMENTS OF FBC 1005.4.
  
 2) SUBMIT THE MANUFACTURER'S SPECS. AND
 LISTING INFORMATIONFOR TH BBQ AND PREFAB
 FIREPLACE.
  
 3) FBC 1007.8.1 REQUIRES STAIR WINDERS
 TO HAVE A MINIMUM TREAD DEPTH OF 6
 INCHES AT THE NARROW EDGE AND SHALL HAVE
 A MINIMUM TREAD DEPTH OF 11 INCHES AT A
 POINT 12 INCHES FROM THE NARROW EDGE.
  
 4) PROVIDE DETAILS OF THE HANDRAILS AND
 GUARD RAILS AT THE STAIRS. SEE FBC
 1007.5 AND 1015.
  
 5) SPECIFY THE WINDLOAD PRESSURES FOR
 THE 7' X 5' FIXED GLASS WINDOW AT THE
 BREAKFAST NOOK.
  
 6) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 ANCHOR BOLTS ON DETAIL 6 ON A7.
  
 7) THE DETAIL FOR THE WOOD FRAME WALL ON
 A8 SPECIFIES A USP RT16F AT THE BOTTOM
 OF THE WALL AND DETAIL 7 ON A12
 SPECIFIES A USP RT18F AT THE SAME
 LOCATION. PLEASE CLARIFY.
  
 8) THE GLASS BLOCK DETAIL ON A12
 INCORRECTLY REFERENCES ASCE 7-88. THE
 CORRECT REFERENCE IS ASCE 7-98.
  
 9) SECTIONS 1 AND 2 ON A 13 SPECIFY FIRE
 STOPS AT 8 INCHES ON CENTER. PLEASE
 CORRECT.
  
 10) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALC. FORMS PER FBC CHAPTER
 13.
  
 11) SUBMIT TWO COPIES OF A KEY PLAN FOR
 THE STORM PANELS.
  
 12) SUBMIT STATE/LOCAL PRODUCT APPROVALS
 FOR THE DOUBLE OUTSWING WOOD GLAZED
 DOORS AT THE ENTRY AND THE SINGLE
 OUTSWING GLAZED DOOR AT THE MASTER
 BEDROOM.
  
 13)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 14) THE PRODUCT APPROVAL SUBMITTED FOR
 THE MULLIONS DO NOT MEET THE REQUIRED
 PRESSURES FOR USE BETWEEN THE 12'
 SLIDING GLASS DOOR AND THE TRANSOM AT
 THE FAMILY ROOM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-03-10 Cont ID  
Sent By btrobaug Date 2006-03-10 Time 07:56 Rev Time 0.33
Received By btrobaug Date 2006-03-10 Time 07:29 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-02-27 Cont ID  
Sent By jleahy Date 2006-02-27 Time 09:52 Rev Time 0.45
Received By jleahy Date 2006-02-27 Time 09:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-11-12 Cont ID  
Sent By jleahy Date 2005-11-12 Time 21:13 Rev Time 0.30
Received By jleahy Date 2005-11-12 Time 21:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-12 Cont ID  
Sent By rmcdouga Date 2005-07-12 Time 09:57 Rev Time 0.00
Received By rmcdouga Date 2005-06-28 Time 12:11 Sent To  
Notes
2005-07-12 00:00:00OK PER B TROBAUGH 6/28/05

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-05-17 Cont ID  
Sent By btrobaug Date 2005-05-17 Time 11:54 Rev Time 0.50
Received By btrobaug Date 2005-05-17 Time 11:35 Sent To B
Notes
2005-05-17 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE LOCATION OF PANEL "B &
 C".
  
 2} INDICATE LOCATION OF OVERCURRENT
 PROTECTION FOR PANELS "A" & "B".
  
 3} THE OCP FOR CIRCUITS 16,17 PANEL "A",
 12,13,14,15 PANEL "B" IS TOO LARGE FOR
 THE CONDUCTORS PER 210.16.
  
 4} THE WHIRLPOOL IN THE MASTER BATH
 REQIURES GFI PROTECTION PER 680.71.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-06 Cont ID  
Sent By btrobaug Date 2005-01-06 Time 18:18 Rev Time 0.75
Received By btrobaug Date 2005-01-06 Time 17:15 Sent To M
Notes
2005-01-06 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE OVERCURRENT PROTECTION FOR AHU
 #2
 & #3 AT 60 AMPS IS TOO LARGE TO PROTECT
 A 5KW UNIT.(5000X125%/240=26 AMPS, MAX
 30 AMP OCP). ALSO 60 AMP OCP SHOWN IN
 THE MAIN PANEL SEEMS TOO LARGE FOR THE
 CONDENSING UNITS. SEE ARTICLE 440.22
 NEC.
  
 2} THERE ARE ONLY TWO A/C DISCONNECTS
 SHOWN ON THE RISER, BUT THREE UNITS ON
 THE PLAN AND IN THE CALC. PLEASE
 CORRELATE.
  
 3} THERE ARE NO PROVISIONS IN THE
 CALCULATIONS FOR POOL EQUIPMENT, BUT
 THERE IS EQUIPMENT SHOWN ON THE PLAN.
  
 4} IF NOTE #14 IS ADHERED TO, THOSE
 CIRCUITS WOULD HAVE TO BE PROTECTED BY
 AN AFCI BECAUSE THE DETECTORS ARE
 LOCATED IN BEDROOMS. 210.12.
  
 5} THE GFI'S SHOWN IN THE DINING ROOM
 AND BREAKFAST NOOK, WHILE NOT REQUIRED
 ALTHOUGH PERMISSIBLE, MUST BE INSTALLED
 IF LEFT ON THE PLAN.
  
 6} RECEPTACLES MUST BE ADDED TO THE
 MASTER SUITE AND HOBBY ROOM TO COMPLY
 WITH 210.52(A). SEE REVIEWED SET OF
 PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 15:47 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 15:47 Sent To E
Notes
2006-03-09 00:00:00TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-02-19 Cont ID  
Sent By adarroug Date 2006-02-19 Time 13:18 Rev Time 0.00
Received By adarroug Date 2006-02-19 Time 13:18 Sent To E
Notes
2006-02-19 00:00:00TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-10 Cont ID  
Sent By btrobaug Date 2005-11-10 Time 14:53 Rev Time 0.00
Received By btrobaug Date 2005-11-10 Time 14:53 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 14:24 Rev Time 0.00
Received By shill Date 2005-06-20 Time 14:24 Sent To E
Notes
2005-06-20 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-16 Cont ID  
Sent By adarroug Date 2005-05-16 Time 14:31 Rev Time 0.00
Received By adarroug Date 2005-05-16 Time 14:31 Sent To E
Notes
2005-05-16 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 08:18 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 08:18 Sent To E
Notes
2005-01-06 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 10:50 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 10:50 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By prafter Date 2005-01-11 Time 14:45 Rev Time 0.45
Received By prafter Date 2005-01-11 Time 14:45 Sent To B
Notes
2005-01-11 00:00:00NO A/C PLANS AND ONLY ONE ENERGY
 MANUALY J CAULK. .
 PAT RAFTER 561/805/6725 OR8056719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-07-09 Cont ID  
Sent By jleech Date 2005-07-09 Time 12:57 Rev Time 0.50
Received By jleech Date 2005-07-09 Time 12:57 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-05-28 Cont ID  
Sent By kstevens Date 2005-05-28 Time 17:34 Rev Time 0.33
Received By kstevens Date 2005-05-28 Time 17:34 Sent To  
Notes
2005-05-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT A-9 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A. CLEANOUT FOR THE WASH MACHINE SHALL
 BE LOCATED 4' ABOVE THE FLOOR. SECTION
 708.10.
 B. THE CABANA BATH IS NOT SHOWN ON THE
 RISER DIAGRAM. SECTION 104.2.1.
 C. THE FUTURE SINK PIPING IS UNCLEAR.
 PLEASE INDICATE IF IT WILL BE LEFT UNDER
 THE SLAB. IF NOT SHOW THE RISER AND
 INDICATE METHOD OF VENT. SECTIONS
 104.2.1. & 901.2.1.
 D. THE FITTING AT THE TOP OF THE RISER
 TO THE SECOND FLOOR DOES NOT DIRECT THE
 WASTE IN THE DIRECTION OF FLOW AS
 REQUIRED IN SECTION 706.3. SEE RED LINE
 EXAMPLE AT TOP OF RISER ONE SET OF
 PLANS.
 2. LOOSE SHEETS ARE NOT ACCEPTABLE.
 PLEASE SUBMIT 2 SETS OF PLANS PER
 SECTIONS 104.2.1, AND 104.2.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-11 Cont ID  
Sent By jleech Date 2005-01-11 Time 14:27 Rev Time 0.33
Received By jleech Date 2005-01-11 Time 14:27 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-05 Cont ID  
Sent By mmclean Date 2005-01-05 Time 18:54 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 18:54 Sent To I
Notes
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK